  • Page 1 FusionModule500 Smart Mini Data Center Product Description (ECC800e) Issue Date 2017-04-20 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Product Description (ECC800e) About This Document About This Document Purpose This document describes the FusionModule500 Smart Mini Data Center (smart module for short) in terms of the appearance, features, and specifications for you to understand the product information. Intended Audience This document is intended for: ...
  • Page 4 FusionModule500 Smart Mini Data Center Product Description (ECC800e) About This Document Symbol Description NOTICE is used to address practices not related to personal injury. Calls attention to important information, best practices and tips. NOTE is used to address information not related to personal injury, equipment damage, or environment deterioration.
  • Page 5: Table Of Contents

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) Contents Contents About This Document ....................... ii 1 Overview ........................... 1 1.1 Positioning ................................1 1.2 Features................................. 3 2 Typical Application Scenarios and Configurations ............5 2.1 Typical Scenarios..............................5 2.2 Typical Configuration (Single-Phase 220 V Power System) ..................6 2.3 Typical Configuration (Dual-Live Wire 208 V Power System) ................13...
  • Page 6 FusionModule500 Smart Mini Data Center Product Description (ECC800e) Contents 3.4.4 Smoke Detector ..............................42 3.4.5 T/H Sensor ................................44 3.4.6 Door Status Switch ............................45 3.4.7 (Optional) Intelligent Battery Monitoring System ....................45 3.4.7.1 CIM................................46 3.4.7.2 BIM................................56 3.4.8 Water Sensor ..............................57 3.4.9 (Optional) Pad ..............................58 3.4.10 (Optional) WiFi Converter ..........................59...
  • Page 7: Overview

    1.1 Positioning To meet the requirements for customers' growing services, Huawei launches the FusionModule500 that can be rapidly deployed and flexibly expanded. The FusionModule500 is positioned as a smart module solution and occupies about 10 m . It is mainly used in the equipment rooms of county-level governments, bank business outlets, and small and medium-sized enterprises.
  • Page 8 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 1 Overview Figure 1-1 Position of the FusionModule500 in the financial industry (1) FusionModule5000 (2) FusionModule2000 (3) FusionModule800 (4) FusionModule500 Issue 01 (2017-04-20) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Features

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 1 Overview Figure 1-2 Position of the FusionModule500 for governments (1) FusionModule5000 (2) FusionModule2000 (3) FusionModule800 (4) FusionModule500 1.2 Features Integration The smart module integrates the cabinets, power supply and distribution system, and monitoring system to provide a comprehensive solution.
  • Page 10 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 1 Overview Safety and Reliability  The Converged Cabinet incorporates the UPS, monitoring system, and power distribution system that are designed in modular manner and feature high security and reliability.  The powerful monitoring system allows you to master the infrastructure status anytime and improves the protection capability of cabinets.
  • Page 11: Typical Application Scenarios And Configurations

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Typical Application Scenarios and Configurations 2.1 Typical Scenarios The smart module is mainly used in the equipment rooms of bank business outlets, small and medium-sized enterprises, and governments.
  • Page 12: Typical Configuration (Single-Phase 220 V Power System)

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations 2.2 Typical Configuration (Single-Phase 220 V Power System) Single-Cabinet Solution Figure 2-1 24 U Converged Cabinet Table 2-1 Typical configuration 1 Item Specifications Cabinet dimensions (W x D x H)
  • Page 13 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Figure 2-2 42 U Converged Cabinet Table 2-2 Typical configuration 2 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm Power backup time 15–240 minutes...
  • Page 14 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Two-Cabinet Solution Figure 2-3 Converged Cabinet+battery cabinet Table 2-3 Typical configuration 3 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm Power backup time 15–240 minutes...
  • Page 15 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications switch (optional) Figure 2-4 Converged Cabinet+network cabinet Table 2-4 Typical configuration 4 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm...
  • Page 16 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications status sensor (network cabinet, optional), smoke detector, water sensor, pad (optional), WiFi converter (optional), infrared remote control module (optional), GSM modem (optional), NetEco (optional),...
  • Page 17 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications Power distribution UPS2000-G, PDU5000, PDU2000, and battery NOTE If batteries are configured, battery packs are not required. Monitoring ECC800e, T/H sensor (Converged Cabinet), T/H sensor (network cabinet, optional),...
  • Page 18 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Table 2-6 Typical configuration 6 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm NOTE Network cabinet dimensions (W x D x H):...
  • Page 19: Typical Configuration (Dual-Live Wire 208 V Power System)

