Honeywell NOTIFIER SLC Wiring Manual

Honeywell NOTIFIER SLC Wiring Manual

Intelligent control panel
Table of Contents
Intelligent Control Panel
SLC
Wiring Manual
Document 51253 Rev: U9
5/3/2022 ECN: 00009566
Table of Contents
loading

Summary of Contents for Honeywell NOTIFIER SLC

  • Page 1 Intelligent Control Panel Wiring Manual Document 51253 Rev: U9 5/3/2022 ECN: 00009566...
  • Page 2 Heat detectors are designed to Limit-F-2020 protect property, not life. Notifier SLC Wiring Manual — P/N 51253:U9 5/3/2022...
  • Page 3 HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus™, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®, Honeywell®, INSPIRE®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.
  • Page 4 Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly. Notifier SLC Wiring Manual — P/N 51253:U9 5/3/2022...
  • Page 5: Table Of Contents

    4.1: Overview..........................................28 4.2: NFPA Class B SLC ......................................28 4.3: NFPA Class A SLC ......................................29 Section 5: SLC Circuits with Isolators........................... 30 5.1: Overview..........................................30 5.2: Fault Isolator Modules.....................................30 5.3: Isolator Detector Bases ....................................31 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 6 11.1.1: Setting an SLC address ..................................65 11.2: Wiring a Manual Pull Station..................................65 Appendix A: Power Considerations ..........................66 A.1: Supplying Power to 24 VDC Detectors and NACs ............................66 A.2: Supervising 24 VDC Power....................................66 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 7 D.1: Wiring a Detector Base ....................................75 D.2: Wiring an Isolator Base....................................76 D.3: Wiring a Relay Base .......................................76 D.4: Wiring a Sounder Base ....................................77 Appendix E: Canadian Versions of SLC Devices ......................78 Index ....................................85 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 8: Section 1: Introduction

    • NCA and NCA-2/C This document also provides basic information that applies to Notifier SLC loops in general, such as the branch resistance measure- ments. NOTE: This manual does not call out Canadian and Export versions of panels and devices where products are the same. The information presented applies to all versions of the base panel/device.
  • Page 9: Reference Documentation

    SLM-318 Installation Document LS10243-000NF-E FireWarden SLC Wiring Manual (Use this manual for Notifier FireWarden series equipment 52304 Voice Alarm System Manual 51252 FireVoice-25/50 & FireVoice-25/50ZS Manual 52290 Table 1.2 Reference Documentation (1 of 4) Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 10 B200S-WH, B200S-IV Addressable Sounder Base Installation document I56-3392 B200SA-WH, B200SA-IV Canadian I56-3469 B200SCOA-WH, B200SCOA-IV Canadian with CO Detection I56-3824 Retrofit installations: B200S I56-3392 B200SA I56-3469 B200SCOA I56-3824-000 Table 1.2 Reference Documentation (2 of 4) Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 11 FSI-851 Ion Detector Installation Document I56-1924 FSI-851A Canadian FSV-951, FSV-951-IV Intelligent High-sensitivity Photoelectric Smoke Sensors, UL listed I56-4281 FSV-951A, FSV-951A-IV Intelligent High-sensitivity Photoelectric Smoke Sensors, ULC listed I56-9132 Table 1.2 Reference Documentation (3 of 4) Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 12: Slc Overview

    At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to Appendix B, “SLC Surge Suppression”, on page 71. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 13: Polling Protocols

    Through these addressable modules, the control panel can selectively activate Notification Appliance Circuits (NAC). • FCM-1 Control Module; FlashScan or CLIP mode. (Earlier monitor modules named CMX-1 and CMX-2 were CLIP mode only.) Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 14: 3: Isolator Modules

    B200SR-LF-WH, B200S-LF-WH A low-frequency version of the B200SR-WH/-IV. (-WH is white; -IV is ivory). Replaces legacy ivory B200SR-LF. Relay Base • B224RB-WH, B224RB-IV (-WH is white; -IV is ivory) Replaces legacy ivory B224RB. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 15: 8: Intelligent Detectors

    FSI-851 Addressable, intelligent smoke detector that incorporates an ionization sensing chamber. Designed to provide open area protec- tion. FlashScan- and CLIP-mode capable. (An earlier model named FSI-751 (discontinued) was also FlashScan- and CLIP-mode capa- ble. Earlier models named CPX-751 and CPX-551 were CLIP mode only.) Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 16: 9: Addressable Manual Pull Stations

    The ACPS-610 is an addressable power supply and battery charger with 24 VDC outputs. It operates in FlashScan or CLIP mode and has built-in strobe synchronization. Its four outputs may be independently configured to drive Notification Appliance Circuits (NACs) or to provide auxiliary power. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 17: 12: Acps-2406 Addressable Charger/Power Supply

