9
|
Electrical installation
Installer reference guide
98
2 Connect the main power supply.
In case of normal kWh rate power supply
Interconnection cable
(= main power supply)
B
A
B
X1M
a Interconnection cable (=main power supply)
In case of preferential kWh rate power supply
Interconnection cable
(= main power supply)
Normal kWh rate
power supply
Preferential kWh rate
power supply contact
[9.8] Benefit kWh power supply
Connect X11Y to X11YB.
Wires: (3+GND)×1.5 mm²
a
1 2 3
X2M
X11YB
X11YA
X11Y
X1A
Wires: (3+GND)×1.5 mm²
Wires: 1N
Maximum running current: 6.3 A
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply contact:
16 V DC detection (voltage supplied by PCB). The
voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
EPRA08~12EAV3+W1 + ETVZ12S18+23EA6V+9W
Daikin Altherma 3 H MT F
4P634887-1 – 2021.03