Honeywell X47 Installation Manual

Universal relay pack

Quick Links

PN 292-118
X47 Universal Relay Pack
Installation Guide
Note: This picture is
for reference only.
The production
enclosure is
available only in
Warm Grey.
The X47 Universal Relay Pack (PN 201-147) is an INNCOM
Integrated Room Automation System (IRAS) device designed
for guestroom controls. The X47 provides five relay outputs
used to switch a variety of loads, including fan coil units
(FCU) and light-duty general loads. The X47 can integrate
with and receive data from multiple points throughout the
IRAS using low-voltage wired communication (S5bus),
infrared (IR) communication (when connected to IR Eye 5), or
radio frequency (RF) communication (when connected to a
PC502). The X47 comes in 24VAC (low-power) or 100-
277VAC (line-power) versions.
Installation
CAUTION!
!
The X47 is intended for indoor use only.
The X47 installer must be a trained, experienced
service technician.
All wiring must comply with local codes and
ordinances.
The X47 is intended for indoor use only.
Failure to follow the instructions provided with the
product could damage the product or cause a
hazardous condition.
Wiring
Figure 1 shows the X47 line-voltage and 24VAC connectors;
Figure 2 shows the communication headers; and Figure 3
shows a typical connection to an FCU.
Figure 2 X47 Headers
Figure 1 Connectors
Line-Voltage Connections: The phase (hot) and neutral
connections are defined on the product label.
Low-Voltage Power/Communications Connection: The
X47 can provide 12VDC 240mA output class-2 power and
S5bus for IRAS devices.
Figure 1 Communications Headers
Typical Fan Coil Unit Connections
FCU
HEAT
COOL
LOW FAN
MED FAN
M
HIGH FAN
NEUT/L2
*
LINE/L1
*Note: Typically Valve and Fan Power use L1/Line Power
Figure 3 Typical FCU Connections
Copyright 2013 INNCOM by Honeywell
Earth
X07
LOGIC BOARD
loading

Summary of Contents for Honeywell X47

  • Page 1 The production enclosure is available only in Warm Grey. The X47 Universal Relay Pack (PN 201-147) is an INNCOM Figure 1 Connectors Integrated Room Automation System (IRAS) device designed Line-Voltage Connections: The phase (hot) and neutral for guestroom controls. The X47 provides five relay outputs connections are defined on the product label.
  • Page 2 Table 2: X47 Relay Output Specifications, request toward the thermostat. 24VAC Input model The thermostat will send a Bind offer to the X47. If it is accepted, the thermostat will buzz multiple times. The X47 will reset. Typical Operation Pin Assignment 1.0A Sealed, 10A inrush,...
  • Page 3 Note: Current consumption values of the X47 with actuated relays should be deducted from class-2 output power rating in Table 3 in order not to overdrive the power supply. The X47 should not be used to provide more than 70mA of external...