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations 2.3 Typical Configuration (Dual-Live Wire 208 V Power System) Single-Cabinet Solution Figure 2-7 42 U Converged Cabinet Table 2-7 Typical configuration 1 Item Specifications Cabinet dimensions (W x D x H)
  • Page 20 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Two-Cabinet Solution Figure 2-8 Converged Cabinet+battery cabinet Table 2-8 Typical configuration 2 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm Power backup time 15–240 minutes...
  • Page 21 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications (optional), NetEco (optional), independent deployment AI/DI unit (optional), and LAN switch (optional) Figure 2-9 Converged Cabinet+network cabinet Table 2-9 Typical configuration 3 Item Specifications...
  • Page 22 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications camera (optional), VCN500 (optional), door status sensor (Converged Cabinet), door status sensor (network cabinet, optional), smoke detector, water sensor, pad (optional), WiFi converter (optional),...
  • Page 23 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications Power backup time 15–240 minutes Power distribution UPS2000-G, PDU5000, PDU2000, battery, and transformer NOTE If batteries are configured, battery packs are not required. Monitoring...
  • Page 24 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Four-Cabinet Solution Figure 2-11 Network cabinet+Converged Cabinet+battery cabinet+battery cabinet Table 2-11 Typical configuration 5 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm...
  • Page 25 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications optional), smoke detector, water sensor, pad (optional), WiFi converter (optional), infrared remote control module (optional), GSM modem (optional), intelligent battery monitoring system (optional), NetEco...
  • Page 26: System Architecture

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture System Architecture 3.1 Structural System The smart module houses the battery cabinet, Converged Cabinet, and network cabinet, and employs air channels before and after cabinets. The cabinet possesses the following features: ...
  • Page 27: Power Supply And Distribution System

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications (42 U) Specifications (24 U) Installation mode Installed on a concrete floor Installed on a concrete floor or electrostatic discharge or ESD floor (ESD) floor Static load...
  • Page 28 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-2 Power distribution conceptual diagram for the 220 V single-phase scenario with the 6 kVA/10 kVA UPS The power distribution system meets the power supply requirements of single-phase 220 V/230 V/240 V.
  • Page 29: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications (10 Specifications (6 Specifications (3 kVA UPS) kVA UPS) kVA UPS)  100 Ah/12 V  100 Ah/12 V Surge protection Level D SPD Level D SPD...
  • Page 30: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Efficiency Communications port (optional) USB/RS485 Dimensions (W x D x H) 430 mm x 615 mm x 86 mm Weight 14 kg Noise < 55 dB 3.2.1.3 6 kVA UPS...
  • Page 31: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Efficiency Communications port (optional) USB/RS485 Dimensions (W x D x H) 430 mm x 615 mm x 86 mm Weight 14 kg Noise < 55 dB 3.2.1.4 10 kVA UPS...
  • Page 32: Pdu5000

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Efficiency 94.5% Communications port (optional) USB/RS485 Dimensions (W x D x H) 430 mm x 615 mm x 86 mm Weight 16 kg Noise < 55 dB 3.2.1.5 PDU5000...
  • Page 33: Pdu2000

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications (3 kVA Specifications (6 kVA UPS) UPS/10 kVA UPS) –5° C to +40° C –5° C to +40° C Operating temperature Humidity 5%–95% RH 5%–95% RH –40° C to +70° C –40°...
  • Page 34 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-7 Electrical conceptual diagram for the 208 V dual-live wire system configured with the 10 kVA/6 kVA UPS Table 3-8 Power distribution system technical specifications Item Specifications (10 kVA...
  • Page 35: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.2.2.2 6 kVA UPS Figure 3-8 UPS2000-G Table 3-9 6 kVA UPS technical specifications Item Specifications Rated capacity 5.4 kVA Maximum input current 31 A Number of phases Dual-live wire Input power factor (full load) >...
  • Page 36: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.2.2.3 10 kVA UPS Figure 3-9 UPS2000-G Table 3-10 10 kVA UPS technical specifications Item Specifications Rated capacity 9 kVA Maximum input current 48 A Number of phases Dual-live wire Input power factor (full load) >...
  • Page 37: Pdu5000

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.2.2.4 PDU5000 Figure 3-10 PDU5000 Table 3-11 PDU5000 technical specifications Item Specifications Maximum input current 63 A Number of phases Dual-live wire input frequency 60 Hz Input voltage 208 V...
  • Page 38: Transformer

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-12 PDU2000 technical specifications Item Specifications (Vertically Installed Full-Height PDU2000) Rated input voltage 100–240 V Rated current 40 A Input frequency 50 Hz/60 Hz Input port Cord end terminal, no input power cable...
  • Page 39: Battery Cabinet

