Terminal Block Communication; Any Mode Shutdown - Emerson SolaHD S4K2UC Series User Manual

Industrial on-line ups 120 v, 700 va–3000 va
Table of Contents

5.3 Terminal Block Communication

The terminal block includes eight pins, as shown in Figure 26.
Figure 26: Terminal block layout

5.3.1 Any Mode Shutdown

The purpose of Any Mode Shutdown is to shut down the UPS output by turning o the recti er, inverter and static bypass
switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally and remotely, as described as follows:
Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2
Remote Any Mode Shutdown can be performed by a switch connected to Pin 1 and Pin 2 and mounted at a remote
location
NOTES:
Remote Power o will be performed either by NO or NC contact of Any Mode Shutdown, depending on the settings
in the con guration program.
A current-limited source for the optocoupler (+12 V dc, 50 mA) will be available from the UPS.
The connection to the UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.
WARNING
!
When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1 and Pin 2, the S4K2UC's
output can turn on automatically and without warning if the Pin 1 and Pin 2 connection is changed.
1
Any Mode
2
Shut Down
3
Battery Mode
4
Shut Down
5
Battery Mode
6
7
Low Battery
8
S4K2UC SERIES USER MANUAL | 33