Emerson Rosemount FS-UVIR-975 Instruction Manual
Emerson Rosemount FS-UVIR-975 Instruction Manual

Emerson Rosemount FS-UVIR-975 Instruction Manual

Flame simulator for rosemount 975uf and 975ur
Hide thumbs Also See for Rosemount FS-UVIR-975:

Quick Links

INFORMATION FOLDER
Flame Simulator
FS-UVIR-975
Part no.
5100783-00A
This Information Folder Contains:
• FS-UVIR-975 Datasheet
• FS-UVIR-975 Manual
• FS-UVIR-975 Battery Saftey Data Sheet
The specifications described herein are subject to change without notice.
Data sheet no. DOC-002609
www.consilium.se
Table of Contents
loading

Summary of Contents for Emerson Rosemount FS-UVIR-975

  • Page 1 INFORMATION FOLDER Flame Simulator FS-UVIR-975 Part no. 5100783-00A This Information Folder Contains: • FS-UVIR-975 Datasheet • FS-UVIR-975 Manual • FS-UVIR-975 Battery Saftey Data Sheet The specifications described herein are subject to change without notice. Data sheet no. DOC-002609 www.consilium.se...
  • Page 2 FS-UVIR-975 Flame Simulator Product Data Sheet FGD-PDS-FS-UVIR-975-Flame-Simulator July 2016 FS-UVIR-975 Flame Simulator for Rosemount 975UF and 975UR ™ To be fully secure against fire, flame detector self-testing is not enough. According to most local jurisdictional authorities and as required for SIL2 compliance, you need to test and ensure the integrity of your entire flame detection system at least once per year.
  • Page 3 July 2016 FS-UVIR-975 Flame Simulator FS-UVIR-975 Flame Simulator at Work The Rosemount flame simulator emits UV and IR radiation in a unique pattern corresponding to, and recognizable as fire by your ™ Rosemount Flame Detector. This allows the detector to be tested under “real” fire conditions without the associated risks of an open flame.
  • Page 4 July 2016 FS-UVIR-975 Flame Simulator Specifications The Flame Simulator Kit, Part No. 00975-9000-0010 includes the FS-UVIR-975 flame simulator, battery, charger and user guide in carrying case. Table 1 - FS-UVIR-975 Flame Simulator Simulator Models Detector Types Detector Sensitivity Setting Min. Testing Distance Max.
  • Page 5 [email protected] ©2016 Emerson Process Management. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. All other marks are the property of their respective owners.
  • Page 6 User Manual 00809-0800-4975 Flame Simulator: FS-UVIR-975...
  • Page 7 Legal Notice The Flame Detector described in this document is the property of Rosemount. No part of the hardware, software, or documentation may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, without prior written permission of Rosemount. While great efforts have been made to ensure the accuracy and clarity of this document, Rosemount assumes no liability resulting from any omissions in this document of from misuse of the information obtained herein.
  • Page 8 Warranty Limited Warranty . Subject to the limitations contained in Section 10 (Limitation of Remedy and Liability) herein, Seller warrants that (a) the licensed firmware embodied in the Goods will execute the programming instructions provided by Seller; (b) that the Goods manufactured by Seller will be free from defects in materials or workmanship under normal use and care;...
  • Page 10: Table Of Contents

    Contents Contents Chapter 1 Introduction ........................1 Model and types ..........................1 Features and benefits ........................1 Principles of Operation ........................2 Simulator status ..........................2 Product Certification ........................3 Simulator structure ........................3 Certification instructions ........................ 7 Chapter 2 Operation Instructions ....................11 Ordering information ........................
  • Page 11 Contents...
  • Page 12: Chapter 1 Introduction

    Introduction Introduction To comply with local standards and jurisdictional authorities, end-to end loop testing of fire protection alarm systems, including detectors, should be performed periodically. Many safety authorities and plant managers of high value / high risk assets and facilities insist on quarterly end-to end testing of their entire fire protection systems using an external flame simulator.
  • Page 13: Principles Of Operation

