Huawei FusionModule500 V100R021C10 User Manual
Huawei FusionModule500 V100R021C10 User Manual

Huawei FusionModule500 V100R021C10 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500 V100R021C10:
Table of Contents
FusionModule500 Smart Mini Data Center
V100R021C10
User Manual
Issue
01
Date
2020-11-30
HUAWEI TECHNOLOGIES CO., LTD.
Table of Contents
loading

Summary of Contents for Huawei FusionModule500 V100R021C10

  • Page 1 FusionModule500 Smart Mini Data Center V100R021C10 User Manual Issue Date 2020-11-30 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Change History Changes between document issues are cumulative. The latest document issue contains all updates made in previous issues. Issue 01 (2020-11-30) This issue is the first official release. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    3.2.5 rPDU....................................... 25 3.3 Cooling System..................................25 3.3.1 Application Conditions..............................26 3.3.2 Technical Specifications..............................26 3.4 Management System................................27 3.4.1 Overview....................................27 3.4.2 System Functions................................28 3.4.2.1 Monitoring..................................28 3.4.2.2 App View................................... 28 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 6 4.2.4 Installing a Drainage Pipe for the Smart Cooling Product..................70 4.2.5 Installing Power Supply and Distribution Devices....................72 4.2.5.1 Installing Lithium Batteries............................72 4.2.5.2 (Optional) Installing Busbars............................. 73 4.2.5.3 Installing rPDUs................................74 4.2.6 Installing Monitoring Devices............................75 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 7 5.3.8 Commissioning Event Notification..........................134 5.3.9 Linkage Control................................139 5.3.9.1 Unlocking the Cabinet Electronic Clasp Lock When a Smoke Alarm Is Generated......140 5.3.9.2 Unlocking the Cabinet Electronic Clasp Lock When a Fire Alarm Is Generated........141 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 8 6.4.1.1 Replacing a Cabinet Electronic Clasp Lock......................209 6.4.1.2 Replacing a Gas Spring.............................. 210 6.4.1.3 Replacing a PDU2000..............................211 6.4.2 Replacing Power Supply and Distribution System Components..............212 6.4.2.1 Replacing a Surge Protection Module........................212 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 9 6.4.3.8 Replacing a T/H Sensor (33010516)........................226 6.4.3.9 Replacing a Smoke Detector........................... 226 6.4.3.10 Replacing an Electrode Water Sensor........................ 228 7 Technical Specifications..................... 229 A Equipment Derating Coefficients..................230 B Acronyms and Abbreviations................... 231 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. viii...
  • Page 10: Safety Information

    The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
  • Page 11 ● Keep irrelevant people away from the equipment. Only operators are allowed to access the equipment. ● Use insulated tools or tools with insulated handles, as shown in the following figure. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 12 Do not change the structure or installation sequence of equipment without permission. ● Do not touch a running fan with your fingers, components, screws, tools, or boards before the fan is powered off or stops running. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 13: Personnel Requirements

    Do not power on the equipment before it is installed or confirmed by professionals. 1.2 Personnel Requirements ● Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ●...
  • Page 14 0°C. Handle cables with caution, especially at a low temperature. – Cables stored at subzero temperatures must be stored at room temperature for at least 24 hours before they are laid out. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 15: Installation Environment Requirements

    Install the equipment in an area far away from liquids. Do not install it under areas prone to condensation, such as under water pipes and air exhaust vents, or areas prone to water leakage, such as air conditioner vents, ventilation Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 16 Any violations must be promptly pointed out by the site manager or safety supervisor and the involved personnel should be prompted for correction. Personnel who fail to stop violations will be forbidden from working. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 17: Mechanical Safety

    Ensure that the wider end of the ladder is at the bottom, or protective measures have been taken at the bottom to prevent the ladder from sliding. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 18 D ANGER When removing a heavy or unstable component from a cabinet, be aware of unstable or heavy objects on the cabinet. ● Be cautious to avoid injury when moving heavy objects. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 19: Cooling System Safety

