Installation

3
Installation
3.1

Actuator check

Before you start to install the actuator make sure that the delivery status corresponds to the
ordered status and to the intended use.
Make sure that the motor and the connection chambers are free of dirt, moisture and
corrosion.
Make sure adequate travel is provided for the valve stroke.
3.2

Installation position

Fig. 3
The actuator's gearing LME620-AI/-AN (Contrac) is lubricated with grease. This means that any
mounting position can be selected.
3.3

Installation instructions

Make sure that the actuator is accessible from all sides to ensure convenient hand wheel
operation, electrical connection, and replacement of assemblies.
Avoid direct exposure to rain, snow and other environmental influences.
Make sure that the drive elements (thrust rod and valve stem) are not exposed to any
additional vibrational loading equivalent to more than double the rated force (e.g., by a spring
coupling or a vibration absorber between thrust rod and valve stem).
The maximum rated force of the actuator must not be permanently exceeded. Occasionally
and for short periods only, loads of up to twice the rated force are permissible.
When mounting the actuator close to heat sources use an insulating layer or shielding.
In IMV 1 mounting position, the actuators are resistant against vibrational loading acc. to EN
60068-2-6, table C.2 up to 150 Hz and additionally 1 g/30 min. If the operating conditions do
not allow you to estimate whether the actuator's vibrational loading is permanently exceeding
the proven contingent by a significant amount, you will need to reduce the maintenance
intervals accordingly.