Emerson PACSystems RX3i User Manual
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Quick Links

USER MANUAL
GFK-2949E
Dec 2020
PACSystems
TM
RX3i
IEC 104 SERVER MODULE
(IC695EIS001)
Table of Contents
loading

Summary of Contents for Emerson PACSystems RX3i

  • Page 1 USER MANUAL GFK-2949E Dec 2020 PACSystems RX3i IEC 104 SERVER MODULE (IC695EIS001)
  • Page 2: Table Of Contents

    User Manual Contents GFK-2949E Dec 2020 Contents Chapter 1: Introduction ..............1 Revisions in this Manual ................1 IEC 104 Overview ..................2 Description ....................3 Product Overview ..................3 Specifications ....................5 Controls and Indicators ................. 6 RX3i IEC 104 Server Specifications and Restrictions ........7 1.7.1 ADSU Supported in General Interrogation ...........
  • Page 3 User Manual Contents GFK-2949E Dec 2020 Chapter 4: System Operation ............23 System Overview ..................23 4.1.1 Communications ................23 4.1.2 Redundancy ..................23 4.1.3 I/O Scans ..................24 4.1.4 Alarms ....................24 4.1.5 Station Manager ................25 Chapter 5: Diagnostics ..............
  • Page 4 User Manual Contents GFK-2949E Dec 2020 5.14 Security ...................... 58 Appendix A: Definition of the Status Area ..........59 General Table View ..................59 Specific Areas of Status ................59 A-2.1 Status of Read ................... 59 A-2.2 Status of a Client Connection ............59 A-2.3 Point Push ..................
  • Page 5 These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met during installation, operation, and maintenance. The information is supplied for informational purposes only, and Emerson makes no warranty as to the accuracy of the information included herein. Changes, modifications, and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein.
  • Page 6: Chapter 1: Introduction

    Added Appendix E: Control Functions to explain usage of STARTDT, Nov 2020 STOPDT, and TESTFR commands. Following Emerson’s acquisition of this product, changes have been made to apply appropriate branding and registration of the product Sep 2019 with required certification agencies. No changes to material, process, form, fit or functionality.
  • Page 7: Iec 104 Overview

    User Manual Chapter 1 GFK-2949E Dec 2020 IEC 104 Overview IEC 104 is a client/server communications protocol originally developed for use in the electric utility sector for power transmission and distribution systems. It has migrated to other vertical markets and is now a general market protocol based on a 3-layer protocol scheme.
  • Page 8: Description

    Product Overview The PACSystems RX3i Ethernet IEC 60870-5-104 Server Module, catalog number IC695EIS001 implements the IEC communications protocol. It permits a PACSystems RX3i controller to be connected to an Ethernet network using a standard TCP/IP connection scheme, allowing an IEC 104 Client to poll data from the Server, as well generate unsolicited communications from the Server back to the Client.
  • Page 9 User Manual Chapter 1 GFK-2949E Dec 2020 • Supports 56-bit IEC 60870-5-104-time format, with the default being 56-bit time format. • Supports Time Set, and query of the RX3i Controller CPU Clock in UTC time. • Cause of Transmission size is two octets. Figure 3: IC695EIS001 Front View The Ethernet 104 Server Module specifications: •...
  • Page 10: Specifications

    Module supports insertion into and removal from an RX3i backplane which is under power. • Firmware upgrade through RX3i CPU using WinLoader software utility. Specifications Module Name PACSystems RX3i Ethernet 104 Server Module. Catalogue IC695EIS001-AA. Protocol Supported IEC60870-5-104 Server. Connectors - Station Manager (RS-232) Port: 9-pin female D-connector - Two 10BaseT / 100BaseTX Ports: 8-pin female shielded RJ-45.
  • Page 11: Controls And Indicators

    User Manual Chapter 1 GFK-2949E Dec 2020 Controls and Indicators Figure 4 shows the front of the module and identifies its controls and indicators. Figure 4: IEC 104 Server Module EIS001 Features at a Glance Introduction...
  • Page 12: Rx3I Iec 104 Server Specifications And Restrictions

