GE PROFINET PACSystems RX3i Quick Start Manual
GE PROFINET PACSystems RX3i Quick Start Manual

GE PROFINET PACSystems RX3i Quick Start Manual

Controller module
Hide thumbs Also See for PROFINET PACSystems RX3i:

Quick Links

GFK-2573K
February 2015
1
OK
2
LAN
3
STATUS
CONFIG
4
PNC001
TO INSTALL, TORQUE TO
6 IN-LB. TO UNINSTALL,
REVERSE MOTION
ACTIVE
USB
RESTART
!
IP ADDRESS
INTERFACE MAC
PORTS
FRONT
3 4
1 2
Ordering Information
IC695PNC001
PACSystems RX3i PROFINET Controller Module 10/100/1000, 4 Ports - 2 SFP connections, 2 Copper
IC200PNS001
VersaMax PROFINET Scanner, 10/100, 2 Ports, Copper
IC200PNS002
VersaMax PROFINET Scanner, 10/100, 2 Ports, Multimode Fiber
IC695PNS001
PACSystems RX3i PROFINET Scanner Module 10/100/1000 with four Ports (two SFP connections, two
Copper) - Includes a blank SD card, two mounting screws and a USB port cover
IC695SPC100
RX3i 10/100/1000base-TX (CAT5 100m) SFP
IC695SPF002
RX3i 100Base-FX (fiber 2 km) SFP
IC695SPF550
RX3i 1000Base-SX (fiber 550 m) SFP (MMF)
IC695SPF010
RX3i 1000Base-LX (fiber 10 km) SFP (Single mode fiber - SMF)
© 2015 General Electric Company. All Rights Reserved.
Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective
*
owners.
The PACSystems
RX3i PROFINET Controller (PNC) module, IC695PNC001, connects a
*
PACSystems RX3i controller to a high-speed PROFINET local area network. It enables the RX3i
controller to communicate with I/O-Devices on the LAN. The PNC provides all the functions,
services, and protocols required for certification as a PROFINET I/O Version 2.2 I/O Controller,
running at both 100 Mbps and 1 Gbps.
The PNC supports 10/100/1000 Mbps Copper, 100/1000 Mbps Multi-mode Fiber, and
100/1000 Mbps Single-mode Fiber. The LAN can include media interfaces of more than one
type. PROFINET communications on the LAN require 100 and 1000 Mbps link speed. 10 Mbps
cannot be used for PROFINET communications. However, 10 Mbps can be used for other
types of Ethernet traffic such as ping and telnet.
Features of the RX3i PNC include:
Full programming and configuration services for the PROFINET Controller, VersaMax
PROFINET Scanner and third-party I/O-Devices using Proficy* Machine Edition.
Firmware upgrades using the WinLoader software utility.
Built-in Command Line Interface function that provides direct monitoring and partial
configuration via the micro USB port or using telnet.
Note: The USB port is for system setup and diagnostics only. It is not intended for
permanent connection.
Support for star, ring, and daisy-chain/line network topologies.
Four switched Ethernet ports - two 8-conductor RJ-45 shielded twisted pair
10/100/1000 Mbps copper interfaces and two Small Form-factor Pluggable (SFP) cages
for user-supplied SFP devices.
Internal clock synchronized with the RX3i CPU for time-stamped diagnostics entries.
Restart pushbutton to manually restart the PNC without power cycling the system.
LEDs: OK, LAN, STATUS, CONFIG, ACTIVE, USB, and four Port LEDs.
Compliant with EU RoHS Directive using the following exemptions identified in the
Annex: 7c-I and 7c-III.
PACSystems* RX3i
IC695PNC001-AJ
PROFINET Controller Module
Table of Contents
loading

Summary of Contents for GE PROFINET PACSystems RX3i

  • Page 1 PACSystems* RX3i IC695PNC001-AJ PROFINET Controller Module GFK-2573K February 2015 The PACSystems RX3i PROFINET Controller (PNC) module, IC695PNC001, connects a PACSystems RX3i controller to a high-speed PROFINET local area network. It enables the RX3i controller to communicate with I/O-Devices on the LAN. The PNC provides all the functions, services, and protocols required for certification as a PROFINET I/O Version 2.2 I/O Controller, STATUS running at both 100 Mbps and 1 Gbps.
  • Page 2 IC695PNC001-AJ PROFINET Controller Module GFK-2573K PNC Specifications PROFINET Support PROFINET Version 2.2 General Class A I/O-Controller. Redundantly controlled operation conforms to PROFINET V2.3 Type S-2 System Redundancy. RX3i CPU Compatibility CPU315 or CPU320, with firmware version 7.0 or higher CPE305/CPE310 with firmware version 7.10 or higher Simplex or redundantly-controlled PROFINET I/O requires CRU320 release 8.40 or higher.
  • Page 3: Emc Installation Requirements

