Maintenance Of Contact System (Before 11/2003) - GE Gerapid 2607 User Manual

High speed dc circuit breaker
Table of Contents

6.2.2. Maintenance of contact system (before 11/2003)

Pay attention to the warnings, Section 1!
This section is valid for breakers manufactured before
11/2003.
This section refers to maintenance works A, B, C from Ta-
ble 4.
A) Remove the arc chute and adapter
See 6.2.1-A/B.
C) Changing the protective walls and arc runners
[Fig. 48]. Pull out two protective walls (3).
[Fig. 51-2]. Loosen screws (6a) with tool (SW4) and take
out front wall (6).
[Fig. 51-2]. Loosen screw (5a) with tool (SW5).
[Fig. 51-1]. Take out the front arc runner as it's shown.
[Fig. 51-2]. Take out the back arc runner (4) by loosen
two screws (4a) with tool (SW5). Don't remove the pro-
tective cap (4b).
[Fig. 51-2]. Install new front-arc runner (5) and new
back-arc runner (4). Tighten it using torque of 10Nm
[88lbf*in].
[Fig. 51-2]. Install front wall (6) and adjust it by posi-
tioning the protective wall (3) [Fig. 48]. Tighten it using
torque of 10Nm [88lbf*in]
[Fig. 48]. Put in two new protective walls (3).
Fig. 51-1 Taking out the front arc runner of old design
42
Design and specifications are subject to change without notice
4b
4
5a
Fig. 51-2 Changing pre-arcing contact
4a
5
6
6a
01/2008
Table of Contents
loading

This manual is also suitable for:

Gerapid 4207Gerapid 6007Gerapid 8007

Table of Contents