D6412/D4412
Installer's Keypad & Installer Mode
13.2.2 Service Start/Service End Reports
After you enter your installer passcode and press Cmd 41 to enter the Installer's Mode, the panel sends a
Service Start report. When you exit the installer's mode, it sends a Service End Report.
13.3 Installer's Menu
13.3.1 Press [1] for Bell Test
The panel activates the Bell Time (1-5) and Alarm Output (1-8, 1-9, 1-10, 1-11, and 1-12.) functions for 3
seconds. See Outputs in the D6412/D4412 Program Entry Guide (P/N: 45351) for a complete description of
output functions.
13.3.2 Press [2] for Strobe Test
The panel activates the Strobe Output function (1-6) and waits for the installer to press the [Cmd] key to end the
test. If the installer fails to press the [Cmd] key within 20 minutes the panel automatically terminates the strobe
test.
13.3.3 Press [3] for Battery Test
The battery test causes the system to run on battery only for four minutes. If the battery voltage falls below 12.1
volts during the four minute test or if the battery is missing, the system restores AC power and displays a system
trouble at all keypads.
13.3.4 Press [4] for Test Report
When you press the [4] key, the panel will attempt to send a Test report. If there is a system trouble present at
the time of the test, the panel sends a Test, Off Normal report
The test report follows the routing for the Automatic Test report.
If the test communication is unsuccessful, the panel creates a system trouble and a communication failure.
This test report is the only report sent when the Installer Switch is closed. No other reports are sent
when the Installer Switch is closed.
IMPORTANT
13.3.5 Press [5] for Point Status
Pressing [5] displays the sensor loop status for the first location in the system. The location, area, point number,
and electrical status (open, short, or normal) are shown. See Locations in the D6412/D4412 Program Entry
Guide (P/N: 45351) for a complete description of the relationship between locations, areas, and points.
Pressing the [*] key advances the display to the status for the next point.
Pressing the [Cmd] key exits the Point Status mode.
45349D
JP1
AUXILIARY
Installer
Figure 45: Installer Switch
D6412/D4412 Installation Guide
Page 56
INSTALLER SWITCH
NORMAL (OPEN)
INSTALLER SWITCH
LOCKED (CLOSED)
© 2002 Radionics