Environmental Conditions; Safety Integrity Level - ABB TZIDC Manual

Digital positioner
Table of Contents
14
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G
... Specification
Communication
HART protocol 5.9 (standard); optionally HART®7.4
Local connector for LCI adapter
(not in explosion protection area)
HART communication via 4 to 20 mA signal line with HART
compatible modem.

Environmental conditions

Ambient temperature range
During operation, storage, and
transport
Limit monitor with proximity switches
SJ2-SN
TZIDC remote sensor
*
Increased temperature range only with TZIDC Remote Sensor.
Relative humidity
During operation with housing closed
and air supply switched on
Transport and storage
−40 to 85 °C (−40 to 185 °F)
−25 to 85 °C (−13 to 185 °F)
−40 to 100 °C (−40 to 212 °F)
95 % (annual average),
condensation permissible
75 % (annual average)

Safety Integrity Level

Applies to applications with single-acting and depressurizing
pneumatics.
The positioner meets the following requirements:
functional safety in accordance with IEC 61508
Explosion protection (depending on the version)
Electromagnetic compatibility in accordance with EN
61000
Without the input signal, the pneumatic module in the
positioner vents the actuator and the spring installed in it
moves the valve to a predetermined end position (OPEN or
CLOSED).
SIL specific safety-related characteristics:
Product
SSF
TZIDC with supply current
94 %
0 mA
For details refer to the Management Summary in the SIL
Safety Instructions 37/18-79XA.
PFDav
λdd + λs
λdu
1.76 * 10-4
651 FIT
40 FIT