HP 204451-002 - UPS T2200 XR Best Practices Manual

HP 204451-002 - UPS T2200 XR Best Practices Manual

Hp ups best practices
HP UPS Best Practices
Abstract......................................................................................................................................... 2
Introduction ................................................................................................................................... 2
The Importance of Power Protection ............................................................................................ 2
Recommended Duration of Use.................................................................................................... 2
Battery Replacement .................................................................................................................... 3
Select Load Appropriately / Sizing A UPS .................................................................................... 3
Select Application Voltage / High volt VS Low Volt (120V or 208V) ............................................. 3
HP UPS Management................................................................................................................... 4
HP Power Manager Software.................................................................................................... 4
HP Management Module (AF401A) .......................................................................................... 5
Rackmount UPS Model Numbers ............................................................................................. 6
Tower UPS Model Numbers ..................................................................................................... 6
UPS Options ............................................................................................................................. 6
HP Rackmount UPS Advantages ................................................................................................. 6
HP Rackmount UPS Models......................................................................................................... 8
HP R1500 G2 Rackmount UPS ................................................................................................ 8
HP R3000 Rackmount UPS ...................................................................................................... 8
HP R/T3000 Rackmount UPS................................................................................................... 9
HP R5500 Rackmount UPS .................................................................................................... 10
HP Three-phase Rack-mountable UPS .................................................................................. 11
HP Tower UPS Advantages........................................................................................................ 12
HP Tower UPS Models ............................................................................................................... 13
HP T750 G2 UPS.................................................................................................................... 13
HP T1000 G3 and T1500 G3 UPSs ........................................................................................ 13
HP T750 Japan T1000 Japan and T1500 Japan UPSs .......................................................... 13
Run Time per HP UPS Model ..................................................................................................... 14
Recommended Power Distribution Units (PDU) ......................................................................... 16
Avoiding Potential Glitches ......................................................................................................... 18
Worldwide Power Requirements................................................................................................. 19
UPS/PDU power cord plug/receptacle reference........................................................................ 22
Additional Information ................................................................................................................. 27
The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth
in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting
an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.
Page 1 of 27
Table of Contents
loading

Summary of Contents for HP 204451-002 - UPS T2200 XR

  • Page 1: Table Of Contents

    HP UPS Best Practices Abstract............................2 Introduction ........................... 2 The Importance of Power Protection .................... 2 Recommended Duration of Use....................2 Battery Replacement ........................3 Select Load Appropriately / Sizing A UPS ..................3 Select Application Voltage / High volt VS Low Volt (120V or 208V) ..........3 HP UPS Management........................
  • Page 2: Abstract

    Abstract This document describes best practices to properly deploy a HP Uninterruptible Power System (UPS) in order to deliver maximum functionality at minimum cost. All HP UPSs are designed to provide superior power protection to servers and other critical electronic equipment, with Rackmount UPS models also preserving valuable rack space.
  • Page 3: Battery Replacement

    Battery Replacement It is best practice to replace the batteries every three years to ensure that the load will be properly supported during power outages, especially during high load conditions. There are a number of conditions that affect battery life, including temperature and the depth and frequency of battery discharges.
  • Page 4: Hp Ups Management

    HP UPS Management HP Power Manager Software HP Power Manager is a web-based application that enables administrators to manage an HP UPS from a browser-based management console. Administrators can monitor, manage and control a single UPS locally and remotely. Use HP Power Manager 4.2.5 or higher. http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/software/power-manager/index.html Power Management Software is a Must on All UPS Allows for Graceful Shutdown...
  • Page 5: Hp Management Module (Af401A)

    HP Management Module (AF401A) The HP UPS Management Module enables you to monitor, manage, and control power environments of up to five devices through the serial connectors located on the front of the management module (local direct connection) and more remote devices over the network connection. The management module can be configured to send alert traps to HP Systems Insight Manager and other SNMP management programs or used as a stand-alone management system.
  • Page 6: Rackmount Ups Model Numbers