    ● When maintaining or replacing components, pay attention to high-pressure components (such as the compressor and refrigerant pipe) to prevent the refrigerant system from being cracked or exploded due to misoperations. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Battery Safety

    Use dedicated insulated tools. ● Move batteries in the required direction. Do not place a battery upside down or tilt it. ● Keep the battery loop disconnected during installation and maintenance. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 21 NO TICE To ensure battery safety and battery management accuracy, use batteries provided with the UPS by Huawei. Huawei is not responsible for any battery faults caused by batteries not provided by Huawei. Battery Installation Before installing batteries, observe the following safety precautions: ●...
  • Page 22 ● Use batteries within the allowed temperature range; otherwise, the battery performance and safety will be compromised. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Others

    UPS output voltage level or frequency. Doing so may affect the power supply to equipment. ● Exercise caution when setting battery parameters. Incorrect settings will affect the power supply and battery lifespan. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 24: Overview

    2 Overview Overview 2.1 Positioning To meet the requirements for customers' growing services, Huawei launches the FusionModule500 that can be rapidly deployed and flexibly expanded. The FusionModule500 is positioned as a small edge data center solution and occupies about 10 m .
  • Page 25 FusionModule500 Smart Mini Data Center User Manual 2 Overview Figure 2-1 Position of the FusionModule500 in the financial industry (1) FusionModule5000 (2) FusionModule2000 (3) FusionModule800 (4) FusionModule500 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Features

    The powerful monitoring system allows you to master the infrastructure status anytime and improves the cabinet protection capability. High Scalability ● The modular design allows the smart module to be flexibly configured so that fast capacity expansion can be achieved. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Typical Application Scenarios And Configurations

    It is mainly sold in China, Asia Pacific, Africa, Europe, and Middle East. The solution supports the 220– 240 V, 1 Ph, and 50/60 Hz power system. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 28: Typical Configurations

    Power backup time 60–240 minutes Power distribution UPS2000-G, lithium battery, and rPDU Monitoring ECC800-Pro, temperature and humidity (T/H) sensor, smoke detector, water sensor, PAD, intelligent lock, WiFi converter, and NetEco (optional) Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 29: System Architecture

    Air channel Cold and hot aisle containment Installation mode Installed on a concrete floor or electrostatic discharge (ESD) floor Static load 1500 kg Dynamic load 1000 kg IP rating IP20 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 30: Power Supply And Distribution System

    3.2 Power Supply and Distribution System 3.2.1 Overview The UPS supplies uninterruptible power to IT loads by means of lithium batteries when the external power supply fails. Figure 3-1 Power distribution principles in the UPS scenario Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 31: Kva Ups

    (9) Battery input (7) USB port terminals (behind the cover) terminal (behind the cover) (10) Parallel current (11) Emergency power-off (12) Parallel equalization port (EPO) port communication port (13) Battery PE terminal Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 32: Power Distribution Subrack

    Weight 15 kg 3.2.3 Power Distribution Subrack Table 3-3 Technical specifications Item Specifications Maximum input current 63 A Number of phases Single phase Input frequency 50/60 Hz Input voltage 220 V Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 33: Lithium Battery Esm-48100B1

    130 mm x 442 mm x 396 mm (excluding mounting ears) Weight (one lithium battery) 43 kg Maximum charge/discharge 100 A/100 A@35°C (The actual charge current current depends on the UPS charge capability.) Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 34: Rpdu

    The figures are for reference only. The actual product prevails. Table 3-5 rPDU specifications Item Model Output Port PDU2000-16-1PH-8/0-B1 10 A: 8 PDU2000-16-1PH-7/0-B1 10 A: 7 3.3 Cooling System Figure 3-5 Appearance of the integrated air conditioner Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 35: Application Conditions