    User Manual Chapter 1 GFK-2949E Dec 2020 RX3i IEC 104 Server Specifications and Restrictions The following tables document the IEC 104 Server capabilities of the EIS001 module. Refer to the IEC 104 standard for details. Interrogation Types Description General General Interrogation is a full request of all point data on the Server from the client.
  • Page 13: Adsu Supported With 56-Bit Time Tag And Rbe

    User Manual Chapter 1 GFK-2949E Dec 2020 1.7.3 ADSU Supported with 56-Bit Time Tag and RBE ADSU supported with 56-bit time tag, and Report by Exception (RBE) Mnemonic Number Description M_SP_TB_1 Single-point information with time tag CP56Time2a M_DP_TB_1 Double-point information with time tag CP56Time2a M_ST_TB_1 Step position information with time tag CP56Time2a M_BO_TB_1...
  • Page 14: Adsu Supported Commands And Responses

    User Manual Chapter 1 GFK-2949E Dec 2020 1.7.5 ADSU Supported Commands and Responses ADSU Command and Responses Mnemonic Number Description C_SC_TA_1 Single command with time tag CP56Time2a C_DC_TA_1 Double command with time tag CP56Time2a C_RC_TA_1 Regulating step command with time tag CP56Time2a C_BO_TA_1 Bit String Response with time tag CP56Time2a C_SE_TA_1...
  • Page 15: Point Count Restrictions

    User Manual Chapter 1 GFK-2949E Dec 2020 1.8.2 Point Count Restrictions Table 1: Maximum Point Counts ADSU Maximum Point Maximum Point Memory Restriction Count (in a Demo Count (when Mode) licensed) M_SP_NA_1 1024 Digital Memory Only. M_DP_NA_1 Digital Memory, where each 2 points is a byte.
  • Page 16: Glossary

    User Manual Chapter 1 GFK-2949E Dec 2020 ADSU When SOE for this Memory Restriction ADSU is enabled M_EP_TC_1 2000 (Default - 512) Digital Memory Only (Only accessible through Point Push) Glossary ADSU A generic term used for referring to a collection of data points, or a single data point, on an IEC 104 device.
  • Page 17: References

    PACSystems TCP/IP Ethernet Communications Station Manager User Manual GFK-2225 PACSystems RX3i System Manual GFK-2314 PACSystems RX3i Ethernet 104 Server IC695EIS001 Quick Start Guide GFK-2948 PACSystems RX3i Ethernet 104 Server IC695EIS001 Important Product Information GFK-2947 User manuals, product updates and other information sources are available on the Support website,https://www.emerson.com/Industrial-Automation-Controls/support...
  • Page 18: Chapter 2: Installation

    LED indications. • Firmware updates. For additional information about RX3i system installation, refer to PACSystems RX3i System Manual, GFK-2314. For all EIS001 module installation procedures, use ETM001 as a reference since EIS001 is constructed on the ETM001 hardware platform. You will also need PAC Machine Edition configuration and programming software, version 8.50 SIM 9 or later.
  • Page 19: Installation In Hazardous Areas

    PACSystems RX3i System Manual, GFK-2314 Chapters 2 and 3 for details on how to mount/dismount RX3i modules and slot choices available. The EIS001 may be installed while the rack is under power. Refer to PACSystems RX3i System Manual, GFK-2314 Chapter 2 for hot-swap details.
  • Page 20 User Manual Chapter 2 GFK-2949E Dec 2020 Installation...
  • Page 21: Eis001 Module Removal

    The EIS001 may be removed from its RX3i rack while the rack is still under power. Follow the standard procedure for removing an RX3i module from its slot position, as detailed in PACSystems RX3i System Manual, GFK-2314 Chapter 2. Once removed from the rack, the Ethernet connection(s) will become inactive. The RS-232 Station Manager Port will also cease to operate.
  • Page 22: Chapter 3: Configuration

    The COMMREQ is executed only once following power-up or restart of the RX3i system. Configuration Tools • PACSystems RX3i CPU Firmware 8.00 or later. Refer to PACSystems RX3i Ethernet 104 Server IC695EIS001 Important Product Information, GFK-2947 for firmware compatibility. •...
  • Page 23 User Manual Chapter 3 GFK-2949E Dec 2020 Figure 5: Adding Module to Rack/Slot location Figure 6: Selection of EIS001 for Installation Note: That any I/O or registers selected for EIS001 write operations should not be assigned to any other modules, as they will be overwritten. PAC Machine Edition does not check for such potential conflicts.
  • Page 24: Rx3I Cpu Settings

    Chapter 3 GFK-2949E Dec 2020 The Emerson provided examples use variable mode on the EIS001 module to identify the terminals and prevent un-intended overlap using symbolic variables. RX3i CPU settings EIS001 modules require some amount of background scan time to efficiently transfer point data to and from the RX3i CPU.
  • Page 25 User Manual Chapter 3 GFK-2949E Dec 2020 Figure 8: EIS001 LAN Status Bits (Bits 11 & 13) Configuration...
  • Page 26: Ethernet Configuration

    User Manual Chapter 3 GFK-2949E Dec 2020 Ethernet Configuration Refer to PACSystems RX7i & RX3i TCP/IP Ethernet Communications User Manual, GFK-2224 Chapter 4. There is a section dealing with Ethernet Configuration for rack-based modules. EIS001 is limited to IPv4 addressing and can accept Advanced User Parameters (AUP) file settings for module parameters.
  • Page 27: Station Manager Configuration

    User Manual Chapter 3 GFK-2949E Dec 2020 as documented in 0. Ranges should be selected to accommodate the amount of data involved, but not overflow the end-point of the memory type. The Server configuration file also includes parameters to define an area of Controller memory for Client station-Server communication status, if required.
  • Page 28: Chapter 4: System Operation

    User Manual Chapter 4 GFK-2949E Dec 2020 Chapter 4: System Operation This chapter provides a System Overview and describes: • Communications • Redundancy • I/O Scans • Alarms • Station Manager System Overview 4.1.1 Communications The EIS001 is a self-standing communication processor. During normal operation, it handles asynchronous requests from its IEC 104 Client and exchanges corresponding data with the host RX3i CPU at designated portions of the CPU scan.
  • Page 29: I/O Scans

    User Manual Chapter 4 GFK-2949E Dec 2020 Note The Write Operations and ADSU will be processed by the active controller only. A Client connected to an RX3i CRU system that uses Redundant IP can experience a bump, or loss of communication in the event of a role switch at the IEC 104 Client station.
  • Page 30: Station Manager

    User Manual Chapter 4 GFK-2949E Dec 2020 4.1.5 Station Manager The RS-232 port on the EIS001 module is set up to be used as a Station Manager. Typically, this is used for trouble-shooting and administrative purposes. In addition to standard Station Manager commands, the EIS001 module responds to specific Stat and Tally Station Manager commands for IEC 104 information.
  • Page 31: Chapter 5: Diagnostics

    User Manual Chapter 5 GFK-2949E Dec 2020 Chapter 5: Diagnostics This chapter describes: • Status Data • Module LED Indicators • Power-up Module Restart — Problems During Power-up and Reset — Transitioning from Firmware Update Mode to Normal Operating Mode —...
  • Page 32: Power-Up

    The EIS001 firmware consists of the ETM001 firmware plus the IEC 104 Server specific firmware, and an Emerson installed license. Each firmware upgrade may be obtained from the Emerson support web-site as a uniquely- identified ZIP file. The ZIP file must be downloaded to a computer which can be connected to the host RX3i CPU.
  • Page 33: Module Faults In The Rx3I I/O Fault Tables

    User Manual Chapter 5 GFK-2949E Dec 2020 After new firmware has been successfully downloaded to the EIS001 module, and the CPU has been switched to RUN mode, the EIS001 module will reboot using the new firmware. In order to initialize and resume IEC 104 Server operation, it is necessary to activate the Configuration of IEC 104 Server Parameters Using COMMREQ command detailed in 0 in order to provide the module with its IEC 104 Server profile.
  • Page 34: Typical Fault Messages During Power-Up