    2 sec. GREEN, then OFF Detector Blinks RED RED continuous AFP-300/AFP-400 Monitor Module Blinks RED RED continuous Control Module Blinks GREEN GREEN continous Detector Blinks RED RED continuous Table 1.4 LED Operations Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 18 Detector Blinks RED RED continuous Blinks GREEN RED continuous NFS2-3030, NFS-3030 Table 1.4 LED Operations NOTE: In CLIP mode, the LPX-751 and HPX-751 blink GREEN in standby and stay RED when activated. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 19: Section 2: Wiring Requirements

    NFS-320, NFS-320SYS, NFS2-640, LEM-320 on NFS2-640, LCM-320/LEM-320 on NFS-3030/NFS2-3030, and N16/SLM-318 loops (with and without self-test detectors) Table 2.1 Wiring Recommendations: NFS-320, NFS2-640, NFS-640, NFS2-3030, NFS-3030, N16, SLM-318, LCM-320, LEM- 320, LIB-200A, and LIB-400 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 20 Note: Maximum total capacitance of all SLC wiring (both between conductors and from any conductor to earth) should not exceed 0.5 microfarads. AFP-300/AFP-400 Table 2.2 Wiring: AFP-100, AFP-200, AFP-300/400, LIB-200, AIM-200 (1 of 2) Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 21: Two-Wire Slc - Class B

    Figure 2.2 below shows the same SLC divided into segments. The total length of the SLC is determined by adding the lengths of Segment 1 + Segment 2 + Segment 3 + Segment 4 + Segment 5. No segment should be summed twice. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 22: Four-Wire Slc Class A And X

    The total wire length in a four-wire SLC cannot exceed the limits set forth in each system’s instruction manual. The figure below identi- fies the output and return loops from SLC terminal on the control panel or loop module: Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 23: Control Panel Terminal Blocks

    CLIP mode or FlashScan mode. SLC loops connect to TB1 on the LCM-320 or LEM-320. SLC Loop Connections SLC Loop Connections on Loop Control Modules on Loop Expander Module Figure 2.6 NFS2-3030, NFS-3030 SLC Loop Connections and Wiring Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 24: 3: Nfs2-640 With Loop Expander Modules, Nfs-320 And Nfs-320Sys

    The AFP-200 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TB5. SLC Loop Connections on FACP’s main circuit board Figure 2.10 SLC Connections for AFP-200 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 25: 7: Afp-300/Afp-400

    System 5000 with AIM-200 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to P8 on AIM-200. Figure 2.13 SLC Connections for AIM-200 NOTE: The AFC-600 has been discontinued; to service existing installations of this panel, refer to the original manuals shipped with the panel. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 26: Section 3: Shielded Wire Termination

    “shield” connection. Figure 3.2 Shield Termination – Full Conduit NOTE: For Class A or Class X SLC wiring, connect one end of the shield to the reference/negative side of the respective channel. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 27: Partial Conduit

    NOTE: Using shielded wire in applications where it is not recommended will reduce the maximum SLC length. If shielded wire must be used where not recommended, failing to float the ends will reduce the maximum SLC length even further. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 28: Section 4: Slc Circuits Without Isolators

    NFPA Class B requirements can be met by using the diagram below. • T-tapping of the SLC wiring is allowed for Class B configuration. Two-wire Addressable Detector Addressable Module T-tapped Circuits B+ B– Control Panel Figure 4.1 Basic NFPA Class B SLC Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 29: Nfpa Class A Slc

    SLC Out Addressable Module SLC Return B+ B– A– A+ Control Panel Figure 4.2 Basic NFPA Class A SLC NOTE: T-tapping of the SLC wiring is NOT allowed for Class A configuration. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 30: Section 5: Slc Circuits With Isolators

    SLC branch or segment. Figure 5.1 shows a Class B example for wiring of an Isolator Module. ISO-6 has the same functionality; see Figure 5.2. Continuation of the SLC Isolated branch of the SLC Figure 5.1 Wiring the ISO-X Isolator Module Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 31: Isolator Detector Bases

    If a short circuit fault occurs at point “X”, devices A, B, C & detector 2 will cease to function and display a trouble warning at the control panel. Devices D, E, F & detectors 1, 3, 4, and 5 will remain normal as they are served by ‘SLC Return’. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 32 Short-circuit path Figure 5.3 Isolator Base Circuit: Sample Class A Wiring NOTE: For information on wiring an isolator base, refer to Figure 10.3, “Wiring a B224BI-WH/B224BI-IV Isolator Base Mounting Plate” on page 56. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 33: Nfpa Class B Slc Using Isolator Modules

