Corrosive Gas Limit - HP HPE FlexFabric 5944 Series Installation Manual

Table of Contents
Keep the equipment room away from pollution sources. Do not smoke, eat, or drink in the
equipment room.
Use double-layer glass in windows and seal doors and windows with dust-proof rubber strips.
Use screen doors and window screens for doors and windows open to the outside and make
sure the external windows are air tight.
Use dustproof materials for floors, walls, and ceilings and use wallpaper or matt paint that does
not produce powders.
Clean the equipment room regularly and clean the air filters of the rack each month.
Wear ESD clothing and shoe covers before entering the equipment room, keep the ESD
clothing and shoe covers clean, and change them frequently.

Corrosive gas limit

Corrosive gases can accelerate corrosion and aging of metal components. Make sure the corrosive
gases in the equipment room do not exceed the concentration limits as shown in Table1-3.
Table1-3 Corrosive gas concentration limits in the equipment room
Gas
SO
2
H
S
2
Cl
2
HCI
HF
NH
3
O
3
NO
X
CAUTION:
As a best practice, control the corrosive gas concentrations in the equipment room at their average
values. Make sure the corrosive gas concentrations do not exceed 30 minutes per day at their
maximum values.
To control corrosive gases, use the following guidelines:
As a best practice, do not build the equipment room in a place with a high concentration of
corrosive gases.
Make sure the equipment room is not connected to sewer, vertical shaft, or septic tank pipelines
and keep it far away from these pipelines. The air inlet of the equipment room must be away
from such pollution sources.
Use environmentally friendly materials to decorate the equipment room. Avoid using organic
materials that contains harmful gases, such as sulfur or chlorine-containing insulation cottons,
rubber mats, sound-proof cottons, and avoid using plasterboards with high sulfur concentration.
Place fuel (diesel or gasoline) engines separately. Do not place them in the same equipment
room with the device. Make sure the exhausted air of the engines will not flow into the
equipment room or towards the air inlet of the air conditioners.
Place batteries separately. Do not place them in the same room with the device.
Employ a professional company to monitor and control corrosive gases in the equipment room
regularly.
Average concentration (mg/m
0.3
0.1
0.1
0.1
0.01
1.0
0.05
0.5
1-3
3
)
Maximum concentration (mg/m
1.0
0.5
0.3
0.5
0.03
3.0
0.1
1.0
3
)