Preset-speed operation (speeds in 15 steps)

 -  : Preset-speed operation frequencies 1-7
 -  : Preset-speed operation frequencies 8-15
• Function
A maximum of 15 speed steps can be selected just by switching an external contact signal. Multi-speed
frequencies can be programmed anywhere from the lower limit frequency  to the upper limit frequency
 .
[Setting method]
1)
Run/stop
The starting and stopping control is done from the terminal board.
Title
Command mode selection

Note: When switching between preset-speed operation and other speed commands (analog signal, setting dial,
communication, etc.), select the frequency setting mode at  . ⇒ See 3) or 5.4 in E6581595
2)
Preset-speed frequency setting
Set the speed (frequency) of the number of steps necessary.
Setting from speed 1 to speed 7
Title
- 
Setting from speed 8 to speed 15
Title
f287- f294
Function
0: Terminal board
1: Panel keypad (including remote keypad)
2: RS485 communication
Funtion
Preset-speed operation frequencies
1-7
Function
Preset-speed operation frequencies
8-15
C-21
Adjustment range
Adjustment range
-  (Hz)
Adjustment range
-  (Hz)
E6581595
3
Setting value
0
Standard defaults
0.0
Standard defaults
0.0