    Introduction Principles of Operation The FS-UVIR-975 includes a halogen lamp that emits UV and IR energy. This energy is accumulated by a reflector directed towards the detector. The FS-UVIR-975 does not include a laser diode, only a mechanical sight; you can see the spot from the simulator and should aim the spot at the center of the detector.
  • Page 14: Product Certification

    Introduction Product Certification The Flame Simulator is certified to ATEX and IECEx Ex II 2 G D Ex d ib op is IIB + H T5 Gb Ex ib op is tb IIIC T135 °C Db -4 °F to 122 °F (-20 °C to 50 °C) This product is suitable for use in hazardous zones 1 and 2, zones 21 and 22 with IIB + H gas group vapor present.
  • Page 15 Introduction Figure 1-1: Flame simulator side view Electronic chamber Battery chamber Battery back cover Handle Reflector Push button Sight...
  • Page 16 Introduction Figure 1-2: Flame simulator rear view Handle Reflector Sight Back cover locking screw...
  • Page 17 Introduction Figure 1-3: Flame simulator front view Handle Push button Sight Laser diode...
  • Page 18: Certification Instructions

    Introduction Figure 1-4: Flame simulator front view Handle Push button Sight Certification instructions The marking of the equipment is: Ex II 2 G D Ex d ib op is IIB + H T5 Gb Ex ib op is tb IIIC T135 °C Db -4 °F to 122 °F (-20 °C to 50 °C) The manufacturer/importer/repair site is Rosemount Inc.
  • Page 19 Introduction Table 1-2: Minimum and maximum widths Flamepath description Type of joint Minimum width L (mm) Maximum gap ic (mm) Joint formed by window Flanged 10.75 0.02 against the enclosure Enclosure end-cap spigot Cylindrical 0.08 Gaps must not be machined to be any larger than the values of ic, and width must not be modified to be any smaller than the values of L shown in the table above.
  • Page 20 Introduction The certification of this equipment relies upon the following materials used in its construction Enclosure: aluminum 6061T6 Window: sapphire glass Seals: EPDM If the equipment is likely to come into contact with aggressive substances (described below), then it is your responsibility to take suitable precautions (described below) to prevent the equipment from being adversely affected, thus ensuring that the type of protection provided by the equipment is not compromised.
  • Page 21 Introduction...
  • Page 22: Chapter 2 Operation Instructions

    Operation Instructions Operation Instructions Ordering information The P/N of the Flame Simulator kit is 00975-9000-001000975-9000-000900975-9000-0013. The kit is supplied in a carry case that includes: Flame Simulator: FS-UVIR-975FS-IR-975FS-HR-975 Charger Tool kit Technical manual: 00809-0800-4975 00809-0500-497500809-0900-4975 Unpacking Verify that you have received the following content: •...
  • Page 23: Detection Ranges Per Detector / Flame Simulator

    Operation Instructions CAUTION! The following test simulates a real fire condition and may activate the extinguishing system or other alarms. If this is not desired, disconnect/inhibit them before the test and reconnect after the simulation. Procedure Verify that you are using the correct simulator that fits the tested detector per the following table: Table 2-1: Flame Simulator compatibility...
  • Page 24: Charging The Battery

    Operation Instructions Table 2-2: Detection ranges per detector / flame simulator (continued) Model Detector types Detector sensitivity Testing distance settings 200 ft. (60 m) 39.3 ft. (12 m) Notes • The minimum distance from the detector is 30 in. (75 cm). •...
  • Page 25: Replacing The Battery

    Operation Instructions Replacing the battery Place the Flame Simulator on a table in a safe area not exceeding 104 °F (40 °C). Release the locking screw (Item D, Figure 1-2). Unscrew the battery back cover (Item C, Figure 1-1). Unscrew the locking disc clockwise (Item C, Figure 2-1).
  • Page 26: Troubleshooting

    Operation Instructions WARNING! Use only Rosemount replacement battery pack, P/N 00975-9000-0012. Troubleshooting Table 2-3: Troubleshooting Model Problem Solution FS-IR-975FS-HR-975 Laser flashes 3 times. 1. Recharge the battery. Laser flashes 5 times. 1. Operate the Flame Simula- tor again. 2. Send the Flame Simulator for repair.
  • Page 27: Physical Specifications

