Honeywell HPF602ULADA Installation & Operation Manual
Honeywell HPF602ULADA Installation & Operation Manual

Honeywell HPF602ULADA Installation & Operation Manual

6 amp nac expander
Table of Contents
HPF602ULADA
HPF602ULADA
6 Amp NAC Expander
6 Amp NAC Expander
INSTALLATION & OPERATION MANUAL
Honeywell Power Products
12 Clintonville Road
Northford, CT 06472-1653
USA
Honeywell
Power Products
Document 151341-L8
Rev:
P/N 151341-L8:P1
P1
ECN: 17-0298
Table of Contents
loading

Summary of Contents for Honeywell HPF602ULADA

  • Page 1 Honeywell Power Products HPF602ULADA HPF602ULADA 6 Amp NAC Expander 6 Amp NAC Expander INSTALLATION & OPERATION MANUAL Honeywell Power Products 12 Clintonville Road Northford, CT 06472-1653 Document 151341-L8 Rev: P/N 151341-L8:P1 ECN: 17-0298...
  • Page 2 [+ BAT-- ] to insure that there is no break in the battery connection wires. Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less as necessary. Honeywell is not responsible for any typographical errors.
  • Page 3: Table Of Contents

    Current Requirements (Standby and Alarm) ................9 4.3.1 Current Drawn From Host Panel ...................9 4.3.2 Current Drawn from Battery ....................9 Connecting the HPF602ULADA to a FACP ................11 4.4.1 Common Trouble Relay ......................12 Notification Appliance Wiring .....................13 4.5.1 Class A Supervised Wiring ....................13 Class A Output Notification Circuits .................13...
  • Page 4 HPF602ULADA Distributed Power Module Installation Manual 4.8.2.1 Selecting Synchronized Faraday Configurations ............18 4.8.2.2 Selecting Synchronized Gentex Configurations ............19 4.8.2.3 Selecting Synchronized System Sensor Configurations ...........19 4.8.2.4 Selecting Synchronized Wheelock Configurations ............19 4.8.2.5 Selecting Synchronized AMSECO Configurations ............20 4.8.3 Setting the Loss of AC Delay ....................21 4.8.4 Setting the Auxiliary Output ....................21...
  • Page 5: Introduction

    Section 1 Introduction The HPF602ULADA is a notification appliance circuit and auxiliary power expander that provides up to 6 amps of filtered, 24 volt power for powering notification appliances and auxiliary devices. The HPF602ULADA provides its own AC power connection, battery charging circuit, and battery connections. Used with security and fire alarm control panels, the HPF602ULADA enables you to connect and distribute power to many more devices than your panel may normally allow.
  • Page 6: System Overview

    151341-L8 Section 3 System Overview CAUTION Each output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will cause it to shut down (power limit). The circuit will automatically reset once you remove the overload condition. Terminal Descriptions and Electrical Ratings Terminal # Description Ratings...
  • Page 7: Notification Appliance Circuit Terminals

    Terminals 3 through 10 are the notification appliance circuit output terminals. Each of the four circuits are rated at 3 amps, although you can only draw a total of 6 amps from the HPF602ULADA. The HPF602ULADA outputs are short-circuit protected (power limited) according to UL 864 standards. Overcurrent indicators are yellow LEDs.
  • Page 8 151341-L8 For Option: These Inputs: Control These Outputs: Input 1 or Outputs 1, 2, 3, and 4 Class B ANSI temporal- Input 2 coded circuits Input 1 Outputs 1 and 2 Class B circuits Input 2 Outputs 3 and 4 Class B circuits Input 1 Output 1...
  • Page 9: Installation

    Section 4 Installation Before installing the HPF602ULADA, the AC input must first be wired into the building’s main electrical power through the TB1 terminals (see Figure 4-2). Shut off the electrical power to the HPF602ULADA, and then complete the general installation of the HPF602ULADA using the information in this section.
  • Page 10: Current Requirements (Standby And Alarm)

    30 mA 4.3.2 Current Drawn from Battery Batteries used with the HPF602ULADA must not exceed 35AH. (33AH max. for FM (Factory Mutual) Installations). Batteries larger than 7 AH will not fit into the HPF602ULADA cabinet and must be housed in the...
  • Page 11 The above numbers were calculated assuming the use of 7 AH batteries at 100% of rated capacity. The total current of the HPF602ULADA, plus all items powered from it, must not exceed 6 A when the panel is in alarm. Use Table 4-2 to ensure that the current does not exceed 6 A and, that the desired amount of standby is...
  • Page 12 Current per Device Devices Current Current For each device use this formula: This column X This column Current per number of devices. HPF602ULADA Distributed Power Standby: 75 mA 75 mA Module Alarm: 205 mA 205 mA (Current draw from battery)
  • Page 13: Connecting The Hpf602Ulada To A Facp

