Fujitsu General ASHG07KPCE Service Manual page 55

Wall mounted type
Table of Contents
2-15. E: 94. Trip detection (Outdoor unit)
Indicator
Indoor unit
Detective actuator
Outdoor unit
Forecast of cause
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
Check point 2. Replace the main PCB
If Check point 1 do not improve the symptom, replace the main PCB.
Check point 3. Replace compressor
If Check point 2 do not improve the symptom, change compressor.
2-15. E: 94. Trip detection (Outdoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
Main PCB
Compressor
End
Continuous flash
Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE: The number of generations is reset when the
compressor starts up.
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
- (03-21) -
9 time flash
4 time flash
E: 94