Honeywell CRIR E1 User Manual
Honeywell CRIR E1 User Manual

Honeywell CRIR E1 User Manual

Commercial carbon dioxide sensor

Quick Links

USER GUIDE FOR THE
COMMERCIAL CARBON DIOXIDE SENSOR,
400 PPM TO 2000 PPM (UP TO 5000 PPM
EXTENDED RANGE),

TABLE OF CONTENTS

1.0 GENERAL INFORMATION .............................................. 1
2.0 SENSOR HANDLING ........................................................ 3
3.0 AUTOMATIC BASELINE CORRECTION ....................... 3
4.0 TERMINATION ................................................................... 3
5.0 CALIBRATION..................................................................... 6
6.0 SELF-DIAGNOSTICS............................................. ............6
7.0 MODBUS REGISTER DEFINITION............................... ..6
8.0 MODBUS FUNCTION DESCRIPTION........................ ....9
1.0

GENERAL INFORMATION

The CRIR E1 Commercial Carbon Dioxide (CO
single channel, non-dispersive infrared (NDIR) sensor. Within
the CRIR E1 is a sensing chamber with an infrared source at
TABLE 1. SPECIFICATIONS
CHARACTERISTIC
Target gas
Operating principle
Standard range
1, 2
Measurement interval
Accuracy
3
Typical response time (T
90
Sensor warm-up time
Repeatability
Operating voltage
Power consumption
Alarm output, open collector
Serial communication
5
Operating temperature range
Storage temperature range
Operating humidity
Expected operating life
Maintenance
6
Weight
Dimensions
1
The CRIR E1 is designed to measure CO
concentrations below 400 ppm may result in incorrect operation of the ABC algorithm and should be avoided when the ABC is ON.
The CRIR E1 provides readings via UART in the extended range; however, the accuracy is reduced.
2
In normal IAQ applications, the sensor accuracy is defined after a minimum of three ABC periods of continuous operation.
3
The sensor accuracy is specified over the operating temperature range and referenced to certified calibration mixtures. Uncertainty of calibration
4
gas mixtures (±1% currently) is to be added to the specified accuracy for absolute measurements.
See Sections 7.0 and 8.0 for Modbus address and parameter definitions.
5
The CRIR E1 normally does not require maintenance in IAQ applications; however, for some industrial applications, maintenance may be required.
6
CRIR E1
) sensor is a
2
PARAMETER
carbon dioxide (CO
non-dispersive infrared (NDIR)
400 ppm to 2000 ppm, up to 5000 ppm extended range
4 s
±5
0 ppm
)
<120 s
3 minimum typical
>97%
4.5 V to 5.5 V unprotected against surges and reverse connection
300 mA peak, 30 mA average
1000 ppm/800 ppm normal state is conducting maximum 100 mA.
Transistor open at CO
UART, Modbus protocol
0°C to 50°C
-40°C to 70°C
0 %RH to 90 %RH non-condensed
10 years
maintenance-free for normal indoor applications
<8 g
33 mm x 22 mm X 11,2 mm (tolerance ±0,5 mm)
in the range of 400 ppm to 2000 ppm with the accuracy specified in Table 1; however, exposure to
2
one end and a detector fitted with an optical filter at the other
end. The source emits radiation at wavelengths which include
the absorption band of CO
are not sensitive to the presence of CO
selectivity and sensitivity. As the light passes through the
sensing chamber, a fraction is absorbed if CO
difference between the light emitted by the source and received
by the detector can then be converted to a CO
reading. The Automatic Baseline Correction (ABC) function can
automatically calibrate the sensor's lowest reading over a pre-
configured interval to 400 ppm CO
stability and may eliminate the need for calibration.
See Tables 1 and 2, and Figures 1 and 2 for specifications and
mounting and dimensional diagrams.
)
2
±5
% of reading
high or at sensor failure (see Figure 1).
2
000841
. The filter blocks wavelengths which
2
, thereby increasing
2
is present. The
2
concentration
2
. This enhances long term
2
Issue 1
loading