    Figure 5.2 on page 31 for isolator module wiring and to Section 5, “SLC Circuits with Isolators” for limitations. Isolator Module Two-wire Addressable Detector Isolated Branch Isolator Module Isolated Branch Addressable Pull Station Isolator Module Isolated Branch B– B+ Control Panel Figure 5.4 NFPA Class B SLC Using ISO-X Modules Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 34 Isolated Branch of SLC Isolated Branch of SLC SLC Loop ISO-6 Six Fault Fire Alarm Control Panel Isolator Module Figure 5.5 NFPA Class B SLC Using the ISO-6 Six Fault Isolator Module Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 35: Nfpa Class A Slc Using Isolator Modules

    Control Panel enclosure as the FACP, or these isolator modules must be connected within 20 ft. (6.1 m) of the FACP enclosure in conduit. Figure 5.6 NFPA Class A SLC Using Isolator Modules Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 36: Nfpa Class X Slc Using An Isolating Device

    20 ft. (6.1 m) of the FACP Control Panel enclosure in conduit. Figure 5.7 NFPA Class X SLC Using Isolator Modules NOTE: See Figure 10.3, “Wiring a B224BI-WH/B224BI-IV Isolator Base Mounting Plate” on page 56. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 37: Section 6: Monitor Modules

    24 VDC + Rotary IDC Return – SLC+ Switches IDC Return + IDC Out + IDC Out – Areas used to record the device address and SLC number. Figure 6.2 FZM-1 Zone Interface Module Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 38: 3: Miniature Monitor Module

    FlashScan capable control or relay modules, as well as detectors, can be set to one of 159 addresses (01-159) and are factory preset with an address of “00”. CLIP mode detectors and panels are limited to addresses 01-99. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 39: Nfpa Class B Idc Using Monitor Modules

    • Sprinkler supervisory service with normally open contact devices • Security service Refer to the Device Compatibility Document for compatible smoke detectors. See Appendix A, “Power Considerations”, on page 66 for information on supervising 24 VDC power. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 40: Nfpa Class A Idc Using Monitor Modules

    • Automatic and manual waterflow alarm service with normally open contact devices • Sprinkler supervisory service with normally open contact devices • Security service Refer to the Device Compatibility Document for compatible smoke detectors. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 41: Nfpa Class B Idc Using Zone Interface Modules

    • Automatic and manual waterflow alarm service with normally open contact devices • Sprinkler supervisory service with normally open contact devices • Security service Refer to the Device Compatibility Document for compatible smoke detectors. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 42: Nfpa Class A Idc Using Zone Interface Modules

    • Automatic and manual waterflow alarm service with normally open contact devices • Sprinkler supervisory service with normally open contact devices • Security service Refer to the Device Compatibility Document for compatible smoke detectors. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 43 FlashScan mode.) Two-wire Return for Class A. See Appendix A for power supervision. smoke detectors FZM-1 3.9K ELR (supplied with module) Figure 6.9 Typical Class A IDC Wiring with FZM-1 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 44: Section 7: Control Modules

    J1 toward the rear of the FCM-1 module so that it exits from the slot in the back. Figure 7.2 FCM-1 Jumper Location NOTE: When using NFS2-3030/NFS-3030 and the “Control” type ID, do not remove jumper J1. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 45: 1: Wiring A Solenoid With The Fcm-1-Rel

    Terminate the circuit across the last device using a UL-listed End-of-Line Resistor 47K, 1/2-watt, SSD P/N A2143-00 (ELR-47K in Canada). Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each device. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 46: Wiring A Class A Nac (Four-Wire) With Addressable Control Modules

    ID with built-in supervision or the alternative wire method is used. Module polarities are shown in Alarm. Figure 7.5 NFPA Class A Notification Appliance Circuit with FCM-1 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 47: Connecting A Releasing Device To The Addressable Control Module

    SLC (-) SLC (+) Figure 7.6 NFPA Class B Wiring of the FCM-1-REL with MRD-1 Manual Releasing Disconnect Switch and FMM-101 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 48 SLC (-) SLC (+) Figure 7.7 NFPA Class A Wiring of the FCM-1-REL with MRD-1 Manual Releasing Disconnect Switch and FMM-101 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 49: Section 8: Relay Module

    8.2 Wiring the Addressable Relay Module (Form-C Relay) The figure below shows the FRM-1 module wired to the Control Panel. FRM-1 Common Normally Closed Normally Open Common Normally Closed Normally Open Figure 8.1 FRM-1 Relay Module Wiring Connections Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 50: Section 9: Multiple Input/Output Modules