    Operation Instructions Battery capacity: 2.2 AH Charging time: 2 hours at 2 A 2.9.3 Physical specifications Dimensions: 9 x 7.3 x 5.35 in. (230 x 185 x 136 mm) Weight: 5.5 lb. (2.5 kg) Enclosure: aluminum, heavy duty copper free, black zinc coating Explosion proof enclosure: ATEX and IECEx Ex II G D...
  • Page 28: Chapter 3 Technical Support

    Technical Support Technical Support For all technical assistance or support contact: Emerson Process Management 6021 Innovation Boulevard Shakopee, MN 55379-9795 U.S.A. T +1 866 347 3427 F +952 949 7001 [email protected]...
  • Page 29 Rosemount The Emerson logo is a trademark and service mark of Emerson 6021 Innovation Blvd. Electric Co. Rosemount is a mark of one of the Emerson Process Shakopee, MN 55379 Management family of companies. All other marks are the property Toll Free + 866 347 3427 of their respective owners.
  • Page 30 Spectrex Battery 380004 S AFETY HEET 1. IDENTIFICATION OF THE SUBSTANCE/PREPARATION AND OF THE COMPANY/UNDERTAKING Product Identification Product Name: Spectrex battery 380004 Nominal Voltage: 14.8V Nominal capacity: 2.2Ah Nominal Pack Wh: 32.56Wh Recommended Use The intended or recommended use of this preparation is as a Lithium-Ion battery. Supplier Information Address: Spectrex, Inc.
  • Page 31 Spectrex Battery 380004 S AFETY HEET Further Information For information purposes: (*) Main ingredients: Lithium hexafluorophosphate, organic carbonates Because of the cell structure the dangerous ingredients will not be available if used properly. During charge process a lithium graphite intercalation phase is formed. Mercury content: Hg <...
  • Page 32 Spectrex Battery 380004 S AFETY HEET Storage Requirements for storage rooms and vessels Storage at room temperature (approx. 20°C) at approx. 20~60% of the nominal capacity (OCV approx. 14.4 – 15.6 V/Pack). Keep in closed original container. 8. EXPOSURE CONTROLS/PERSONAL PROTECTION Ingredient Risk Codes Safety...
  • Page 33 Spectrex Battery 380004 S AFETY HEET R38,R11, mg/m3 (TWA) total dust and 5 mg/m3 (TWA) repairable fraction for Aluminum metal as Al - ACGIH Threshold Limit Value (TLV): 10 mg/m3 (TWA) Aluminum metal dusts Copper foil R11 R36 R37 R38 S5,S26,S16,S F(Highly Flammable) Copper Dust and Mists, as...
  • Page 34 Spectrex Battery 380004 S AFETY HEET 10. STABILITY AND REACTIVITY Stability Stable Conditions to avoid Keep away from open flames, hot surfaces and sources of ignition. Do not puncture, crush or incinerate. Materials to avoid No materials to be especially mentioned. Hazardous decomposition products In case of open cells, there is the possibility of hydrofluoric acid and carbon monoxide release.
  • Page 35 Spectrex Battery 380004 S AFETY HEET limited to the above mentioned. We further certify that the enclosed products have been tested and fulfilled the requirements and conditions in accordance with UN Recommendations (T1 – T8) on the Transport of Dangerous Goods Model Regulations and the Manual of Testes and Criteria. Test results of the UN Recommendation on the Transport of Dangerous Goods Manual of Test and Criteria Test...
  • Page 36 Spectrex Battery 380004 S AFETY HEET OTHER INFORMATION 16.1 Hazardous Materials Information Label (HMIS) Health: 0 Flammability: 0 Physical Hazard: 0 16.2 NFPA Hazard Ratings Health: 0 Flammability: 0 Reactivity: 0 Unique Hazard: 16.3 Full text of R-phrases referred to under sections 2 and 3 R10 Flammable.

This manual is also suitable for:

Rosemount fs-ir-975Rosemount fs-hr-975

Table of Contents