Ups Electrical Characteristics; Table 10 Ups Terminal - Emerson Liebert NX 10-30kVA Installation Manual

Liebert nx series 10-30kva, 208v, 60hz
Table of Contents
6.4

UPS Electrical Characteristics

Table 10
UPS terminal
Input (for single-input unit)
Nominal
Unit
Input
Rating
Current
10
28
15
42
20
56
30
83
Rectifier input (for dual input unit only)
Nominal
Unit
Input
Rating
Current
10
25
15
37
20
50
30
75
Bypass input (for dual input units)
Nominal
Unit
Input
Rating
Current
10
28
15
42
20
56
30
83
Output
Nominal
Unit
Output
Rating
Current
10
28
15
42
20
56
30
84
Battery
Unit
Battery
Rating
Current
10/15
55
20/30
110
Maximum
Input
OCP
Current
Current
35
42
53
63
70
84
104
125
Maximum
Input
OCP
Current
Current
31
37
47
57
63
76
94
113
OCP
OCP
Device
Current
Rating
35
35
53
60
70
70
104
110
OCP
Current
35
53
70
105
OCP
Current
55
110
OCP
Device
Rating
Bolt Size
45
6M (1/4")
70
6M (1/4")
90
6M (1/4")
125
6M (1/4")
OCP
Device
Rating
Bolt Size
40
6M (1/4")
60
6M (1/4")
80
6M (1/4")
125
6M (1/4")
Maximum Recommended Lug
Lug T&B
One Hole
Bolt Size
54000
6M (1/4")
54105
6M (1/4")
54106
6M (1/4")
54107
6M (1/4")
54152
OCP
Device
Rating
Bolt Size
35
6M (1/4")
60
6M (1/4")
70
6M (1/4")
110
6M (1/4")
OCP
Device
Rating
Bolt Size
70
6M (1/4")
125
8M (5/16")
39
UPS Specifications
Maximum Recommended Lug
Lug T&B
Lug T&B
One Hole 54000
One Hole REDDY
54105
62204
54106
62204
54107
62204
54152
62205
Maximum Recommended Lug
Lug T&B
Lug T&B
One Hole 54000
One Hole REDDY
54130
62204
54106
62204
54107
62204
54152
62205
Lug T&B
One Hole
REDDY
62204
62204
62204
62205
Maximum Recommended Lug
Lug T&B
Lug T&B
One Hole 54000
One Hole REDDY
54130
62204
54106
62204
54106
62204
54108
62205
Maximum Recommended Lug
Lug T&B
Lug T&B
One Hole 54000
One Hole REDDY
54106
62204
54153
62212

Hide quick links: