Chapter B - Configuration Parameters; List Of Device Configuration Parameters - Honeywell TR80UWD Installation And Operating Manual

Wall module
Table of Contents
APPENDIX
B

List of Device configuration parameters

Config
parameter
Name
number
0
Firmware Version1
1
Firmware Version2
2
ConfigId
3
ConfigDateCode
4
Modbus slave
address
5
Port Baudrate
6
Port1 Parity
7
Port1 StopBits
8
Port2 Baudrate
9
Port2 Parity
10
Port2 StopBits
11
Port2 Response
Timeout
12
Dali64 sensor slave
address
TR80 - Installation and Operation Guide
CONFIGURATION PARAMETERS
Type/
Unit
(min-Max)
2 bytes
0-255
0-255
2 bytes
0-255
0-255
int
0-65535
2 bytes
0-65535
int
1-120
enum
0: No function
1: Dark Mode
2: Sleep Mode
enum
0: °C
1: °F
C
0: not allowed
1: allowed
C
0...100%
C
C
0-9999
int
0-247
Range
Default
0
0
1
0
0: °C
1
%100
0
0x7FFF
1
Notes
Firmware version: major, minor
Firmware version: bug, biult
Configuration date code
Cleaning Mode Timeout
Power Button Function
Temperature display unit: °C or °F
Allow temperature unit change on
device?
LCD backlight brightness in percent
Resets some settings to default values
Room Number
0 = No DALI sensor on port 2, no
repeater function
61