Commissioning; Function In Factory Settings; Location Of The Device Certificate Qr Code; Commissioning The Device - Siemens N 148/23 Manual

Ip interface secure
Hide thumbs Also See for N 148/23:
Table of Contents

6.1 Function in factory settings

6.2 Location of the device certificate QR code

6.3 Commissioning the device

A6V11689762_en--_d

6 Commissioning

In the factory settings, the configuration parameters are set as follows:
Physical address of IP Interface Secure: Setting: "15.15.255" (=FFFF hex)
Specifying the name and physical address of the device [➙ 12]
IP address assignment: Setting: "Obtain IP address automatically"
Assigning an IP address [➙ 12]
Fig. 3: Device certificate
The QR code of the device certificate is affixed to the device as a sticker. There is
a duplicate QR code, which can be removed for easy commissioning.
Commissioning the device with "KNX IP Secure"
w
A project is open in ETS.
1. Add the device to the project.
a
If the project is not yet password-protected, the 'Set project password' win-
dow appears.
2. Enter the password in the 'New password' and 'Confirm password' input fields,
then click 'OK' to confirm.
a
The 'Add device certificate' window appears.
3. If you have a webcam, press the '...' button and then scan the QR code sticker
on the device.
4. If you do not have a webcam or are unable to read the QR code, enter the 6x6-
character certificate key on the sticker on the device.
a
Once the certificate key has been entered correctly, a green checkmark ap-
pears at the end of the line. In addition, the serial numbers and the factory
key of the device are displayed.
Commissioning
Function in factory settings
6
11 | 18
Table of Contents
loading

Table of Contents