HANYOUNG NUX NP100 Manual
Hide thumbs Also See for NP100:
NP100
Programmable Controller
Manual
Table of Contents
loading

Summary of Contents for HANYOUNG NUX NP100

  • Page 1 NP100 Programmable Controller Manual...
  • Page 2: Table Of Contents

    CONTENTS 1. SAFETY INFORMATION 2. ORDERING INFORMATION 3. TERMINAL ARRANGEMENT 4. DIMENSION & PANEL CUTOUT 5. INPUT & OUTPUT • Input Signal and Measurement Range • Output type 6. NAME & FUNCTION 7. LIST OF SETUP ITEMS 8. SETUP METHOD •...
  • Page 3: Safety Information

    1. SAFETY INFORMATION Before using the product, please read the safety information thoroughly and use it properly.Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality DANGER indicates an imminently hazardous situation which, if not avoided, will result in Danger death or serious injury WARNING indicates a potentially hazardous situation which, if not avoided, could result in...
  • Page 4 10. Do not use this product at any place with possible thermal accumulation due to direct sunlight or heat radiation. 11. Install this product at place under 2,000 m in altitude. 12. Attach the bractets(2pcs) on the fixed halls and tighten with a screwdriver. Fixing torque is about 14.7 N·cm (1.5 kg·cm) 13.
  • Page 5 ● Summary Program temperature controller is consisted of three types of modes: operation indicator mode, engineering mode, and program mode. Operation indicator mode is displayed when the power is ON and it indicates process value and set value, process value and output volume, and remaining time of the corresponding segment when in operation.
  • Page 6: Ordering Information

    2. ORDERING INFORMATION Model Code Information NP100-   Programmable Controller Control type Universal type (Heating) 0 None Time signal 2 points Option RS 485/422 Time signal 2 points +RS 485/422 3. Connection diagram Caution Main power must be OFF before wiring...
  • Page 7: Input & Output

    5. INPUT & OUTPUT Caution ● Measurement Input Wiring - When wiring the input line, cut off the controller and the external power. - Be careful with polarity and wire the input signal at some interval from power circuit and ground connection circuit. - Use shielded input cable when wiring and earth the shield 1 point.
  • Page 8: Name & Function

    6. NAME AND FUNCTION ● Function description 6-1. The function of individual LED LED display Function ① display lamp Lights when there is an ascending section of the segment. ② display lamp Lights when there is a soak section of the segment. ③...
  • Page 9 6-2. Function of control key Caution - Press the key firmly with your finger - Do not press the key with any sharpened thing. It could cause key malfunction Name Function • Operate the current pattern number. • Input the parameter setup value • Use when moving the parameter •...
  • Page 10 6-3. Function of 4 digits LED 1. Digital Formation 1Digit 2. Possible range of maximum indication using the button. 3. Rounding Up & Off of Digits ·Rounding Up ·When it becomes “9” in any digit besides the 4th digit (4D), it will be rounded up to the next digit when the button is pressed continuously.
  • Page 11: List Of Setup Items

    7. LIST OF SETUP ITEMS NP100 Caution - Preparation must be carried out in engineering mode when operating the controller. - There are setup mode for input and output functions and setup mode for control Power function in engineering mode but must start with the setup of the input and output functions.
  • Page 12 Caution ● Mode Setup - Mode setup is recommended after completing the Program operation since the set value varies in accordance with the setup of the specific parameter. - Each parameter may not be indicated in accordance with the selection of form, addendums, control type and varieties of the control system.
  • Page 13 - A set up value is changed and initialized depending on change of particular engineering mode. - There is a mode which cannot show up depending on controller's types, optional items, and control types, etc. NP100 【Program mode】 Power (ON) 【Operation indicator mode】...
  • Page 14: Setup Method

    8. SETUP METHOD ● Model NP 100 program temperature controller is divided into operation indicator mode and program mode and this program mode is further divided into engineering group and program group. Operation Operation indicator mode is displayed when the power is ON and it indicates process value and set value, Indicator Mode process value and volume of output, and remaining time of the corresponding segment when in operation.
  • Page 15 Always 1) Selection of Input Type : NP100 Program Temperature Controller supports universal input and can be conveniently used by selecting and setting up the input signal symbol of the “Input Type Range” List. This list includes the application input sensor and input types in accordance with voltage among the total of 18 types of input such as 12 types of thermocouple input (13 types of range), 2 types of R.
  • Page 16 8-1-2. Output Setup Group Signal Item Setup range Display condition Initial value Output group Setup below parameters. Refer to the output's types ON/OFF : ON/OFF Output type SSR : Contact-less relay output Always selection SCR : Current Output(4 - 20 mA) RLY : Relay Output Heating / Cooling REV :...
  • Page 17 8-1-3. Communication Setup Group Caution ● PC-LINK Communication / LADER Communication Wiring - Must disconnect the controller and the external power source when connecting to the communication terminal due to the danger of electric shock. - Connect the termination resistor (220Ω 1/4W) at the end or master located at the both ends of the communication equipment.
  • Page 18 8-1-4. Retransmission Setup Group Caution ● Retransmission Output Wiring - Must disconnect the controller and external power source when setting up/removing a receiver since there is a danger of electric shock. - Use same terminal for retransmission output and SPS output. Use of the terminal with what function of output is selected through parameter.
  • Page 19 8-1-5. Alarm Setup Group Caution ● Alarm Output Wiring - In relay close contact output, use relay to operate ON/OFF when the close contact capacity exceeds 240 V AC, resistance 1 A, and 30 V DC resistance load 1 A. - Connect the Bleeder resistance for the current to flow more than the opening and closing volume of the relay when opening or closing of small amount of current.
  • Page 20 8-1-6. Control Setup Group Signal Item Setup range Display condition Initial value Control setup group Setup below items. Fuzzy function Except OFF/ON selection ON / OFF HH.MM (00 hr. 00 min.) Time unit selection HH.MM MM.SS (00 min 00 sec.) Wait zone setup OFF/0~max.
  • Page 21 8-1-7. PID Setup Group Signal Item Setup range Display condition Initial value PID setup group Setup below items. P.I.D Anti Reset wind up Auto/50.0 ~ 200.0 % Auto control PID indication group OFF / P1Gr ~ P4Gr Always P.I.D n. Proportion 0.1 ~ 999.9 % 5.0 % control...
  • Page 22 8-1-8. Auto Tuning Setup Group Signal Item Setup range Display condition Initial value Setup below items. Auto tuning setup group Please select 1 at “ the AT operation selectin” to run. STD : Standard AT Except Auto tuning type LOW : Low PV AT(*1) RUN&...
  • Page 23 8-2. Program Group Setup ① After “finishing the setup of the engineering group, go into the program mode by pressing on “Group mode”. ② Also, on operation mode condition (initial mode when power is ON), engineering group will be indicated when pressing for 2.5 seconds, and program mode will be represented when pressing Power ON...
  • Page 24 8-2-1. Setup Group for Program Repeat Frequency ※ Setup group for program repeat frequency is indicated if the system is operated as follow when power is ON. 2.5 sec. Power Signal Item Setup range Display condition Initial value Setup group for program It sets up the repeat frequency and set up items.
  • Page 25: Program Setup

