HPE T750 G4 UPS, T1000 G4 UPS, and T1500 G4 UPS User Guide Abstract This document is for the person who installs, administers, and troubleshoots power products. Hewlett Packard Enterprise assumes you are qualified in the servicing of high-voltage equipment and trained in recognizing hazards in products with hazardous energy levels.
Page 2
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. The Tower UPS models that are covered in this manual are intended for installation in an environment within 0 to 40°C/32 to 100°F, free of conductive contaminant.
Page 3
Personal Safety • The system has an internal battery as a backup power source. Consequently, the power outlets may be energized, even if the system is disconnected from the AC power source. • Dangerous voltage levels are present within the system. It should be opened exclusively by qualified service personnel.
1. Overview Save these instructions. This document contains important safety instructions that should be followed during installation, operation, and maintenance of the UPS and batteries. 1.1 Environmental protection Products are developed according to an eco-design approach. Substances This product does not contain CFCs, HCFCs, or asbestos. Packing To improve waste treatment and facilitate recycling, separate the various packing components.
Dimensions (mm/inch) (kg/lb) D x W x H HPE T750 G4 NA/JP UPS 10.9 kg/24 lb. 345 x 150 x 231 mm/13.6 x 5.9 x 9.1 in. HPE T1000 G4 NA/JP UPS 11.3 kg/25 lb. 345 x 150 x 231 mm/13.6 x 5.9 x 9.1 in.
Page 7
1. Overview HPE T750 G4 INTL UPS HPE T1000 G4 INTL UPS RS232 RS232 OUTPUT OUTPUT OUTPUT INPUT INPUT Refer to the Bottom of Refer to the Bottom of the unit for caution markings! the unit for caution markings! HPE T1500 G4 INTL UPS...
2. User Interface 2.1 Control panel The UPS has a three-button control panel. On/Off button Scroll Mute alarm 2.2 LCD window The LCD window provides useful information about the UPS, load status, events, measurements, and settings. UPS on line mode AVR (Automatic Voltage Regulation ) mode Battery mode...
Release the scroll down button to select a menu. Output voltage Alarm Sensitivity Tower UPS HPE T750 G4 INTL UPS, HPE T1000 G4 INTL UPS, HPE T1500 G4 INTL UPS Release the scroll down button to select a menu. Output voltage Alarm Sensitivity Note: In Lo (low sensitivity) mode, the UPS will tolerate more fluctuations in power and goes on battery power less often.
3.1 Unpacking and contents check (1) HPE Tower UPS (2) Documentation (4) Two connection cables for protected equipment (HPE T750 G4 INTL UPS, HPE T1000 G4 INTL UPS, HPE T1500 G4 INTL UPS)(5) RS-232 communication cable (6) USB communication cable Packing materials must be disposed of in compliance with all local regulations concerning waste.
3. Installation 3.3 Communication ports Connection of RS-232 or USB communication port The RS-232 and USB communication ports cannot operate simultaneously. Connect the RS-232 or USB communication cable to the serial or USB port on the computer equipment. Connect the other end of the communication cable to the USB or RS-232 communication...
4. Operation 4.1 Start-up and normal operation To start the UPS: 1. Verify that the UPS power cord is plugged in. 2. Press the button on the UPS control panel for at least two seconds. 3. Check the UPS LCD window display for active alarms. If the indicator is on, do not proceed until all alarms are cleared.
5. Maintenance 5.1 Troubleshooting Operation status Possible cause Action Overload Power requirement exceeds the UPS Remove some of the equipment from capacity (greater than 105% of nominal). the UPS. The UPS continues to operate, but may shutdown if the load increases. The alarm resets when the condition becomes inactive.
Page 14
Minimize the amount of time the UPS uses battery power by matching the UPS configuration with the utility voltage (see "6.1 HPE T750 G4 NA/JP UPS, HPE T1000 G4 NA/JP UPS, and HPE T1500 G4 NA/JP UPS", page 16 and "6.2 HPE T750 G4 INTL UPS, HPE T1000 G4 INTL UPS, and HPE T1500 G4 INTL UPS", page 17).
5. Maintenance Battery tray removal (cont.) Remove the plastic protection cover in front of the battery. Pull the plastic tab to remove the battery block and replace the block. Installing the new battery module Perform the removal instructions in reverse order. ●...
Support and other resources Accessing Hewlett Packard Enterprise Support For live assistance, go to the Contact Hewlett Packard Enterprise Worldwide website (http://www.hpe.com/assistance). To access documentation and support services, go to the Hewlett Packard Enterprise Support Center website (http://www.hpe.com/support/hpesc). Information to collect ...
Page 19
Customer self repair Hewlett Packard Enterprise customer self repair (CSR) programs allow you to repair your product. If a CSR part needs to be replaced, it will be shipped directly to you so that you can install it at your convenience. Some parts do not qualify for CSR.
Page 20
Additional warranty information HPE ProLiant and x86 Servers and Options www.hpe.com/support/ProLiantServers- Warranties HPE Enterprise Servers www.hpe.com/support/EnterpriseServers-Warranties HPE Storage Products www.hpe.com/support/Storage-Warranties HPE Networking Products www.hpe.com/support/Networking-Warranties Regulatory information To view the regulatory information for your product, view the Safety and Compliance Information for Server, Storage, Power, Networking, and Rack Products, available at the Hewlett Packard Enterprise Support Center: www.hpe.com/support/Safety-Compliance-EnterpriseProducts Additional regulatory information...