    User Manual Chapter 5 GFK-2949E Dec 2020 EIS001 module continues to read data from the RX3i CPU memory, per its IEC 104 Server configuration. Since no new data is available to be written to the CPU during the Ethernet reset period, the EIS001 presents no new data to the RX3i CPU. Disconnecting an RJ-45 connector from Port 1A or Port 1B will disrupt Ethernet traffic on the corresponding port.
  • Page 35: Using Status Data For Troubleshooting

    User Manual Chapter 5 GFK-2949E Dec 2020 * In Demo mode more messages will be present indicating the lack of a license. Refer to Appendix C: for more details, or other log messages. 5.4.2 Using Status Data for Troubleshooting There are three main types of status data available to the RX3i application program: 1.
  • Page 36: Clearing The Rx3I Fault Tables

    EIS001 module, and what the user’s options are. The values supplied throughout the chapter are examples and may not relate to the way you wish your IEC 104 Server to be configured. Ladder logic examples can be found on the Emerson Support web-site https://www.emerson.com/Industrial- Automation-Controls/support.
  • Page 37 User Manual Chapter 5 GFK-2949E Dec 2020 accomplished by using Service Request 24 (refer to PACSystems RX7i and RX3i CPU Programmer’s Reference Manual, GFK-2950). In the following ladder example, a one-shot is employed to ensure the ST block is executed only once following power-up or following a restart of the CPU.
  • Page 38: Required Configuration Parameters

    User Manual Chapter 5 GFK-2949E Dec 2020 Required Configuration Parameters The ten parameters outlined in sections 5.6.1 and 5.6.2 are required for all RX3i IEC 104 Server configuration files. These parameters set a basic configuration in the IEC 104 Server module that allows connection to an IEC 104 Client station.
  • Page 39: Memory Translation Feature Configuration Parameters

    User Manual Chapter 5 GFK-2949E Dec 2020 Parameter Value Description mComreq_Setup [10] Number of Segments Value: 1 Memory Translation Feature Configuration Parameters The Optional Configuration Parameters listed in Section 5.8 are optional for RX3i IEC 104 Server configuration files. The Memory Translation feature can be configured using the parameters as described in this section.
  • Page 40: Parameters For Command Translation Table

    User Manual Chapter 5 GFK-2949E Dec 2020 5.7.2 Parameters for Command Translation Table Parameter Value Description mComreq_Setup [84] 0 to 32000 Command Translation Table MSP mComreq_Setup [85] 0 to 32000 Command Translation Table MDP mComreq_Setup [86] 0 to 32000 Command Translation Table MST mComreq_Setup [87] 0 to 32000 Command Translation Table MBO...
  • Page 41 User Manual Chapter 5 GFK-2949E Dec 2020 Figure 16: Red/Write Interaction between Controller and IEC104 Client (Case 1) • Master requesting (read & write commands) for corresponding point offset address should be synchronized with translation memory offset address Case 2: Configuring Translation Memory Offset with Zero and CPO with Non-Zero Value Figure 17: COMMREQ Parameters &...
  • Page 42 User Manual Chapter 5 GFK-2949E Dec 2020 Figure 18: Red/Write Interaction between Controller and IEC104 Client (Case 2) • Points < CPO are Read only • Point >= CPO are Read / Write Case 3: Configuring Different Translation Memory Offsets and CPO as a Zero Figure 19: COMMREQ Parameters &...
  • Page 43 User Manual Chapter 5 GFK-2949E Dec 2020 Figure 20: Red/Write Interaction between Controller and IEC104 Client (Case 3) Case 4: Configuring Command Translation Memory Offsets to Zero and CPO as Non- Zero Value Figure 21: COMMREQ Parameters & Corresponding Read/Write Permissives (Case 4) Configuration of IEC-104 Server Parameter...
  • Page 44 User Manual Chapter 5 GFK-2949E Dec 2020 Figure 22: Red/Write Interaction between Controller and IEC104 Client (Case 4) • Since Command Translation offset is configured to 0 and read translation offset is non- zero, there is a problem from the client end in synchronizing these two offsets, as shown in the above communication.
  • Page 45: Optional Configuration Parameters

