5.3 Terminal Block Communication
The terminal block includes eight pins, as shown in Figure 26.
Figure 26: Terminal block layout
5.3.1 Any Mode Shutdown
The purpose of Any Mode Shutdown is to shut down the UPS output by turning o the recti er, inverter and static bypass
switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally and remotely, as described as follows:
Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2
•
Remote Any Mode Shutdown can be performed by a switch connected to Pin 1 and Pin 2 and mounted at a remote
•
location
NOTES:
Remote Power o will be performed either by NO or NC contact of Any Mode Shutdown, depending on the settings
•
in the con guration program.
A current-limited source for the optocoupler (+12 V dc, 50 mA) will be available from the UPS.
•
The connection to the UPS for remote connection will be via terminal block connector.
•
Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.
•
WARNING
!
When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1 and Pin 2, the S4K2UC's
output can turn on automatically and without warning if the Pin 1 and Pin 2 connection is changed.
1
Any Mode
2
Shut Down
3
Battery Mode
4
Shut Down
5
Battery Mode
6
7
Low Battery
8