    The figure below shows the FDM-1 wired to the control panel. SLC– 9 H– Rotary SLC+ Address +1 Switches 8 H+ Base Address 6L– Areas used to record the device address and SLC number. Figure 9.1 FDM-1 Dual Monitor Module Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 51: Wiring The Addressable Dual Monitor/Dual Relay Module

    The IDC provides the following services (do not mix): • Fire alarm service • Automatic and manual waterflow alarm service with normally open contact devices • Sprinkler supervisory service with normally open contact devices • Security service Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 52 Refer to the Device Compatibility Document for compatible smoke detectors. Manual Pull Station Heat Detector FDM-1 Base +1 Address (IDC Circuit H) Base Address (IDC Circuit L) Figure 9.3 Typical Class B IDC Wiring with FDM-1 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 53: Section 10: Intelligent Detectors, Intelligent Detector Bases, And Wireless Gateway

    FSA-20000P covers 28,800 square feet through one to four addressable pipes These detectors are listed with UL for use with the NFS-320, NFS-320SYS, NFS2-640, and NFS2-3030. They support FlashScan mode only (an early version of FSA-8000 supported CLIP only). See Section 10.6. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 54: 3: Wireless Gateway

    Device on RA100Z Remote LED Annunciator (Optional) – Figure 10.1 Wiring Detector Base B300-6/-IV, B210LP, or B501 NOTE: The base wiring is identical for the flanged B300-6, B210LP, flangeless B501, and color variations. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 55 Power Supply RA100Z Remote LED Annunciator (Optional) Figure 10.2 Wiring of the B710HD Detector Base NOTE: Use a spade lug to wire the Remote LED Annunciator (–) to Terminal 2 (–). Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 56: Wiring An Isolator Base

    SLC illustration purposes only. Normally Closed Common Normally Open Figure 10.4 Wiring of a B224RB Relay Base Mounting Plate NOTE: The base wiring is identical for color variations. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 57: Wiring A Sounder Base

    Figure 10.6 Wiring of the B200SR/B200SR Sounder Base NOTE: The base wiring is identical for color variations. For more detailed wiring on sounder bases, refer to the device’s installation instructions. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 58: Wiring And Programming Aspiration Detectors

    10.6 Wiring and Programming Aspiration Detectors VESDA-E VES Wiring (Class B) VES Connections VES Connections on Door Inside Backbox NOTE: VESDA-E VES supports Class B power wiring. Figure 10.7 VESDA-E VES: FACP Connections Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 59 VEP & VEU Connections Inside Backbox VEP & VEU Connections on Door NOTE: VESDA-E VEU and VEP support Class B or Class A power wiring. Figure 10.8 VESDA-E VEU and VEP: FACP Connections Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 60 Wiring and Programming Aspiration Detectors VESDA-E VEA Wiring (Class B) VEA Connections Inside Backbox VEA Connections on Door NOTE: VESDA-E VEA supports Class B power wiring. Figure 10.9 VESDA-E VEA: FACP Connections Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 61 To Next Device + 24V External From Power Supply or Previous Device + Power To Next Device - From Power Supply or Previous Device - Figure 10.11 FSA-8000 Connection to the FACP Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 62: Wiring The Fwsg(A)

    For details about wireless devices, system setup, and operation, see the SWIFT® Wireless Gateway Manual. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 63: Power Connections: Powered By The Slc

    SLC loop. SLC out to next device (Class B) or SLC back to FACP (Class A) SLC in from FACP/device Jumpers Figure 10.14 FWSG Wiring Diagram, Powered by SLC Loop Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 64: 1: Power Connections: External, Regulated +24 Vdc Power Source

    NOTE: Terminal A5 is referenced more than once in the above connections. It is recommended to use wire of the same gauge for all connections to A5 and use the same wire gauge if there are multiple connections to the same terminal. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 65: Section 11: Addressable Manual Pull Stations

    11.2 Wiring a Manual Pull Station Typical wiring for the NBG-12LX Manual Pull Station to an SLC is shown below. – To next device on SLC – Figure 11.1 Wiring the NBG-12LX Pull Station to an SLC Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 66: Appendix A: Power Considerations

    When power is removed from the relay, the normally closed contacts open the supervised circuit, generating a trouble condition. There- fore, the relay needs to be installed at the end of the supervised circuit, so it does not disrupt the operating capability of all the devices on Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 67 Control Panel or Power Supply FCM-1 ELR 47K Power Supervision Relay (EOLR-1) Supervised NAC or IDC ELR 47K FMM-1 Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit - Class B Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 68: A.2.3: Using The Addressable Control Module Without Relay

