5.0 Installation Instructions
WARNING
To reduce risk of fire, connect only to a circuit provided with 20A maximum branch circuit
overcurrent protection in accordance with the National Electrical Code
INSTALLATION NOTICE
TO AVOID CRITICAL DAMAGE TO UPS:
DO NOT BOND THE INPUT AND OUTPUT NEUTRALS TOGETHER.
•
DO NOT CONNECT THE OUTPUT NEUTRAL TO GROUND
•
Placement: Install the UPS horizontally in a protected area with adequate airflow: 20mm above and
•
below the unit, 10mm in front of the unit� Do not operate the UPS outdoors� It is required that an input
breaker is added in front of the UPS�
COMM CARD Installation: To install the optional card, remove the COMM PORT cover and insert the
•
card� Refer to the SDU COMM CARD Manual for more details� (Refer to inside cover for COMM CARD
options or contact your SolaHD representative)�
DIN Rail Mounting: Follow instructions below�
•
Location
Install the power module and battery module in a protected area with adequate airflow and free of excessive
dust� Do not operate the UPS outdoors�
Page: 10
Figure 5: Input/Output Terminals
(NEC
) and CEC.
®
®