2-26. Network converter for LonWorks

¢ Switch location
¢ Address setting
Following steps are necessary for setting address of Network converter.
For Touch panel controller, Central remote controller, Network converter for Group remote con-
troller, Modbus converter, and Network converter for LonWorks connected in same VRF network
system, set an exclusive address on each device.
1. Turn on the power of the Network converter.
2. Select the special mode by pressing and releasing SW7 (reset button) while holding down
SW4 (set button) until special mode "1" is displayed.
Special mode changes from "1" to "4" as shown in the following figure.
3. Press SW3 (mode button) to set special mode "2". Special mode "2" is the address setting
mode.
4. Press SW4 (set button). Current set address is displayed.
5. Press SW3 (mode button) to select the address. The displayed address changes as fol-
lows each time the mode button is pressed.
6. Press SW4 (set button) to set the selected address.
7. Turn the power off and on or press SW7 (reset button) to exit from address setting mode.
Anyone of the following indication will disappear:
: VRF Network address allocation is not registered by using Tool for Network converter
: Binding and commissioning is not executed
: Normal mode (Ready for operation)
Others
: Refer to the installation manual for more details.
2-26. Network converter for LonWorks
D19
JP1
SW7
SW3 SW4
A00
D9
SW1
SW2
D14
Example: Address no. 15 (Factory setting)
A01
A02
Example: Address no. 3 is selected.
- (07-143) -
A15
Example: Address no. 3 is set