    Connect the NAC power as follows: NAC Terminal Block (24 VDC) FCM-1 Note: Drawing shows power wiring only; SLC Wiring not shown. Circuit supervised by control panel FCM-1 Figure A.3 NFPA Class B NAC Power (Alternate) Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 69 Connect the NAC power as follows: NAC Terminal Block (24 VDC) FCM-1 Circuit supervised by control panel Note: Drawing shows power wiring only; SLC Wiring not shown. FCM-1 Figure A.4 NFPA Class A NAC Power Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 70: A.3: Basics Of Class A Power Supervision

    24VDC Power for Circuit supervised SLC devices by control panel to be supervised 24VDC Power for SLC devices to be supervised Figure A.5 Class A Wiring to Supervise 24 VDC Power to SLC Devices Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 71: Appendix B: Slc Surge Suppression

    Locate on an available stud and secure with nut. • Unit is connected in series with the SLC Loop to protect the Control Panel. • Provide a common ground to eliminate the possibility of a differential in ground potentials. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 72: Appendix C: Terminal Conversion Charts For V-Type And H-Type Devices

    H-type Terminal Number SLC - SLC + VDC - VDC + Unused Solenoid B/A - Solenoid B/A + Solenoid A + Solenoid A - Unused Unused Table C.2 FCM-1 and FZM-1 Terminal Conversions Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 73: C.3: Fmm-1

    SLC - SLC + Riser - Riser + Unused Class A/B Supervision - Class A/B Supervision + Class A Supervision + Class A Supervision - Unused Unused Table C.4 FTM-1 Terminal Conversions Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 74: C.5: Fdm-1

    H-type Terminal Number SLC - SLC + Unused Unused Unused Class A/B Supervision - Class A/B Supervision + Class A Supervision + Class A Supervision - Unused Unused Table C.5 FDM-1 Terminal Conversions Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 75: Appendix D: Intelligent Detector Base Layouts For Legacy Devices

    RA100Z Remote LED Annunciator (Optional) Figure D.1 Wiring of the B710LP or B501 Detector Base NOTE: The B710LP base wiring is identical to the B501, except there is no shield terminal. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 76: D.2: Wiring An Isolator Base

    Figure D.3 shows typical wiring of the B224RB plug-in relay detector base connected to an SLC. To next device on SLC For connection of cable shield Figure D.3 Wiring of the B224RB Plug-in Relay Detector Base Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 77: D.4: Wiring A Sounder Base

    Figure D.4 shows typical wiring of the B501BH(-2) and B501BHT(-2) Sounder Bases. UL-Listed 24V Power Supply Optional Sounder Interconnect SLC + SLC - Figure D.4 Wiring the B501BH(-2) and B501BHT(-2) Sounder Bases Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 78: Appendix E: Canadian Versions Of Slc Devices

    FlashScan mode only. White. FSV-951R-IV FSV-951RA-IV Intelligent High-sensitivity Photoelectric Smoke Sensors Intelligent High- sensitivity Photoelectric Smoke Sensors, Retrofit (Backwards compatible for use with older panels) FlashScan and CLIP mode. Ivory. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 79 Addressable VESDA-E VEU with 3.5" Display, UL 268 7th edition VEA-040-A00-NTF-UL — Addressable VESDA-E VEA-40 point with LEDs, UL 268 7th edition VEA-040-A10-NTF-UL — Addressable VESDA-E VEA-40 point with 3.5" Display, UL 268 7th edition Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 80 A. The modules come with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box. FCM-1-REL FCM-1-RELA Control Module for releasing applications. FlashScan only. (For use with NFS2-3030, NFS2-640, NFS-320(C), and NFS-320SYS.) Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 81 XP6-R XP6-RA Controls six Form-C relays. XP10-M XP10-MA Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor normally open contact initiating devices. XP6-MA XP6-MAA Monitors six zones of conventional two-wire detectors. Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 82 Notes Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 83 Notes Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 84 Notes Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 85: Index

    FMM-101, see miniature monitor modules ISO-X, see isolator modules communications loop – FMM-4-20 conduit, types of Terminal Designations connector screw junction box Form-C contacts control modules Form-C relays CPB-PCB and CPB-2PCB, see SLM-318 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 86 NFPA Class X Style 4, Style 6, Style 7, Style B, Style D, Style Y, NFS2-3030/NFS-3030 Style Z see NFPA Class A, Class B, Class C, Class X NFS2-640 NFS-3030 supervised circuits Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 87 Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM. Warn-HL-08-2009.fm Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021...
  • Page 88 NOTIFIER 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 www.notifier.com...