    User Manual Chapter 5 GFK-2949E Dec 2020 • This type of configuration is not recommended. Figure 24: Red/Write Interaction between Controller and IEC104 Client (Case 5) • Communication between controller and IEC104 client with translation memory offsets Note: Point offset address is assigned with respective configured translation Offset + 1 to their address.
  • Page 46: Parameters For Filter Times

    User Manual Chapter 5 GFK-2949E Dec 2020 5.8.1 Parameters for Filter Times Parameter Value Description mComreq_Setup [11] 0 to 65530 Input Change Filter Time, default is 10 ms, typical [3x Controller Sweep]. The Input Change Filter is a shutter on the data intake by the module from the Controller.
  • Page 47: Parameters For Server Status Space

    User Manual Chapter 5 GFK-2949E Dec 2020 5.8.3 Parameters for Server Status Space The Server Status Space is a 100-word data table that contains the current operational status of the Client station-Server connection. Set appropriate values for the constituent parameters as required by the application. The Controller memory location assigned to contain the Server Status Space is defined by the user, as follows: Parameter Value...
  • Page 48 User Manual Chapter 5 GFK-2949E Dec 2020 The CPO value determines which portion of the ADSU object is Read-Only, and which is Read/Write as shown below: CPO = 0 All ADSUs are Read-Only. CPO = Length All ADSUs are Read-Only. Non-zero Length CPO <...
  • Page 49 User Manual Chapter 5 GFK-2949E Dec 2020 Configuration of IEC-104 Server Parameter...
  • Page 50 User Manual Chapter 5 GFK-2949E Dec 2020 MDP Configuration M_DP ADSU COMMREQ Configuration Parameter Value Description mComreq_Setup [22] m-type value Memory Type for DP Objects Value: 70-%I, 72-%Q, 76-%M, 74-%T, 68-%G, 0-unused mComreq_Setup [23] address value Memory Address for ADSU object Value: 1 to maximum (based on memory type) mComreq_Setup [24] Length...
  • Page 51 User Manual Chapter 5 GFK-2949E Dec 2020 Parameter Value Description mComreq_Setup [33] Refer to Control Point Offset Configuration discussion in Section 5.8.4. MMENA Configuration M_ME_NA ADSU COMMREQ Configuration Parameter Value Description mComreq_Setup [34] m-type value Memory Type for ME_NA Object Value: 8-%R, 10-%AI, 12-%AQ, 196-%W, 0-unused mComreq_Setup [35] address value...
  • Page 52 User Manual Chapter 5 GFK-2949E Dec 2020 Parameter Value Description mComreq_Setup [44] Length Number of ADSU Objects *Note Each object is 2 words representing an IEE Float mComreq_Setup [45] Refer to Control Point Offset Configuration discussion in Section 5.8.4 Configuration of IEC-104 Server Parameter...
  • Page 53: Option Parameters

    User Manual Chapter 5 GFK-2949E Dec 2020 MEPTB Configuration *Future M_EP_TB ADSU COMMREQ Configuration does not scan the Controller memory, you must use Point Push interface for this ADSU. Parameter Value Description mComreq_Setup [46] m-type value unused mComreq_Setup [47] address value unused mComreq_Setup [48] Length...
  • Page 54 User Manual Chapter 5 GFK-2949E Dec 2020 Parameter Value Description Bit 6 – When 1 SOE Disabled for M_ME_NB Bit 7 – When 1 SOE Disabled for M_ME_NC [Note: The SOE events are generated only when the Controller is in RUN I/O Enable state when the Bit 1 to Bit 7 is set to 1 for individual ADSUs.
  • Page 55 User Manual Chapter 5 GFK-2949E Dec 2020 Parameter Value Description If value is greater than equal to 2000, then the queue depth is clamped to 2000 by the EIS001 firmware. mComreq_Setup [73] Integer Queue Depth Override for Analog Points, 0 to 2000 If value is 0, then queue depth is set to 512.
  • Page 56 User Manual Chapter 5 GFK-2949E Dec 2020 COMMREQ –Shift RBE on Client Connection Associated with a Specified Port Number The following are important aspects of Multiple Client connections for an IEC 104 Server module: - 1. All Client connections in multiple Client configuration will support Polling or General Interrogation 2.
  • Page 57 User Manual Chapter 5 GFK-2949E Dec 2020 Shift the RBE (Report by Exception/Unsolicited Response) to client connection associated with a specified Port number. Return the COMMREQ Status word to %R10. Dec (Hex) Word 1 00008 (0008) Length of Channel command Data Block Word 2 00000 (0000) Always 0 (no-wait mode request) Word 3...
  • Page 58: Point Push Interface Definition