    Common Trouble Relay The HPF602ULADA has a Form C trouble relay built into Terminals 11-13. The relay provides a normally open and a normally closed contact, both of which are rated at 2.5A. The trouble relay will deactivate under any trouble condition.
  • Page 14: Notification Appliance Wiring

    151341-L8 Note: The N.C. contact is the contact that is closed when the HPF602ULADA has power and there are no trouble conditions. Must be connected to a power limited source Figure 4-3 Trouble Relay Connection Example Notification Appliance Wiring Note: Not all devices can use the sync feature.
  • Page 15: Class B Supervised Wiring

    Class B Supervised Wiring Figure 4-5 shows how to wire for Class B input and output supervision. Use in/out wiring methods for proper supervision (Refer to the Appendix for notification appliances approved for use with the HPF602ULADA.) Class B Output Notification Circuits Figure 4-5 shows four, 1.5 A devices wired as Class B.
  • Page 16: Class B Supervised Input Circuits

    Use an EOL resistor as shown to enable notification appliance circuit input supervision. Some panels use EOLs that have a different value from the 4.7k ohm EOL resistor used by the HPF602ULADA. In this case, the EOL must be UL listed for the fire alarm control panel (not the HPF602ULADA).
  • Page 17: Dip Switch Settings

    The position of Switches 4 and 5 does not affect the relationship of inputs to outputs. Note: The HPF602ULADA checks switches 1, 2, 3, and 6 only when powering up the HPF602ULADA. If you change these switch settings, you must remove both the AC power and the battery to make the HPF602ULADA recognize the new...
  • Page 18: Input/Output Configurations That Select Ansi Temporal-Coded Outputs

    151341-L8 settings. Figure 4-7 Setting DIP Switches 1-3 Figure 4-8 Setting DIP Switches 1-3 (Continued) Note: For 100 mS input signal debounce with no synchronization DIP switches 6 and 7 must be turned On. 4.8.1.1 Input/Output Configurations That Select ANSI Temporal-Coded Outputs The DIP switch settings marked with an asterisk (*) in Figure 4-7 and Figure 4-8 are designed to produce ANSI temporal-coded outputs from a constant input.
  • Page 19: Selecting Synchronized Output Configurations

    The HPF602ULADA can also produce temporal patterns if the inputs are non-ANSI temporal configurations. 4.8.2 Selecting Synchronized Output Configurations The following sections describe how to configure the HPF602ULADA as a synchronization power expander for Amseco, Faraday, Gentex, System Sensor, or Wheelock synchronized horn/strobe appliances. Note: In order for the synchronization feature to operate properly, make sure you have set the DIP switches for the proper manufacturer.
  • Page 20: Selecting Synchronized Gentex Configurations

    151341-L8 4.8.2.2 Selecting Synchronized Gentex Configurations To select the input/outputs for Gentex synchronized appliances, set the DIP switches as shown in Figure 4-10. Figure 4-10 Gentex Synchronized Configurations 4.8.2.3 Selecting Synchronized System Sensor Configurations To select the input/outputs for System Sensor synchronized appliances, set the DIP switches as shown in Figure 4-11.
  • Page 21: Selecting Synchronized Amseco Configurations

    Switch 5 on the DIP switch determines how the auxiliary power operates on the HPF602ULADA. The HPF602ULADA checks Switch 5 only when powering up the HPF602ULADA. If you change this switch, you must remove both the AC power and the battery to force the HPF602ULADA to recognize the new switch setting.
  • Page 22: Sample Applications

    151341-L8 Section 5 Sample Applications The drawings in this section show various HPF602ULADA configurations, including “daisy-chaining”. Notification Power Applications HPF602ULADA Local Fire Alarm Control Panel Figure 5-1 Input 1 Activates All Four Outputs HPF602ULADA Local Fire Alarm Control Panel Figure 5-2 Input 1 Activates NACs 1 and 2; Input 2 Activates NACs 3 and 4...
  • Page 23 HPF602ULADA Distributed Power Module Installation Manual Note: When multiple power supplies are used with one control unit they will not sync with each other HPF602ULADA Local Fire Alarm Control Panel HPF602ULADA Figure 5-3 One Control Activating Two HPF602ULADAs HPF602ULADA Local Fire Alarm...
  • Page 24: Non-Resettable Power Application

    Non-Resettable Power Application The HPF602ULADA provides a dedicated 3 A auxiliary power output that you can select as non-resettable (output is always on). See Section 4.8.4 for setting the auxiliary power. If you need more than 3 A, wire the inputs as shown in Figure 5-6.
  • Page 25: Door Holder Application

    HPF602ULADA Distributed Power Module Installation Manual Door Holder Application In a typical door holder application, the door holder power must be interrupted to close all fire doors under the following conditions: • Any active alarm condition. • AC power failure (to conserve battery power).
  • Page 26: Trouble Conditions