    References For additional information, please refer to the manuals listed below. Manuals can be downloaded from the Support website, http://support.ge-ip.com. GFK-2571, PACSystems RX3i PROFINET Controller Manual GFK-2572, PACSystems RX3i PROFINET Controller Command Line Interface Manual GFK-2721, VersaMax PROFINET Scanner User’s Manual...
  • Page 4: Status Reporting

    IC695PNC001-AJ PROFINET Controller Module GFK-2573K Status Reporting The PNC provides 32 bits of status information to a configured location in the RX3i CPU’s reference memory. The status data consists of the Module OK bit, which indicates the health of the module itself, a status bit for each external port, and a bit that indicates the connection status of the configured devices.
  • Page 5: Quick Start

    IC695PNC001-AJ PROFINET Controller Module GFK-2573K LEDs on the PROFINET Controller Module The table below summarizes LED functions. For detailed information about error indications and special blink patterns refer to Installation and Diagnostics in GFK-2571. Indicates whether the module is able to perform normal operation. Indicates network packets are being processed by the network interface (not just passing through the embedded switch).
  • Page 6 IC695PNC001-AJ PROFINET Controller Module GFK-2573K 4. Installing SFP devices Warning Optical SFPs use an invisible laser to generate a fiber-optic signal. Always keep the port covered if a cable is not installed. Do not look into the open port if a cable is not installed. Warning If the surrounding air operating temperature of the PNC is greater than 40°C,SFP devices could have operating temperatures over 70 °C (158 °F).
  • Page 7: Release History

    IC695PNC001-AJ PROFINET Controller Module GFK-2573K Release History Version Firmware Revision Date Comments IC695PNC001-AJ 2.11 Feb. 2015 Increased number of Profinet Devices that PNC can control from 64 to 128. Still limited to 63 devices in an MRP Ring if the PNC is the MRP Ring Manager.
  • Page 8 Upgrades The PNC can be field-upgraded to firmware version 2.11 using the Winloader firmware upgrade kit 82A1790-MS10-000-A9, which can be downloaded from http://support.ge-ip.com. Compatibility The following CPU firmware, programming software and backplane hardware versions are required to use the features introduced in PNC release 2.11 and later:...
  • Page 9 IC695PNC001-AJ PROFINET Controller Module GFK-2573K Restrictions and Open Issues Restrictions and Open Issues related to PNC Operational Behavior Issue Description There are 2 scenarios that can cause the PNC to indicate that an MRP Ring is closed PNC indicates premature MRP Ring when in fact it is still open.
  • Page 10 IC695PNC001-AJ PROFINET Controller Module GFK-2573K Issue Description Unexpected Loss of Device faults Loss of Device faults for currently connected devices may appear in the PLC I/O Fault table and/or PNC local log when the PNC is reset via its reset pushbutton. Unintended operation of The power flow output of the PNIO_DEV_COMM function block provides validation PNIO_DEV_COMM function block...
  • Page 11 IC695PNC001-AJ PROFINET Controller Module GFK-2573K Restriction/Open Issues Description "telnetd" command response The CLI does not echo the new number of max connections in its response to the telnetd command. However, the command still functions properly, and updates the maximum number of telnet connections. "log details"...
  • Page 12: Operational Notes

    IC695PNC001-AJ PROFINET Controller Module GFK-2573K Operational Notes Operational Note Description Minimum I/O Update Rates for If your application requires the PROFINET I/O to operate in a bumpless fashion (no Bumpless Operation in a Ring Loss of Device faults and no defaulting of I/O) through a break in the ring, then the Topology I/O Update Rates of all of the devices in that ring must be no smaller than the Minimum I/O Update Rate described below.
  • Page 13 IC695PNC001-AJ PROFINET Controller Module GFK-2573K Operational Note Description Data packets arriving on ports When a network is configured for MRP operation, MRCs and Media Redundancy blocked by Media Redundancy Managers (MRMs) can put one of their ring ports into a “Blocking” state. MRP uses Protocol (MRP) still forwarded over this blocked port state to break the continuous ring and allow only MRP mirrored ports...

This manual is also suitable for:

Profinet ic695pnc001-aj

Table of Contents