    User Manual Chapter 5 GFK-2949E Dec 2020 Point Push Interface Definition Point Push is an IEC 104 Server feature used to manually enter IEC 104-point data, date and time, and/or flags information into the internal database of the EIS001 module. This feature is available in either SOE mode, or NON-SOE Mode.
  • Page 59: Record Format

    User Manual Chapter 5 GFK-2949E Dec 2020 mComreq_Setup [71] Memory Address Value 1-Based, high word High word only used for accessing %W memory above 65535 5.9.2 Record Format The Point Push Record Format consists first of a 3-word Header Section and a 13-word Record Section.
  • Page 60: Interface Collection Mechanism

    User Manual Chapter 5 GFK-2949E Dec 2020 Note: The field ADSU in the above record format can be set to the Type of ADSUs required for point push by using the ADSU number in the appropriate fields. Refer to ADSU Supported in General Interrogation 5.9.3 Interface Collection Mechanism...
  • Page 61: Point Push For Digital And Analog Data

    User Manual Chapter 5 GFK-2949E Dec 2020 • If words [000] and [002] are both 0, the push is complete. Word [001] will revert to the same sequence number pushed. A new Point Push record can now be initiated. • The Point Push interface will HOLD if no event space is available and will not accept any point push records, the step where the three records are set to -1 will not occur, and the header information will remain the same as that entered by the user’s application code.
  • Page 62: Program Download

    User Manual Chapter 5 GFK-2949E Dec 2020 The COMMREQ function block parameters are described in the table below. Set values for these parameters as required by the application. Parameter Value Description mComreq_Setup Location of the COMMREQ Command Block Parameters, always mComreq_Setup SYSID iRackSlot Slot Location of the IEC 104 EIS001 module in RX3i...
  • Page 63: Security

    Such devices should also be protected from direct access using the security features found in the latest released versions of PAC Machine Edition and PACSystems RX3i CPU firmware. Consult Emerson technical support for more information.
  • Page 64: Appendix A: Definition Of The Status Area

    User Manual Appendix A GFK-2949E Dec 2020 Appendix A: Definition of the Status Area General Table View Figure 29: Status Area Contents and Layout Note The status representing the "Client Connection 01 to 08" in Status area are only applicable with Multiple Client connection configuration with RBE on one Client connection.
  • Page 65: A-2.4 Events Being Stored

    User Manual Appendix B GFK-2949E Dec 2020 A-2.4 Events being stored Indices 31 to 39 show the queue amounts for each of the supported ADSUs. Station Manager Status...
  • Page 66: Appendix B: Station Manager Status

    Typically, these are for tech support to use, but they can be used to debug a system prior to engaging Emerson IP support. Below are examples of its usage in the STAT and Tally Commands...
  • Page 67 User Manual Appendix B GFK-2949E Dec 2020 NODE The Node Command indicates the presence of the Plug-in communication modules. Figure 31: Node Commands Showing Available Plug-in Communication Modules Station Manager Status...
  • Page 68: Appendix C: Log Messages Table

