Troubleshooting By Protection Code (Outdoor Unit) - Hitachi YUTAMPO Series Service Manual

Table of Contents
6 Troubleshooting
Troubleshooting by protection code (Outdoor unit)
204
Alarm code
•  This alarm is displayed when an indoor unit stops answering to Master PC-ARFTE for more than 3 minutes.
•  Alarm recovery: When the communication is established again the alarm is recovered.
205
Alarm code
•  This alarm is displayed there is no messages from the central for more than 30 seconds.
•  Alarm recovery: When the communication is established again the alarm is recovered.

6.3 Troubleshooting by protection code (Outdoor unit)

Protection 
P102
code
•  Outdoor unit LED301 blinks 2 times
•  This protection code is displayed 3 times before alarm 102 appears at the LCD controller.
Yes
LD301 blinks twice
Operation stopped due to the detection of 
abnormality by the compressor control. It may be an 
abnormality of the compressor and an abnormality 
Peak current cut
of the drive circuit in case of heavy load.
P103
Protection 
code
•  Outdoor unit LED301 blinks 3 times
•  This protection code is displayed 3 times before alarm 103 appears at the LCD controller.
Yes
LD301 blinks 3 times.
Abnormally slow rotation
74
SMGB0135 rev.0 - 06/2020
Indoor unit stops answering to Master PC-ARFTE
Operation stopped due to the detection of 
abnormality by the compressor control. It 
may be an abnormality of the drive circuit 
in case of heavy load.
Central Alarm, no Central message
LCD controller has no power
Abnormal
Check the compressor 
for loose connectors and 
continuity of the cord.
Normal
Is a leakage breaker
installed?
No
Is the insulation of the compressor 
normal? Check it with a megger.
Normal
Conduct a "self-check"
Abnormal low speed of the compressor
No
Is the service valve open?
Yes
Abnormal
Check the compressor 
for loose connectors and 
continuity of the cord.
Normal
Is a leakage breaker
installed?
No
Is the insulation of the compressor 
normal? Check it with a megger.
Normal
Conduct a "self-check"
Fix the point of 
abnormality.
Abnormal
Replace the compressor and 
inspect the outdoor electrical
parts.
Replace the parts found to be 
defective based on the results of 
the "self-check" evaluation.
Open the service valve
Fix the point of 
abnormality.
Abnormal
Replace the compressor and 
inspect the outdoor electrical
parts.
Replace the parts found to be 
defective based on the results of 
the "self-check" evaluation.

Hide quick links:

Table of Contents
loading

This manual is also suitable for:

Raw-35rhcTaw-190rhcTaw-270rhc

Table of Contents