13. CHARACTERISTICS

13.5 Inrush currents at power-on of main circuit and control circuit

The following table indicates the inrush currents (reference value) that will flow when the maximum
permissible voltage (253VAC) is applied at the power supply capacity of 2500kVA and the wiring length of
1m.
Servo Amplifier
MR-J2S-10CP 20CP
MR-J2S-40CP 60CP
MR-J2S-70CP 100CP
MR-J2S-200CP 350CP
MR-J2S-500CP
MR-J2S-700CP
MR-J2S-10CP1 20CP1
MR-J2S-40CP1
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic
contactors. (Refer to section 14.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped
by an inrush current.
Main circuit power supply (L
30A (Attenuated to approx. 5A in 10ms)
30A (Attenuated to approx. 5A in 10ms)
54A (Attenuated to approx. 12A in 10ms)
120A (Attenuated to approx. 12A in 20ms)
44A (Attenuated to approx. 20A in 20ms)
88A (Attenuated to approx. 20A in 20ms)
59A (Attenuated to approx. 5A in 4ms)
72A (Attenuated to approx. 5A in 4ms)
Inrush Currents (A
0-p
, L
, L
)
Control circuit power supply (L
1
2
3
(Attenuated to approx. 0A in 0.5 to 1ms)
(Attenuated to approx. 0A in 0.5 to 1ms)
(Attenuated to approx. 0A in several ms)
(Attenuated to approx. 0A in 0.5 to 1ms)
13 - 7
)
11
70 to 100A
100 to 130A
30A
100 to 130A
, L
)
21