Evacuation System; Fresh Air; Evacuation Connection - Electrolux DC6-4 Installation Manual

Drying cabinet
Hide thumbs Also See for DC6-4:
Table of Contents
Installation manual
11

5 Evacuation system

5.1 Fresh air

When the drying cabinet is running, about 50 m
3
of moist air is evacuated per hour. This air is taken from the room
where the drying cabinet is situated.
It is therefore important to ensure that fresh air can enter the room from the outside to replace the humid air that is
vented out.
The recommended fresh air intake should be 5 times larger than the recommended shared exhaust air duct.

5.2 Evacuation connection

The drying cabinet should be connected to a standard exhaust ventilation unit.
There are two possible ways to connect the drying cabinet to a ventilation duct – either with a draft stabilizer or with a
permanent connection to an exhaust air system. If the drying cabinet is being connected to an existing ventilation
system, a draft stabilizer must always be used so that the general ventilation in the room is not affected.
Permanent connection is only permitted if a drying cabinet comes with a separate exhaust air duct.

Hide quick links:

Table of Contents
loading

Table of Contents