    151341-L8 Color Description BATT Yellow When ON, a low battery condition exists. Green When OFF, there is no AC power to the unit. Under normal conditions, this LED is ON to indicate the presence of AC power. See Figure 4-2 for locations of LEDs. Trouble Conditions Trouble Condition What Happens...
  • Page 27: Earth Fault Resistance

    HPF602ULADA Distributed Power Module Installation Manual Earth Fault Resistance Table 6-1 lists the earth fault resistance detection for each applicable terminal on the FACP. Table 6-1: Earth Fault Resistance Values by Terminal Terminal Value Function Terminal Label Number (in kohms)
  • Page 28: Replacing The Control Panel

    151341-L8 Remove the two heat sink screws. The heat sink screws are located on the top of the cabinet. See Figure 6-1. Figure 6-1 Mounting Screw Locations Remove the four chassis mounting screws. See Figure 6-1 for chassis screw locations. Carefully remove the control panel.
  • Page 29: Ul Listed Notification Appliances

    Synchronization is UL listed for multi-circuit operation. Notification Appliances Table A-1 below lists notification appliances compatible with the HPF602ULADA. Appliances which can be synchronized indicate the type of sync available in the columns marked Audio and/or Visual.
  • Page 30 HPF602ULADA Distributed Power Module Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Vibrating Bell Vibrating Bell Single Stroke Bell 2700 -M. -R, -T, -Y, -Z Strobe 2701 Series Strobe 2705 Series Strobe 2820 Snyc Temporal Horn/Strobe...
  • Page 31 151341-L8 UL Listed Notification Appliances Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type 5378 8-Tone Horn/Strobe 5383 8-Tone Horn/Strobe with Sync Strobe 5386 8-Tone Horn/Strobe with Sync Strobe 5387 8-Tone Horn/Strobe with Sync Strobe 5388 8-Tone Horn/Strobe with Sync Strobe 5508 Single Gang Sync Strobe 5509...
  • Page 32 HPF602ULADA Distributed Power Module Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type S2415-FC Strobe S241575-FC Strobe S2430-FC Strobe 130-3117C Mini Horn 130-3147C Mini Horn BLV-6 Vibrating Bell BLV-10 Vibrating Bell BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC...
  • Page 33 151341-L8 UL Listed Notification Appliances Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type GEC-24-15 Horn/Strobe GEC-24-30 Horn/Strobe GEC-24-60 Horn/Strobe GEC-24-75 Horn/Strobe GEC-24-177 Horn/Strobe Gentex GEC-24-110 Horn/Strobe GEC-24-15/75 Horn/Strobe GX91 MiniHorn Steady Tone GX93 MiniHorn Temporal Tone HG124 Horn HS24-15 Horn/Strobe HS24-30...
  • Page 34 HPF602ULADA Distributed Power Module Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Chime Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe Horn Horn Horn Horn WHT Wall 4x4 Horn Red Wall 4x4 HGRL Horn Red Wall 2x4...
  • Page 35 151341-L8 UL Listed Notification Appliances Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type 4-Wire Horn/Strobe PC4W 4-Wire Horn/Strobe P4WH 4-Wire Horn/Strobe High Candela PC4WH 4-Wire Horn/Strobe High Candela P4RK 4-Wire Horn/Strobe PC4RK 4-Wire Horn/Strobe P4RHK 4-Wire Horn/Strobe High Candela PC4RHK 4-Wire Horn/Strobe High Candela PC4RH...
  • Page 36 HPF602ULADA Distributed Power Module Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type SCRHK Strobe High Candela SRL, SRL-P, SRL-SP* Strobe Red Wall 4x4 SWL, SWL-P, SWL-ALERT Strobe White Wall 4x4 SWL-CLR-ALERT* SCRL Strobe Red Ceil 4x4...
  • Page 37 151341-L8 UL Listed Notification Appliances Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type HS-24 Horn HS4-241575W Horn/Strobe HS4-24MCW Horn/Strobe HS4-24MCWH Horn/Strobe HS4-24MCC Horn/Strobe MIZ-24S Mini Horn Strobe MT-121575W MultitoneHorn Strobe MT-241575W Multitone Horn Strobe MT-24MCW Multitone Horn Strobe MTWP-2475W Multitone Horn Strobe MTWP-2475C...
  • Page 38 HPF602ULADA Distributed Power Module Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type RSSR-2475W Strobe RSSR-2475C Strobe RSSR-24110C Strobe RSSA-24110W Strobe RSSB-24110W Strobe RSSG-24110W Strobe RSSR-24110W Strobe RSSA-24MCC Multi-Cd Strobe RSSB-24MCC Multi-Cd Strobe RSSG-24MCC Multi-Cd Strobe RSSR-24MCC...
  • Page 40 Honeywell Power Products P/N 151341-L8 12 Clintonville Rd., Northford, CT 06472-1653 Phone: (203) 484-7161...

Table of Contents