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-11 Battery pack Table 3-14 Battery pack technical specifications Item Specifications (7 Ah/240 Specifications (9 Ah/240 Capacity (single battery 7 Ah 9 Ah pack) Voltage (single battery 240 V...
  • Page 40 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-12 Battery cabinet Issue 01 (2017-04-20) Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd.
  • Page 41 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-13 Battery cabinet components (1) Circuit breaker (2) BIM (3) Batteries (4) BIB (5) CIM Table 3-15 Battery cabinet technical specifications Item Specifications Dimensions (H x W x D)
  • Page 42 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Dynamic load 1000 kg Weight 128 kg (excluding batteries) Protection level IP20 Table 3-16 lists the number of batteries with different capacity a single battery cabinet can house.
  • Page 43: Cooling System

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.3 Cooling System The cooling system is deployed by customers by default. Civil air conditioners can be configured to cool equipment based on the equipment room temperature.  If the battery is installed in another equipment room, temperature of the smart module equipment room should be in the range of 0°...
  • Page 44 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-14 Appearance (1) Power input (2) Infrared receiver (IR) (3) SW button socket (4) Micro SD port (5) USB (USB1–USB4) port (6) Default button (7) FE port (WAN (8) RS485 port (COM1, (9) AI/DI_1–5 sensor input...
  • Page 45 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specification (RJ45) of 20 W, maximum withstand voltage of 60 V DC, and rated current of 0.5 A.  Supports one active DO port with the output voltage of 12 V DC and output current of 450 mA.
  • Page 46: Optional) Independent Deployment Ai/Di Unit

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-20 Wireless network pairing and IP address reset buttons Name Function Function Status Description 1. When the system WiFi pairing button Reserve enters the pairing mode, the RUN indicator is steady on.
  • Page 47 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-21 Indicators on the front panel of the independent deployment AI/DI unit Silk Screen Color Meaning Status Description Green Power indicator Steady on The power supply is normal.
  • Page 48: Smoke Detector

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Silk Screen Port Description  6: D–  7: D+  8: GND The AI/DI module is configured with a 4-bit DIP switch. Set toggle switches 1 to 3 to configure the address of the AI/DI module, and set toggle switch 4 to enable or disable the build-out resistor for the RS485 port.
  • Page 49 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-16 Smoke detector Table 3-24 Smoke detector technical specifications Item Specifications Operating voltage 9–27 V Alarm current < 20 mA Indication Monitoring: The red indicator blinks once every 3 to 8 seconds.
  • Page 50: T/H Sensor

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.4.5 T/H Sensor Figure 3-17 T/H sensor Table 3-25 T/H sensor technical specifications Item Specifications –20° C to +70° C Temperature measurement range Temperature measurement precision ± 1° C (at 25° C) –10°...
  • Page 51: Door Status Switch

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.4.6 Door Status Switch Figure 3-18 Door status switch Table 3-27 Door status switch technical specifications Item Specifications Connection method Using wiring terminals Rated current 500 mA 25 mm ≤ Opening distance ≤ 45 mm...
  • Page 52: Cim

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture The battery interface module (BIM) is a battery monitoring module that monitors the voltages, internal resistances, and pole temperatures of batteries.  One CIM can support a maximum of 300 BIMs, and manage BIMs of a maximum of four battery strings.
  • Page 53 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Appearance Figure 3-20 Figure 3-21 show the appearance of a CIM. Figure 3-20 CIM front view (1) –48 V 0.5 A port (power (2) PoE port (3) COM_IN port (RS485...
  • Page 54 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-21 CIM bottom view (1) Fastener (2) Micro SD card slot (3) Default button (IP (4) ADDR dual in-line package (DIP) switch (RS485 reset) communications address) (5) 12V 2A port (power...
  • Page 55 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-29 –48 V, 0.5 A port pin definitions Definition Description The system provides 48 V DC operating voltage in this – scenario. PoE Port Figure 3-23 PoE port pins...
  • Page 56 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture COM Port Figure 3-24 COM port pins Table 3-31 COM port pin definitions Signal Description RS485+ Two cascaded RS485 communication ports RS485– RS485+ RS485– DI and DO Ports Table 3-32 DI and DO port pin definitions...
  • Page 57 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Definition Signal Status Initial Remarks Descriptio Description Status input is closed. Dry contract  Open: The Open output dry contact signal output is open.  Closed: The dry contact output is closed.
  • Page 58 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture  If the positive or negative battery string cable is too thick to be routed through the Hall effect sensor, or the measurement range of the Hall effect sensor is not enough, use multiple Hall effect sensors to monitor the current of one battery string.
  • Page 59 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-35 BCB_IN and BCB_OUT cascading port pin definitions Definition BCB_IN BCB_OUT Status Initial Descrip Signal Signal Description Status tion Description Description Specifies Specifies  Grounded: Discon Receives whether the...
  • Page 60 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Indicators Table 3-37 Indicator description Indicator Color Meaning Status Description Measure RF_Z Green Wireless Steady No network Requires no communication parameters exist. handling. status (A network is to be created.)
  • Page 61 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Indicator Color Meaning Status Description Measure  If no, contact Huawei technical support. Alarm indicator Steady The actual Check the value number of of BIM number, online devices is...
  • Page 62: Bim

