24
3.3.5 Specification
Items
Input Specification
Inputs Per Module
Indicators
Sensor Types
Module Accuracy
(Need 20 minute
preheating to get enhanced
accuracy.)
Connection Method
Conversion Time
Data Format
Calibration
Specification
4 Channels
4 Green Input Status LEDs , 1 Green Input CJ Status LED
Thermal Couple Input Range
Type
Maximum Input Range
K
J
T
B
R
S
E
N
L
U
C
D
10uV Input
1uV Input
2uV Input
Recommend Input Range
±0.1% Recommended Scale @ 25℃ ambient
-
±0.3% Recommended Scale @ -40℃ ~ 70℃
-
C/D Type Recommend Input Range
±0.3% Recommended Scale @ -40℃ ~ 70℃
-
External Cold Junction(PT100)
± 2℃ Recommended Scale @ -40℃ ~ 70℃
-
2-Wire
Average Conversion Time < 30ms
16 Bits Integer (2' complement )
Not Required
Recommended Input Range
-270 ~ 1372℃
-210 ~ 1200℃
-270 ~ 400℃
30 ~ 1820℃
-50 ~ 1768℃
-50 ~ 1768℃
-270 ~ 1000℃
-270 ~ 1300℃
-200 ~ 900℃
-200 ~ 600℃
0 ~ 2310℃
0 ~ 2490℃
-81.0 ~ 81.0mV, 10uV/1 Count
-32.7 ~ 32.7mV, 1uV/1 Count
-65.5 ~ 65.5mV, 2uV/1 Count
HX-RIO3 Series
-200 ~1200℃
-40 ~ 1100℃
-200 ~ 350℃
600 ~ 1700℃
0 ~ 1600℃
0 ~ 1600℃
-200 ~ 800℃
-200 ~ 1250℃
-100 ~ 850℃
-100 ~ 550℃
100 ~ 2100℃
100 ~ 2200℃