Remaining hazards Units from the LABOM universal panel meter PH5100 are state of the art and safe to operate. A risk of danger can occur when deployed and operated improperly by untrained personnel. In this manual remaining hazards are marked by the following warning symbol:...
The universal panel meter PH5100 is a quite versatile process indicator with totalizing function. With a wide list of input types - thermocouples, thermo-resistance, voltage and current the PH5100 is capable of measuring the majority of the variables and sensors encountered in industrial processes.
Page 5
presents problems such as interrupted sensor, bad connection, etc. Table 02: Alarm functions Note: The figures are also valid for Alarm 2 (SPA2). - 5 - BA_074e, Rev.1C5 Operating instruction BA_074_2020-01_10.00 Universal panel indicator PH5100 Page 5/15...
powered off these information is not stored. 4.13 24 VDC auxiliary voltage source The standard version of the PH5100 provides an auxiliary power supply (24 VDC) for exciting field transmitters (terminal 13 on the rear panel). 4.14 Interface USB-Port (virtual COM-Port) to program the digital display.
• • • • It is recommended to use RC FILTERS (0,1uF in series with 100 ohms) to suppress the noise generated by contactors coils, solenoids, etc. - 8 - BA_074e, Rev.1C5 Operating instruction BA_074_2020-01_10.00 Universal panel indicator PH5100 Page 8/15...
When the controller is powered up, its firmware version is displayed for 3 seconds, after which the PH5100 starts normal operation, when the value of PV is displayed and the outputs are enabled. Before the indicator is ready to be used in a given process, it requires some basic configuration, consisting of assigning values to the parameters according to the desired behavior.
Defines if the total value is restored or reset on indicator power up Reset Reset Totalizer No reset of the Totalizer - 11 - BA_074e, Rev.1C5 Operating instruction BA_074_2020-01_10.00 Universal panel indicator PH5100 Page 11/15...
Serial number 4 least significant digits. Password protection The PH5100 indicator provides means for protecting the parameters configurations, not allowing modifications to the parameters values, avoiding tampering or improper manipulation. The parameter Protection ( ) in the Calibration level determines the protection strategy, limiting ...
Page 13
As an example, for the equipment with serial number 07154321, the master password is 9 3 2 1. The indicator serial number can be obtained by pressing for 5 seconds. - 13 - BA_074e, Rev.1C5 Operating instruction BA_074_2020-01_10.00 Universal panel indicator PH5100 Page 13/15...