HANYOUNG NUX HY Series Instruction Manual

HANYOUNG NUX HY Series Instruction Manual

Digital temperature controller
Available languages

Available languages

Quick Links

HY series
Digital temperature controller
INSTRYCTION MANUAL
Thank you for purchasing HANYOUNG product. please check whether
the product is the exactly same as you ordered. before using the
product, please read this instruction manual carefully. please keep this
manual where you can view at any time.
▍ Safety information
Before using the product, please read the safety information throughly and use it properly.
Alerts declared in the manual are classified to danger, warning and caution by their criticality
DANGER
Danger indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
WARNING
Warning indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
CAUTION
Caution indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury
DANGER
• There is a danger of occurring electric shock in the input/output terminals so please never let you body or conductive substance is touched
WARNING
• If there is a concern about a serious accident caused by a
malfunction or abnormality of this product, please install an
external protection circuit and device a scheme for preventing an
accident.
• Thisd product does not contain an electric switch or fuse, so the
user needs to install a separate electric switch or fuse
externally.(Fuse rating : 250 V 0.5 A)
• To prevent defection or malfunction of this product, apply a
proper power voltage in accordance with the rating.
• To prevent electric shock or malfunction of product, do not
supply the power until the wiring is conpleted.
CAUTION
• The contents of this manual may be changed without prior
notification.
• Before using the product you purchased, make sure that it is
exactly what you ordered.
• Make sure that there is no damage or abnormality of the product
during the delivery.
• Make sure that there is no damage or abnormality of the product
during the delivery.
• Use this product within the range of the operating ambient
temperature, 0 ~ 50 °C (When it is closely installed max 40°C) and
ambient humidty, 35 ~ 85 %R.H (No condensation).
• Do not use this product at any place with occuring
corrosive (especially noxious gas or ammonia)or flammable gas.
• Do not use this product at any place with direct vibration or
impact.
• Do not use this product at any place with liquid, oil, medical
substances, dust, salt or iron contents.(use at pollution level 1 or 2)
• Do not polish this product with substances such as alchol or
benzene.(use neutral detergent.)
• Do not use this product at any place with a large inductive difficulty
or occurring static electrictly or magnetic noise.
• Do not use this product at any place with possible thermal
accumulation due to direct sunlight or heat radiation.
• Install this product at place under 2,000m in altitude.
• When the product gets wet, the inspection is essential because
there is danger of an electric leakage or fire
• In case of inputting thermocouple, use a compensating cable. (if
using a normal wire, there is a possibility of occurring temperature
error.)
• For R.T.D input, use a cable which is a lead wire has small
resistances and resistances of there wires shall be the same. (if the
there wires have different resistances then there will be a
temperature error.)
• To avoid an effect of inductive noise to input signal cables, use the
product after separating the input signal cables from power,
output and load cables.
• Separate an input signal cable from an output signal cable. if
separating is not possible, please use the input siganal cable after
sheilding it.
• Use non-each sensor with thermocouple. (in case of using earth
sensor, there is a possibility of occurring malfunction caused by a
short circuit.)
• If there is excessive noise from the power supply, using insulating
transformer ans noise filter is recommended. the noise filter must
be attached to a panel which is already connected to a ground and
▍ Suffix code
Model
Code
HY-
⃞-
8000S
8200S
Dimension
72D
48D
Control type
P
K
Input
P
Control output
M
Alarm output
Control action (Internal selection)
Range code
