Selecting Synchronized AMSECO Configurations

To select the input/outputs for AMSECO synchronized appliances, set the DIP switches as shown in Figure 4-13.
4.8.3

Setting the Loss of AC Delay

Normal selection for reporting loss of AC is 3 hours.
The ON position is for test purposes only and the normal position for Switch 4 is OFF. For testing the Low AC
reporting, you can temporarily turn Switch 4 ON without removing power.
Note:
Remember to turn the switch OFF when testing is complete.
4.8.4

Setting the Auxiliary Output

Switch 5 on the DIP switch determines how the auxiliary power operates on the HPF602ULADA.
The HPF602ULADA checks Switch 5 only when powering up the HPF602ULADA. If you change this switch,
you must remove both the AC power and the battery to force the HPF602ULADA to recognize the new switch
setting.
Figure 4-13 AMSECO Synchronized Configurations
Figure 4-14 Setting DIP Switch 4
Figure 4-15 Setting DIP Switch 5