8.4.4 To determine the complete recharge amount
8.4.5 To charge additional refrigerant
8.4.6 To fix the fluorinated greenhouse gases label
ERGA04~08E + EHVH04+08SU18+23E
Daikin Altherma 3 R F
4P629090-1C – 2022.08
If the total liquid piping
length is...
≤10 m
>10 m
INFORMATION
Piping length is the one-way length of liquid piping.
INFORMATION
If a complete recharge is necessary, the total refrigerant charge is: the factory
refrigerant charge (see unit name plate) + the determined additional amount.
WARNING
▪
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
▪
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
▪
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is
connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to the service port.
2 Charge the additional refrigerant amount.
3 Open the gas stop valve.
If pump down is needed in case of dismantling or relocating the system, see
4
"15.2 To pump
down" [
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
f
GWP: XXX
2
1
1
+
GWP × kg
1000
a If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
Do NOT add additional refrigerant.
R=(total length (m) of liquid piping – 1 0 m)×0.020
R=Additional charge (kg) (rounded in units of
0.01 kg)
263] for more details.
a
kg
b
1
=
kg
c
2
=
d
kg
2
=
=
e
tCO
eq
2
8
Piping installation
|
Then...
Installer reference guide
95