※ Alarm output can not be specified other than model name HY-8200S.
▍ Dimension and panel cutput
Model
A
B
C
HY-48D
48
48
112
HY-72D
72
72
125
HY-8000S,
96
96
141
HY-8200S
HANYOUNGNUX CO.,LTD
28, Gilpa-ro 71 beon-gil, Nam-gu, Incheon, Korea
Tel : (82-32)876-4697
http://www.hynux.com
• Since this product is not designed with explosion-
protective structure, do not use it any place with flammable or
explosive gas
• Do not decompose, modify, revise or repair this product. this may
be a cause of malfunction, electric shock or fire.
• Reassemble this product while the power is OFF, otherwise, it may
be a cause of malfunction or electric shock.
• If you use the product with methods other than specified by the
manufacturer, there may be bodily injuries or property damages.
• There is a possibility of occurring electric shock so please use
this product after installing it on to a panel while it is operating.
the wire between the filter output side and power supply terminal
must be short as possible.
• If twisting the power cables closely together then it is effective
against noise.
• If the alarm functions are not properly set then it will not
be output when the product is malfunctiong. therefore, maek sure
its movements are properly working before the operation.
• Turn the power OFF when replacing a sensor.
• Use an auxiliary relay in case of high frequent operation such as
proportional operation or etc. ist life span will be shorter if
connecting a load without permissible rating of output relay. in this
case. using SSR output type is recommended.
◦Using electromagnetic switch : proportional cycle : set it avobe
20 sec
◦Using SSR : proportional cycle : set it above 1 sec.
◦Life span of contact point output : mechanical life span : avobe
10 million times (with no load) electrical life span : 100thousand
times (250 V a.c.3 A : with the rated load)
• Do not connect anything to the unsed terminals.
• After checking the polarity of termanal, connect wires at the
correct position.
• When this product is connected onto a panel, use a circuit breaker
or switch approved with IEC60947-1 or IEC60947-3.
• Install a circuit breaker or switch at near place for convient use.
• Write down on a label that if the circuit breaker or switch is
operating then the power will be disconnected since the circuit
breaker or switch is installed.
• For the continuous and safe use of this product, the periodical
maintenance is recommened.
• Some parts of this product have limited life span, and others are
changed by their usage.
• The warranty period for this product including parts is one year if
this product is properly used.
• When the power is on, the preparation period of contact output is
required. in case of using signals of external interlock circuit or etc.,
use it with a delay relay.
• In case of replacing this unit with a spare unit, make sure its
compatibility because its operation cna be different by different
parameter settings even thought the model name is the same.
• Before using a temperature controller, there could be a
temperature difference between PV of the temperature controller
and the actual temperature so please operate the temperature
controller after compensating the temperature difference
appropriately.
Description
Digital temperature controller
96(W) X 96(H)
96(W) X 96(H) (Alarm setting general specification)
72(W) X 72(H)
48(W) X 48(H)
Proportional control
K thermocouple
RTD, Pt 100 Ω (IEC)
Relay
N
None
O
High alarm (HY-8200S)
R
Reverse action (Heating control)
Refer to the range and input code
D
E
F
G
100
44
45
45
+0.5
+0.5
-0
-0
110
67
68
68
+0.5
+0.5
-0
-0
125
89
91
91
+0.5
+0.5
-0
-0
▍ Specification
Model
W x H x D (mm)
Thermocouple input
Fax :(82-32)876-4696
Input sampling cycle
Input
MK2101KE200409
Allowable wiring resistance
Performance
Control
function
and
Input disconnection
output
Alarm setting range
Control output
Alarm output
Power supply voltage
Voltage fluctuation rate
Power consumption
Ambient temperature/humidity
Storage temperature
Weight (g)
▍ Range and input code
Classification
Thermocouple
RTD
▍ Connection diagram
■ HY
8000S
■ HY
72D
※ 110 V a.c. or 220 V a.c. can be selected by the internal dip switch.(Default : 220 V a.c.)
