Daikin Aurora Series Service Manual page 81

Hide thumbs Also See for Aurora Series:
Table of Contents
SiUS341802E
Program dry operation
Program
∗7
dry display
∗8
OFF
Thermostat status
ON
Fan
MF
:
Operating in L mode
Electronic
YE :
expansion valve
(Option)
Superheated degree control
A
7. Program dry display
No set temperature and airflow rate of the remote controller are displayed.
8. Thermostat status
Set temperature when operating the program dry mechanism.
a
b
Suction air temperature
∗9
Fan Operation
(Option)
Drain
MP
: OFF
pump kit
Aux.
∗16
EH
: OFF
electric heater
Humidifier
Hu
: OFF
No
Swing flap
Yes
Swing flap
∗11
Fan
MF
:
Operating with set airflow rate
Electronic
YE :
expansion valve
Closed
A
∗9. Fan operation
By setting the remote controller to Fan, the fan
will operate with thermostat OFF in set
temperature control operation mode.
∗10. Set wind direction
According to wind direction instruction from the
remote controller, the wind direction is set to
100% horizontal while in heating operation.
∗11. Fan
According to fan speed instruction from the
remote controller, the fan is put into operation
in LL mode while in heating operation.
12. Wind direction
When the heating thermostat turns OFF,
the wind direction will be set to 100%
horizontal.
Functions and Control
Fan
: Operating
MF
in L mode after it stops for 6 min.
Electronic
YE :
expansion valve
Closed
Drain pump kit
: OFF after 5-min.
MP
residual operation
(Option)
∗16
Aux.
electric heater
Humidifier
Fan
∗10
LL operation
Set wind direction
Electronic
expansion valve
Closed
13. Hot start
If the condenser inlet temperature exceeds 34°C (93.2˚F) at the time of starting operation or
after the completion of defrost operation, or until 3 minutes pass or Tc is above 52°C (125.6˚F),
hot starting will be conducted.
14. Thermostat status
∗15. Outlet air temperature drop protection
When the set temperature is below 24°C (75.2°F) or the electronic expansion valve opening is
small, the protection will be activated.
∗16. The control of auxiliary electric heater connected to FXTQ-TA models differ from this flowchart.
For details, refer to "Heater Control (FXTQ-TA Models)" on page 85.
Heating Operation
(option)
Drain
MP
pump kit
Swing flap?
∗12
Yes
Swing flap
Is
defrost operation in
progress?
No
Is hot
starting in progress?
No
DEFROST/HOT START
indicating lamp: OFF
Restart
Yes
prevention operating
in progress?
(4 min.)
No
Yes
Is test run
in progress?
No
∗14
(1)
Thermostat status
(2)
(Option)
∗16
Aux.
EH
EH
: OFF
electric heater
Hu
: OFF
Humidifier
Hu
∗15
MF
:
Fan
Operating with set airflow rate
YE :
Electronic expansion valve
Capacity control
A
(3)
–4˚C (24.8˚F)
–2˚C (28.4˚F)
Suction air temp.
Outline of Control (Indoor Unit)
: OFF
No
∗12
Set wind direction
Yes
∗13
Yes
(3)
(Option)
∗16
∗16
Aux.
EH
: OFF
: ON
electric heater
: ON
Humidifier
Hu
: ON
Is
outlet air
Yes
temperature drop protection
in progress?
No
MF
:
Fan
MF
:
Operating in L mode
YE :
a
(2)
(1)
b
Set temp.
DEFROST/HOT START
indicating lamp: ON
(Option)
Aux.
EH
: OFF
electric heater
Humidifier
Hu
: OFF
Fan
MF
:
Stop
Electronic
YE :
expansion valve
Open
68