    HP UPS Models Available Rackmount UPS Model Numbers Tower UPS Model Numbers AF419A R1500 G2 NA AF446A T750 G2 NA AF418A R1500 G2 INTL AF447A T750 G2 INTL AF421A R1500 G2 JPN/TWN AF456A T750 JAPAN AF422A R3000 Low Volt NA AF448A T1000 G3 NA AF423A...
  • Page 7: Power Management Software

    Preserves Valuable Rack Space  R1500 G2 occupies just 1U (1.75 inches) of rack space; R3000 models occupy just 2U (3.5 inches); and R5500 occupies only 3U (5.25 inches), leaving more space for server and storage equipment Industry-leading Power Density ...
  • Page 8: Hp Rackmount Ups Models

    HP Rackmount UPS Models HP R1500 G2 Rackmount UPS The HP R1500 G2 UPS is a high power-density solution designed for customers desiring power protection in space-constrained rack environments. Offering 1500VA/1050Watts of protection, the R1500 G2 occupies just 1U of valuable rack space, while delivering key benefits such as Enhanced Battery Management, Load Segment Control, and serial and USB ports for data exchange.
  • Page 9: Hp R/T3000 Rackmount Ups

    HP R/T3000 Rackmount UPS The new HP R/T3000 Uninterruptible Power System (UPS) packs up to 3000 watts into a space saving 2U design. Proven Digital Signal Processor (DSP) technology clean, reliable power protection in an energy efficient transformer-less design while reducing generated heat. The HP R/T3000 UPS includes a Rack to Tower Conversion Kit for non rack applications outside the data center or to support multiple tower servers, wiring closets, and blade enclosures such as the HP c3000 BladeSystem.
  • Page 10: Hp R5500 Rackmount Ups

    HP R5500 Rackmount UPS The R5500 UPS provides more power protection per U than any other HP UPS, and supports any rackmount server application requiring up to 4500 watts of power protection. With two load segments and free HP power management software, it is easy to customize this UPS to specific applications, as well as manage systems remotely.
  • Page 11: Hp Three-Phase Rack-Mountable Ups

    HP Three-phase Rack-mountable UPS The HP three-phase, UPS line delivers industry-leading energy efficiency, scalability and flexibility. With 12kVA/12kW modules that occupy just 6U of valuable rack space, the HP three-phase UPS line features twice the power density of any comparable product on the market. Furthermore, the scalable design of the UPS helps customers meet the changing demands of their data centers, as it can expand from the RP36KW model to RP60kW N+1 redundant system.
  • Page 12: Hp Tower Ups Advantages

    HP Tower UPS Advantages Providing advanced power protection and increased uptime for servers, storage devices, computer equipment, and other network environments, HP’s Tower UPS models are designed with a host of key benefits including:  Increased power rating to protect more equipment than competitive UPSs ...
  • Page 13: Hp Tower Ups Models

    HP Tower UPS Models HP T750 G2 UPS Ideal for small and medium businesses and desktop/workstation environments with power requirements of 750VA/500 watts and less, the HP T750 G2 delivers reliable protection for entry level servers, desktops, work stations and small peripherals. With serial and USB connectivity for multiple configuration options, the HP T750 G2 UPS provides four output receptacles.
  • Page 14: Run Time Per Hp Ups Model

    Run Time per HP UPS Model Backup times** (in minutes) T750 G2 and T750 Japan Load, percent Load, Watts Estimated battery runtime at 100% battery charge 15 minutes 100% 5 minutes T1000 G3 and T1000 Japan Load, percent Load, Watts Estimated battery runtime at 100% battery charge 15 minutes 100%...
  • Page 15 R5500 With Standby With 1 ERM With 3 ERMs Load (VA/W) With 2 ERMs † With 4 ERMs † Battery 1000/900 59 minutes 160 minutes 273 minutes 406 minutes 520 minutes 2000/1800 26 minutes 75 minutes 124 minutes 183 minutes 233 minutes 2200/1980 21 minutes...
  • Page 16: Recommended Power Distribution Units (Pdu)