▍ Terminology & function explanation
■ Proportional control
110 V a.c./220 V a.c.
50/60 Hz(Universal)
Temperature
PB
Setting
volume
ON
OFF
20mA d.c.Max
100%
Unit : mm
0%
• Proportional control is that an outout capacity regarding a
setting value (SV) is proportionally operated by a deviation. the
width which the output is varied within 0~100% is called
proportional band(PB). therefore, for reverse action, if PT =
present (process) temperature, PB = proportional band
110 V a.c./220 V a.c.
• PT<PB→Output capacity 100 %, PT>PB→Output capacity
50/60 Hz(Universal)
0 %, PT=PB→Output capacity 50 %
※ PT : Present(process) temperature, PC : Proportional cycle,
SV : Setting value(temperature), PB : Proportional band
■ Reset volume (RST)
Temperature
Over shoot
• For proportional control, when the controlling temperature (PT)
Setting
and SV* are the same, it generates 50 % of output so that there is
volume
constant error(normal deviation) by heat capacity or etc. of a
H
I
controlling target. to eliminate this matter, change the output
Above 60
Above 60
capacity by reset volume.
Above 90
Above 90
• Display value < setting value : turn the volume in clockwise.
• Display value > setting value : turn the volume in
Above 120 Above 120
counterclockwise.
ON
Output
OFF
HY-8000S,
HY-72D, HY-48D
HY-8200S
96.0 x 96.0 x 125.0
RTD input
Resolution
Allowable signal
Thermocouple reciprocating 100 Ω or less
source resistance
RTD (10 Ω or less, but the resistance between 3 wires should be the same)
Display accuracy
Withstand voltage
2,000 V a.c. 50/60 ㎐, 1 minute (between different live parts)
Setting range
Proportional band
Manual reset (MR)
Proportional cycle
Hysteresis
0.2% fixed (on ON / OFF control)
When the range is over 10 ℃, the output is turned off.
detection
Alarm type
Model HY-8200S only, high-limit absolute alarm
Alarm hysteresis
Contact capacity: 1 C, 250 V a.c., 5 A (resistive load)
Contact capacity: 1 c, 250 V a.c., 5 A (resistive load) ※ Only for model HY-8200S
110/220 V a.c. 50/60 Hz (shared)
However, Model HY-48D is 110/220 V a.c. (Select by internal dip switch)
± 10% of power supply voltage
0 ~ 50 ℃, 35 ~ 85 % RH (whithout condensation)
700
POWER
Code
Input
100-240 V a.c.
HY-8000S, 8200S
50/60 Hz 3 Va
5
8
K
12
설정값
13
3
5
Pt 100 Ω
6
ON
8
OFF
100%
0%
■ HY
POWER
100-240 V a.c.
50/60 Hz 3 Va
POWER
100-240 V a.c.
50/60 Hz 3 Va
■ HY
POWER
100-240 V a.c.
50/60 Hz 3 Va
220 V a.c.
110 V a.c.
50/60 Hz(Universal)
■ Limit(HY-8200S)
PT
Time
PC
220 V a.c.
PB
110 V a.c.
4mA d.c.Min
50/60 Hz(Universal)
SV
• Output : Example of ON/OFF + ON/OFF operation
※ PT* : Present(process) temperature,
PC* : Proportional cycle,
SV* : Setting value(temperature),
PB* : Proportional band
■ Proportional band(PB)
• For proportional control : if the proportional band(PB) is narrow,
then the output's variable width will become smaller so that the
time which the controlling temperature (PT) is approaching to
SV* is fast. also, OFF-set(deviation)becomes small. however, if
Hunting
Adjusting sensitivity
PB* is too narrow, then there is over shoot or hunting, PB* can
be set within the max range of 1~10%. if turn the PB volume in
clockwise then PB* gets larger. if turn the PB volume in
counterclockwise then PB gets smaller.
• For ON-OFF control : for the case of selecting ON-OFF control,
the adjusting sensitivity is varied within the max range of 1~10%
Time
by the PB volume.
HY-800S
HY-72I, HY-48I
72.0 x 72.0 x 110.0
48.0 x 48.0 x 100.0
K
Pt 100 Ω
500 ms
1 ℃
±1 % of FS ±1 Digit
Same as input range
0.1 ~ 10.0 % of FS
±50 % of ㎷ (Output)
Output -50 ~ +50 %
Within range
1 ℃ fixing
POWER
100-240 V a.c.
50/60 Hz 3 Va
3 VA or less
-25 ~ 65 ℃
750
500
450
Range (℃)
HY-72D
HY-48D
POWER
현재온도
100-240 V a.c.
온도
0 ~ 399
50/60 Hz 3 Va
POWER
0 ~ 399
100-240 V a.c.
50/60 Hz 3 Va
비례대
0 ~ 1199
0 ~ 1199
0 ~ 199
0 ~ 399
비례주기
0 ~ 199
0 ~ 399
20mA d.c.Max
비례대
4mA d.c.Min
8200S(Built-in alarm output)
설정값
POWER
100-240 V a.c.
50/60 Hz 3 Va
220 V a.c.
온도
오버슈트
110 V a.c.
헌팅
조절감도
50/60 Hz(Universal)
설정값
48D
110 V a.c./220 V a.c.
50/60 Hz(Universal)
ON
출력
OFF
220 V a.c.
110 V a.c.
50/60 Hz(Universal)
110 V a.c./220 V a.c.
Main
50/60 Hz(Universal)
Limit
Main
ON
OFF
Limit
ON
OFF
시간