UL864 (Commercial Fire) Compliance
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
General Requirements
The VISTA-128FBPT/VISTA250FBPT control panels provide features that allow the system to meet UL864 Commercial
Fire requirements. To meet these requirements, follow the guidelines outlined in this section.
•
The reporting of bypassed points to the central station must be enabled in Report Code Programming mode.
•
Fire alarm notification circuits must be supervised (e.g., supervisory zones 970 and 971 for Bell 1 and Bell 2
outputs)
•
Only one relay of the 4204CF can be programmed for a NAC. If the 4204CF relay is programmed as a NAC, the
stop action must be programmed as a zone type 62, Bell 2 Timeout.
•
Output devices are not intended for overriding automatic fire and building functions.
•
Line cut detection must be enabled for both the main and backup phone lines (supervisory zones 974 and 975).
•
Access Control Devices cannot be used.
•
Audio Alarm Verification Devices cannot be used.
•
Remote downloading can only be performed if a service person is at the premises.
•
All supervision zones for the polling loop, RF receivers, keypads, NAC outputs, and telephone lines that are used,
must be enabled as zone type 19 (24-hour trouble).
Programming Field Settings for UL864 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
This product incorporates field-programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features
or options must be limited to specific values or not used at all as indicated below.
Program feature or option
∗ 08 TEM PORAL SI REN PUL SE
∗ 13 BEL L 1 TI M EOUT
∗ 14 RS232 comm.
∗ 17 AC L OSS K EYPAD
SOUNDI NG
∗ 19 RANDOM I ZE AC L OSS
REPORT
∗ 20 TEL EPH ONE M ODUL E
PH ONE CODE
∗ 22 K EYPAD PANI C ENABL ES
(PARTI TI ON SPECI FI C)
∗ 23 M UL TI PL E AL ARM S
(PARTI TI ON SPECI FI C)
∗ 24 I GNORE EXPANSI ON
ZONE TAM PER
∗ 26 I NTEL L I GENT TEST
REPORTI NG
PARTIES
Permitted in
Possible settings
UL864? Y/N
0 = disable
N
1 = enable
Y
Ent er 01-15 mult iplied by 2 minut es.
00 = no t imeout.
0 = no
N
1 = yes
0 = disable
N
1 = enable
Y
0 = wit hin 2 minutes
1 = 10-40 minut es
2 = 1-3 hour s
3 = 6-12 hour s wit hout Type 13, 1-3
hour s with Type 13
N
1-9 = fir st digit of access code
∗ or # = second digit of access code
(ent er # +11 for "∗", or # +12 for "#")
To disable ent er 00 for the 1
0 = disable
N
1 = enable
N
0 = disable
1 = enable
N
0 = disable (t amper det ect ion)
1 = enable (no t amper detect ion)
0 = disable
N
1 = enable
st
digit
7
Settings permitted in UL 864
Not used at t his t ime. M ust be set t o
"0" (disable).
M ust be set to "3" (M inimum of 6
minutes).
M ust be set to "0".
M ust be set to "1" (enabled).
M ust be set to "2".
Not Used. M ust be set to "00".
M ust be set to "000" for par t it ion 1
in fire syst ems.
M ust be set to "1" (enabled).
M ust be set to "0" (enabled).
M ust be set to "0" (disable).