    8-2-2. Program Setup Mode ※ Setup group for program frequency will be indicated if operated as follow under the power ON condition (operation indicator mode). However, if you do not operate the key for more than 30 seconds, operation indicator mode will be displayed. 2.5 sec.
  • Page 26 1) Selection of Pattern Number : NP100 temperature controller can set up pattern 1, and pattern 2. Select “pattern 1” to operate in the setup item of pattern number selection. (Pattern refers to one setup program.) 2) Selection of segment number : It is designed to set up to 10 segments for each pattern.
  • Page 27: Specification

    9. SPECIFICATION 9-1. Input Input channel number 1 channel Input type Thermocouple, R.T.D(pt), Direct voltage Possible to change thermocouple thermoresistance within table's temperature range. Input range DC Voltage is going to be minimum voltage sensitivity within each of ranges, and maximum range is variable Sampling time 250 ms...
  • Page 28 9-2. Countrol output Contact capacity : 240 V AC 3 A, 30 V DC 3 A (resistive load) Contact : 1C Output operation : P.I.D control, ON / OFF Relay Proportional cycle : 1 ~ 1000 sec. contact output Output limit : 0.0 ~ 100.0 % range, higher limit(OL-H) or lower limit(OL-L) selectable (valid when AT) ON/OFF hysteresis : 0 ~ 100 % Time resolution : 0.1 % or 10 ms...
  • Page 29 9-5. Communication Interface Standard EIA RS485 Communication address 31, 1~99 setting available Communication method 2 wire half duplex Synchronization Start-stop synchronous mode Communication sequence None Communication distance 1.2Km max. Communication speed 600, 1200, 2400, 4800, 9600 BPS Start bit 1 BIT Data bit 7 or 8 BIT Parity bit...
  • Page 30 9-9. Power Supply Rated voltage 100 - 240 V AC, 50 - 60 Hz Tolerable voltage ±10 % of rated voltage regulation Power consumption MAX 10 VA(6.0 W max) 9-10. Insulation Resistance Primary terminal Secondary terminal MIN. 500 V DC 20 MΩ Primary terminal Ground MIN.
  • Page 31: Function

    9-12. Function -100.0 ~ 100.0 % for measuring input range Bias Valid setting a correction value. Measuring According to setup of SL-H, SL-L of measuring range, scaling Scaling Input is available. Filter OFF, 1 ~ 120 sec. Pattern 2 Patterns Segment 10 Segments / 1 pattern PID Group...
  • Page 32 9-13. Alarm Type 1) Output Tangent (When alarm rings : ON) Name Code ON condition OFF condition High absolute alarm 1(11) PV≥ALM PV< ALM–HYS Low absolute alarm 2(12) PV≤ALM PV >ALM+HYS High deviation alarm 3(13) DEV≥ALM DEV< ALM–HYS Low deviation alarm 4(14) DEV≤–ALM DEV >–ALM+HYS...
  • Page 33: Alarm Type & Code

    10. ALARM TYPE AND CODE (Notice) : Display lamp will be ON when output OFF in inverted type. Hysteresis (△ : Set point , : Mins Alarm set point ▲ : Alarm set point ) Code NO. Alarm type Function High absolute alarm Low absolute alarm High deviation alarm...
  • Page 34: Fnd Display

    11. FND DISPLAY ※ FND display in English In the introduction manual, please refer to a sign which is displayed as FND is marked as following English characters for some reason. Alphabet Alphabet Alphabet None...
  • Page 35: Program Setup Chart

    12. PROGRAM SETUP CHART Input type High limit range Low limit range High limit scale Low limit scale 8-1-1 Input setup group Output type Cycle time Hysteresis Preset output Max. output Min. output 8-1-2 Output setup group 8-1-5 Pattern ending Alarm type Alarm dead band Set value of alarm...
  • Page 36 HANYOUNG NUX CO., LTD. 28, Gilpa-ro 71 beon-gil, Nam-gu, Incheon, Korea TEL : (82-32)876-4697 FAX : (82-32)876-4696 http://www.hynux.com E-mail. [email protected] MA0102E140110...