    User Manual Appendix C GFK-2949E Dec 2020 Appendix C: Log Messages Table All EIS001-specific faults are logged under Group 16. Other (ETM001-derived) module faults may also be logged under Group 16. The EIS001 module faults are: Module Word 2 and 3 Word 4 and 5 Word 6 and 7 Word 8 and 9...
  • Page 69: Appendix D: Device Profile

    User Manual Appendix D GFK-2949E Dec 2020 Appendix D: Device Profile This Appendix is a copy of IEC 60870-5-104 Configuration/Interoperability Guide for IC695EIS001. SOFTWARE DOCUMENTATION IEC 60870-5-104 Configuration/Interoperability Guide for IC695EIS001 D O C U M E N T V E R S I O N 2 . 4 , S E P T E M B E R 2 7 , 2 0 1 0 Revision History Document Version: Date:...
  • Page 70: Introduction

    October 17, 2014 Reviser: Daniel J. Bingham • Modified for Emerson Support. Introduction The purpose of this document is to describe the specific implementation of the IEC 60870- 5-104 Source Code Library, V3. Uses the Triangle MicroWorks, Inc. IEC 60870-5-104 Slave Source Code Library Version 3.
  • Page 71: D-3.1 System Or Device

    User Manual Appendix D GFK-2949E Dec 2020 Note: In addition, the full specification of a system may require individual selection of certain parameters for certain parts of the system, such as the individual selection of scaling factors for individually addressable measured values. The selected parameters should be marked in the white boxes as follows: Function or ASDU is not used Function or ASDU is used as standardized (default)
  • Page 72: D-3.4 Link Layer

    User Manual Appendix D GFK-2949E Dec 2020 Standard Recommended if >1 200bit/s Transmission speed (monitor direction) Unbalanced interchange Unbalanced interchange Balanced interchange Circuit V.24/V.28 Circuit V.24/V.28 Circuit X.24/X.27 Standard Recommended if >1 200bit/s D-3.4 Link layer (network-specific parameter, all options that are used are to be marked ‘X’. Specify the maximum frame length.
  • Page 73: D-3.5 Application Layer

    User Manual Appendix D GFK-2949E Dec 2020 When using an unbalanced link layer, the following ASDU types are returned in class 2 messages (low priority) with the indicated causes of transmission: The standard assignment of ASDUs to class 2 messages is used as follows: Type identification Cause of transmission 9, 11, 13, 21...
  • Page 74 User Manual Appendix D GFK-2949E Dec 2020 Maximum length of APDU per system in control direction Maximum length of APDU per system in monitor direction Selection of standard ASDUs Process information in monitor direction (station-specific parameter, mark each Type ID ‘X’ if it is only used in the standard direction, ‘R’...
  • Page 75 User Manual Appendix D GFK-2949E Dec 2020 <21> Measured value, normalized value without quality descriptor M_ME_ND_1 <30> Single-point information with time tag CP56Time2a M_SP_TB_1 <31> Double-point information with time tag CP56Time2a M_DP_TB_1 <32> : =Step position information with time tag CP56Time2a M_ST_TB_1 <33>...
  • Page 76 User Manual Appendix D GFK-2949E Dec 2020 <50> Set point command, short floating point value C_SE_NC_1 <51> Bitstring of 32-bit C_BO_NA_1 <58> Set point command, scaled value C_SE_NB_1 <59> Double command with time tag CP56Time 2a C_DC_TA_1 <60> Regulating step command with time tag CP56Time 2a C_RC_TA_1 <61>...
  • Page 77 User Manual Appendix D GFK-2949E Dec 2020 <105> : = Reset process command C_RP_NA_1 <106> : = Delay acquisition command C_CD_NA_1 <107> : = Test command with time tag CP56time2a C_TS_TA_1 Control Functions...
  • Page 78 User Manual Appendix D GFK-2949E Dec 2020 Parameter in control direction (station-specific parameter, mark each Type ID ‘X’ if it is only used in the standard direction, ‘R’ if only used in the reverse direction, and ‘B’ if used in both directions) <110>...
  • Page 79 User Manual Appendix D GFK-2949E Dec 2020 Type identification Cause of transmission 2 3 4 5 6 44 45 46 47 <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 <10> M_ME_TA_1 <11>...
  • Page 80 User Manual Appendix D GFK-2949E Dec 2020 Type identification Cause of transmission 2 3 4 5 6 44 45 46 47 <33> M_BO_TB_1 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47>...
  • Page 81 User Manual Appendix D GFK-2949E Dec 2020 Type identification Cause of transmission 2 3 4 5 6 44 45 46 47 <101> C_CI_NA_1 <102> C_RD_NA_1 <103> C_CS_NA_1 <104> C_TS_NA_1 <105> C_RP_NA_1 <106> C_CD_NA_1 <107> C_TS_TA_1 <110> P_ME_NA_1 <111> P_ME_NB_1 <112> P_ME_NC_1 <113>...
  • Page 82: D-3.6 Basic Application Functions

    User Manual Appendix D GFK-2949E Dec 2020 D-3.6 Basic Application Functions Station initialization (station-specific parameter, mark ‘X’ if function is used) Remote initialization Cyclic data transmission (station-specific parameter, mark ‘X’ if function is only used in the standard direction, ‘R’ if only used in the reverse direction, and ‘B’...
  • Page 83 User Manual Appendix D GFK-2949E Dec 2020 Station interrogation (station-specific parameter, mark ‘X’ if function is only used in the standard direction, ‘R’ if only used in the reverse direction, and ‘B’ if used in both directions) global group 1 group 7 group 13 group 2...
  • Page 84 User Manual Appendix D GFK-2949E Dec 2020 Control Functions...
  • Page 85 User Manual Appendix D GFK-2949E Dec 2020 Transmission of integrated totals (station-specific parameter, mark ‘X’ if function is only used in the standard direction, ‘R’ if only used in the reverse direction, and ‘B’ if used in both directions) Mode A: Local freeze with spontaneous transmission Mode B: Local freeze with counter interrogation Mode C: Freeze and transmit by counter-interrogation commands Mode D: Freeze by counter-interrogation command, frozen values reported...
  • Page 86 User Manual Appendix D GFK-2949E Dec 2020 Control Functions...
  • Page 87 User Manual Appendix D GFK-2949E Dec 2020 File transfer (station-specific parameter, mark ‘X’ if function is used) File transfer in monitor direction Transparent file Transmission of disturbance data of protection equipment Transmission of sequences of events Transmission of sequences of recorded analog values File transfer in control direction Transparent file Background scan...
  • Page 88 User Manual Appendix D GFK-2949E Dec 2020 Maximum range of values k: 1 to 32767 (215-1) APDUs, accuracy 1 APDU Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU (Recommendation: we should not exceed two-thirds of k). Portnumber Parameter Value...
  • Page 89: Appendix E: Control Functions

    User Manual Appendix E GFK-2949E Dec 2020 Appendix E: Control Functions E-1.1 STARTDT & STOPDT The STARTDT_ACT (Start Data Transfer Activation) command is sent by the controlling station /IEC104 Master to the controlled station /IEC10 Server- IC695EIS001 to indicate the data transfer after an established connection.
  • Page 90: E-1.2 Testfr

    User Manual Appendix E GFK-2949E Dec 2020 Figure 33 shows a Wireshark trace capturing these control functions during startup (U type). Figure 33: Wireshark Trace of STARTDT Function E-1.2 TESTFR The TESTFR_ACT (Test Frame Activation) command is sent by the controlling station /IEC104 Master to the controlled station /IEC10 Server- IC695EIS001 at regular intervals to check the status of established connections.
  • Page 91: E-1.3 Reference

    User Manual Appendix E GFK-2949E Dec 2020 Figure 34 demonstrates ; demonstrates typical handshake between Controlling station /IEC104 Master) to the Controlled station /IEC10 Server- IC695EIS001 Figure 34: Test Harness Tool Figure 35 shows a Wireshark trace capturing these control functions during startup (U type).
  • Page 92: General Contact Information

    Note: If the product is purchased through an Authorized Channel Partner, please contact the seller directly for any support. Emerson reserves the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product.

Table of Contents