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Default Button Table 3-39 Default button description Name Definition Function Default button Hold down the button Reset to the default IP address (192.168.0.10) for more than 10 seconds. 3.4.7.2 BIM The BIM is a battery monitoring module that monitors the voltages, internal resistances, and pole temperatures of batteries and supports 12 V power.
  • Page 63: Water Sensor

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Indicator Color Silk Status Description Screen intervals Blinking at The networking succeeds. long intervals Alarm The BIM is not faulty.  Steady on The BIM is faulty.  Communication with the CIM times out.
  • Page 64: Optional) Pad

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-28 Water sensor Table 3-42 Water sensor technical specifications Item Specifications Operating voltage 12 V DC (9–16 V DC) Insulation resistance > 500 megohms –20° C to +70° C, 10%–80% RH...
  • Page 65: Optional) Wifi Converter

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-43 Pad technical specifications Item Specifications Dimensions (L x W x 248.5 mm x 150 mm x 8.3 mm Weight About 433 g Touchscreen 9.6-inch, 1280x800 IPS full view, IPS screen, and capacitive...
  • Page 66: Optional) Vcn500

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-44 WiFi converter technical specifications Item Specifications Wireless standard IEEE 802.11n, IEEE 802.11g, and IEEE 802.11b Network bandwidth  11n: up to 150 Mbit/s  11g: up to 54 Mbit/s ...
  • Page 67 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Storage performance A single VCN500 supports the storage access from a maximum of 32 cameras and the maximum storage access bandwidth of 160 Mbit/s. Video playback and...
  • Page 68: Optional) Ip Camera

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications monitoring-level hard disks) Maximum power 215 W consumption (including monitoring-level hard disks) Typical power 200 W consumption (including enterprise-level hard disks) Maximum power 250 W consumption (including...
  • Page 69: Optional) Gsm Modem

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications 0lux (infrared enabled) Wide dynamic 120 dB Focal length 2.8–12 mm manual zoom, 4.3x optical zoom Video coding format H.265/H.264/MJPEG Maximum resolution 1920x1080 Intelligent video analysis Supports tripwire detection, loitering detection, intrusion...
  • Page 70: Optional) Infrared Remote Control Module

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.4.14 (Optional) Infrared Remote Control Module The infrared remote control module allows for the automatic startup of civil air conditioners. The air conditioners with a carrier frequency of 38 kHz± 2%, an infrared transmitter wavelength of 940±...
  • Page 71: Cable Management

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.5 Cable Management Cables inside cabinets are sorted by cable managers, cable rings, and cable trays. Cable managers route cables horizontally, cable rings on the cabinet side route cables vertically, and cable trays route cables from the cabinet front to cabinet rear.
  • Page 72 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-35 Cable ring Table 3-51 Cable ring specifications Name Dimensions (H x W x D) Weight Standard cable ring 55 mm x 48 mm x 188.6 0.163 kg...
  • Page 73 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-52 Cable tray specifications Dimensions (H x W x D) Weight Space Occupied 43.6 mm x 482.6 mm x 250 1.89 kg Issue 01 (2017-04-20) Huawei Proprietary and Confidential...
  • Page 74: A Technical Specifications (Single-Phase 240 V Power System)

    FusionModule500 Smart Mini Data Center A Technical Specifications (Single-Phase 240 V Power Product Description (ECC800e) System) Technical Specifications (Single-Phase 240 V Power System) Table A-1 Key technical specifications Item Specifications ≤ 2 (including the Converged Cabinet and Number of IT cabinets network cabinet) ≤...
  • Page 75: B Technical Specifications (Dual-Live Wire 208 V Power System)

    FusionModule500 Smart Mini Data Center B Technical Specifications (Dual–Live Wire 208 V Product Description (ECC800e) Power System) Technical Specifications (Dual–Live Wire 208 V Power System) Table B-1 Key technical specifications Item Specifications ≤ 2 (including the Converged Cabinet and Number of IT cabinets network cabinet) ≤...
  • Page 76: C Derating Coefficients

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) C Derating Coefficients Derating Coefficients Table C-1 UPS2000-G derating coefficients Altitude (Unit: m) Derating Coefficient 1000 1500 0.95 2000 0.91 2500 0.86 3000 0.82 3500 0.78 4000 0.74 Coefficients in the previous table are based on the dry air density (sea level temperature + 15° C) of 1.225 kg/m...
  • Page 77: D Acronyms And Abbreviations

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) D Acronyms and Abbreviations Acronyms and Abbreviations application Battery control I/O board Battery Interface Module Communication Interface Module energy control center power distribution unit uninterruptible power system virtual customer network Issue 01 (2017-04-20) Huawei Proprietary and Confidential Copyright ©...

Table of Contents