Hitachi WJ200 Series Quick Reference Manual page 77

Hide thumbs Also See for WJ200 Series:
Table of Contents
Output Function Summary Table – This table shows all functions for the logical outputs
(terminals [11], [12] and [AL]) at a glance. Detailed descriptions of these functions, related
parameters and settings, and example wiring diagrams are in "Using Intelligent Output
Terminals" in chapter 4.
Option
Terminal
Code
Symbol
RUN
Run Signal
00
FA1
Frequency Arrival Type
01
1–Constant Speed
FA2
Frequency Arrival Type
02
2–Over frequency
OL
Overload Advance
03
Notice Signal 1
OD
Output Deviation for PID
04
Control
AL
Alarm Signal
05
FA3
Frequency Arrival Type
06
3–Set frequency
OTQ
Over/under Torque
07
Signal
UV
Undervoltage
09
TRQ
Torque Limited Signal
10
RNT
Run Time Expired
11
ONT
Power ON time Expired
12
THM
Thermal Warning
13
BRK
Brake Release Signal
19
BER
Brake Error Signal
20
ZS
Zero Hz Speed
21
Detection Signal
Output Function Summary Table
Function Name
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Description
When the inverter is in Run Mode
When the inverter is in Stop Mode
When output to motor is at the set frequency
When output to motor is OFF, or in any
acceleration or deceleration ramp
When output to motor is at or above the set freq,
even if in accel (C042) or decel (C043) ramps
When output to motor is OFF, or at a level below
the set frequency
When output current is more than the set
threshold (C041) for the overload signal
When output current is less than the set threshold
for the deviation signal
When PID error is more than the set threshold for
the deviation signal
When PID error is less than the set threshold for
the deviation signal
When an alarm signal has occurred and has not
been cleared
When no alarm has occurred since the last
cleaning of alarm(s)
When output to motor is at the set frequency,
during accel (C042) and decel (C043).
When output to motor is OFF, or is not at a level of
the set frequency
Estimated motor torque exceeds the specified
level
Estimated motor torque is lower than the specified
level
Inverter is in Undervoltage
Inverter is not in Undervoltage
Torque limit function is executing
Torque limit function is not executing
Total running time of the inverter exceeds the
specified value
Total running time of the inverter does not exceed
the specified value
Total power ON time of the inverter exceeds the
specified value
Total power ON time of the inverter does not
exceed the specified value
Accumulated thermal count exceeds the C061 set
value
Accumulated thermal count does not exceed the
C061 set value
Output for brake release
No action for brake
Brake error has occurred
Brake performance is normal
Output frequency falls below the threshold
specified in C063
75