    Recommended Power Distribution Units (PDU) UPS Model UPS Description PDU Model PDU Description Number Number AF419A R1500 G2 NA AF418A R1500 G2 INTL AF421A R1500 G2 JPN/TWN AF422A R3000 Low Volt NA 252663-D71 Single Phase Modular 2.8 kVA PDU + 4 extension bars AF423A R3000 High Volt NA...
  • Page 17 UPS Model UPS Description PDU Model PDU Description Number Number AF429A R12000/3 NA AF512A Three Phase Modular 8.6 kVA PDU AF504A Three Phase Monitored 8.6 kVA Single Input Full Rack Height AF503A Three Phase Monitored 17.3 kVA Dual Input Full Rack Height AF430A R12000/3 INTL AF513A x 2...
  • Page 18: Avoiding Potential Glitches

    Avoiding Potential Glitches 1. Configuring the HP software for delay before shutdown One must consider the run time required to gracefully shut down a system. Every server with its configured operating system (OS) and subsequent attached storage has a required time for shutdown, which must be taken into account when configuring the UPS software so sufficient battery life is allotted for the graceful shutdown of the attached equipment.
  • Page 19: Worldwide Power Requirements

    7. R12000/3 and the NC REPO connector This UPS has two kinds of REPO (remote emergency power off) options, NO (normally open) and NC (normally closed). The NC REPO connector must be installed for the UPS to function properly. Not installing the NC REPO is equivalent of a REPO signal being sent to the UPS.
  • Page 20 Page 20 of 27...
  • Page 21 Page 21 of 27...
  • Page 22: Ups/Pdu Power Cord Plug/Receptacle Reference

    UPS/PDU power cord plug/receptacle reference Rackmount UPS products HP R1500 G2 NA/JPN/TWN Input plug type Output receptacles Part number: AF419A / Low Voltage NEMA 5-15P 4 - Low Voltage NEMA 5-15R AF421A HP R1500 G2 UPS INTL Input receptacle type Output receptacles Part number: AF418A High Voltage IEC320 C14...
  • Page 23 HP R/T3000 low voltage Input plug type Output receptacles UPS NA/JPN Low Voltage NEMA L5-30P LS 1 - 2 - NEMA 5-20 Part number: AF452A LS 1 - 1 - NEMA L6-20R LS 2 - 2 - NEMA 5-20 HP R/T3000 high voltage Input plug type Output receptacles UPS NA/JPN...
  • Page 24 HP R8000/3 high voltage Input plug type Output receptacles UPS NA NEMA L21-30P 1 - NEMA L15-30 Part number: AF431A HP R8000/3 high voltage Input plug type Output receptacles UPS INTL IEC309 516P6 (16A) 1 - IEC309 516C6 (16A) Part number: AF432A HP R12000/3 high voltage Input plug type Output receptacles...
  • Page 25 HP RP36000/3 high voltage No Photo Available Receptacles on output modules UPS NA 2 - NEMA L15-30 Part number: AF438A HP RP36000/3 high voltage No Photo Available Receptacles on output modules UPS INTL 2 - IEC309 516C9 (16A) Part number: AF439A Page 25 of 27...
  • Page 26 Tower UPS products HP T750 G2 UPS NA Input plug type Output receptacles Part number: AF446A Low Voltage NEMA 5-15P 4 - Low Voltage NEMA 5-15R HP T750 G2 UPS INTL Input receptacle type Output receptacles Part number: AF447A High Voltage IEC320 C14 4 - High Voltage IEC320 C13 HP T750 UPS JAPAN Input plug type...
  • Page 27: Additional Information

    HP T1500 G3 UPS NA Input plug type Output receptacles Part number: AF450A Low Voltage NEMA 5-15P 6 - Low Voltage NEMA 5-15R HP T1500 G3 UPS INTL Input receptacle type Output receptacles Part number: AF451A High Voltage IEC320 C14 4 - High Voltage IEC320 C13 HP T1500 UPS JAPAN Input plug type...