Summary of Contents for Honeywell CRIR E1

  • Page 1: Table Of Contents

    (±1% currently) is to be added to the specified accuracy for absolute measurements. See Sections 7.0 and 8.0 for Modbus address and parameter definitions. The CRIR E1 normally does not require maintenance in IAQ applications; however, for some industrial applications, maintenance may be required.
  • Page 2 COMMERCIAL CARBON DIOXIDE SENSOR, 400 PPM TO Issue 1 000841 2000 PPM (UP TO 5000 PPM EXTENDED RANGE), CRIR E1 FIGURE 1. ALARM STATE DIAGRAM Alarm state open concentration (ppm) FIGURE 2. MOUNTING DIMENSIONS (FOR REFERENCE ONLY: MM) 33,00 2,50 2,50 TABLE 2.
  • Page 3: Sensor Handling

    • Handle the CRIR E1 by the black PCB on the edges as Table 3 shows the ABC period specifications. Please refer to shown in Figure 1.
  • Page 4 (V) and CO V(output) = 0.4 + 0.0008 x C(CO concentration (ppm) output accuracy ±20 mV The specified parameter relies on the subcontractor's specification and is not tested by Honeywell. 4 Sensing and Internet of Things...
  • Page 5 G+ resistor 10 k maximum sink current 100 mA saturation voltage 2.3 V to Vin + 0.3 V The specified parameter relies on the subcontractor's specification and is not tested by Honeywell. Sensing and Internet of Things...
  • Page 6: Calibration

    2000 PPM (UP TO 5000 PPM EXTENDED RANGE), CRIR E1 CALIBRATION SELF-DIAGNOSTICS The CRIR E1 has the following built-in, self-diagnostic With the ABC function on, the sensor readings, which may functions: have drifted due to mishandling during transportation and/ or installation, may gradually be recalibrated to the correct •...
  • Page 7 COMMERCIAL CARBON DIOXIDE SENSOR, 400 PPM TO Issue 1 000841 2000 PPM (UP TO 5000 PPM EXTENDED RANGE), CRIR E1 TABLE 6. INPUT REGISTERS DEFINITION DESCRIPTION NAME Reserved — Reserved — Reserved — Reserved — Temperature Detector Temperature DI 1 – reserved DI 2 –...
  • Page 8 COMMERCIAL CARBON DIOXIDE SENSOR, 400 PPM TO Issue 1 000841 2000 PPM (UP TO 5000 PPM EXTENDED RANGE), CRIR E1 TABLE 7. HOLDING REGISTERS DEFINITION NAME DESCRIPTION Reserved — Reserved — Reserved — Reserved — ABC Period ABC period in hours...
  • Page 9: Modbus Function Description

    COMMERCIAL CARBON DIOXIDE SENSOR, 400 PPM TO Issue 1 000841 2000 PPM (UP TO 5000 PPM EXTENDED RANGE), CRIR E1 MODBUS FUNCTION DESCRIPTION The serial port configuration is: 9600, 8, 1, N, N. The sensor is addressed as “Any address” (0xFE).
  • Page 10 COMMERCIAL CARBON DIOXIDE SENSOR, 400 PPM TO Issue 1 000841 2000 PPM (UP TO 5000 PPM EXTENDED RANGE), CRIR E1 8.1.7 Read Memory Map Version Master Transmit: <04> <00> <0B> <00> <01> <54 > <07> Slave Reply: <04> <02>...
  • Page 11 COMMERCIAL CARBON DIOXIDE SENSOR, 400 PPM TO Issue 1 000841 2000 PPM (UP TO 5000 PPM EXTENDED RANGE), CRIR E1 8.2.3 Setup User Concentration Master Transmit: <06> <00> <07> <01> <90> <2D > Slave Reply: <06> <00> <07> <01> <90> <2D > ...
  • Page 12 In no event shall Honeywell be liable for consequential, special, or indirect damages. While Honeywell may provide application assistance personally, through our literature and the Honeywell web site, it is buyer’s sole responsibility to determine the suitability of the product in the application.