Restore To Normal Operation After "Epo - Emergency Power Off" With Load Not Supplied - GE TLE 625 UL S2 User Manual

Table of Contents
7.1.4 Restore to normal operation after "EPO - Emergency Power Off" with Load not
supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
 "Q1 - UPS Output switch" MUST BE CLOSED.
 "External Battery Protections" MUST BE DISCONNECTED.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
View of the Synoptic Diagram after performed the
command "EPO - Emergency Power Off" with LOAD
NOT SUPPLIED.
1. Restore the "EPO -Emergency Power Off" button.
Press "MUTE" key to reset Alarm and Acoustical Alarm.
LED ALARM remains lit.
2. Perform the "Inverter OFF" command.
Perform the "Inverter OFF" command from the
screen: Commands 1 / Inverter / OFF.
Load is transferred to Utility by Automatic Bypass.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status
"LOAD SUPPLIED BY AUTOMATIC BYPASS".
Modifications reserved
GE_UPS_USM_TLE_SUL_M62_1M0_2US_V010.docx
Critical Power
Continue →
Page 64/92
User Manual TLE Series 625 - 750 - 1000 UL S2