    220–240 V AC 50/60 Hz, 1 Ph Refrigerant R410A Cooling capacity 3.5 kW Air supply mode Upward air supply and return at the indoor side, and rear air return at the outdoor side Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 36: Management System

    It also provides a graphical user interface (GUI) for ease of operating and maintaining devices inside the smart module. Figure 3-6 System network diagram Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 37: System Functions

    You can view the alarm cause and solution in the alarm details. ● Alarms can be classified into four severities: critical, major, minor, and warning. The alarm severities can be user-defined. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 38: Historical Data Query

    The ECC800-Pro data center controller is used to monitor the devices and environment in the smart module. It consists of the power module and main control module. You can insert and remove the power module. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 39 6.3 kg (with a single power module and a main control module) Color Black Installation Can be installed in a 1 U space in a standard 19-inch cabinet Environmental protection RoHS, REACH, and WEEE Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 40: Main Control Module

    Pin 1 Pin 2 Pin 3 Pin 1 48V+ Pin 2 48VGND 3.4.3.2 Main Control Module Figure 3-9 ECC800-Pro main control module (1) USB (2) Status indicator (3) AIDI_1 (4) AIDI_2 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 41 LAN port ● Supports two LAN ports, which can be connected southbound devices. The ports support autonegotiation of 10/100/1000 Mbit/s communication rates. ● Connect shielded network cables to the LAN ports. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 42 Group 1: 12 V of the AIDI_1 and DO/12V ports Group 2: 12 V of the AIDI_2, COM1/AIDI_4, and COM3/12V ports Group 3: 12 V of the AIDI_3 and COM2/AIDI_5 ports Wireless Supports wireless communication that complies with communication IEEE802.15.4. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 43 ● Restores the default IP address, factory settings, and user information. ● Supports RF_Z networking. Table 3-13 ECC800-Pro RF_Z parameters Item Specifications RF_Z Operation 2405–2480 MHz Frequency RF_Z EIRP (max.) 8 dBm Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 44 There are four GE ports, that is, two WAN ports (WAN1 and WAN2) and two LAN ports (LAN1/POE and LAN2/POE). Table 3-15 GE port pin definitions Item Description Pin 1 GE1+ Pin 2 GE1- Pin 3 GE2+ Pin 4 GE3+ Pin 5 GE3- Pin 6 GE2- Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 45 ● Off: No 12 V DC output is provided. Table 3-17 COM3/12V port pin definitions Item Description Pin 1 RS485+ Pin 2 RS485- Pin 3 12V DC_OUT Pin 4 RS485+ Pin 5 RS485- Pin 6 Pin 7 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 46 Pin 7 can detect temperature sensors. Table 3-19 AIDI_1, AIDI_2 and AIDI_3 ports pin definitions Item Description Pin 1 Type_1 Pin 2 Type_2 Pin 3 12V DC Pin 4 Type_3 Pin 5 Type_4 Pin 6 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 47 ● Steady on: The 12 V DC output is normal. ● Off: No 12 V DC output is provided. Table 3-21 USB port pin definitions Item Description Pin 1 Pin 2 Pin 3 Pin 4 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 48 The RF_Z indicator is network RF_Z pairing mode, press and hold down blinking at super (802.15.4) the button for 3s to 5s to enter the short intervals. pairing wireless network pairing mode. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 49: Power Module

    1s and then off for 1s). Blinking at The module application short program is being loaded (the intervals indicator blinks at 4 Hz, on for 0.125s and then off for 0.125s). Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Environment Monitoring System

    The module is working properly. 3.4.4 Environment Monitoring System 3.4.4.1 Electrode Water Sensor The electrode water sensor with the BOM number of 33010444 contains electrode probes and cables. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 51: T/H Sensor (Bom Number: 33010516)

    3.4.4.2 T/H Sensor (BOM Number: 33010516) Figure 3-13 Appearance The T/H sensor uses an RJ45 connector. NO TE The appearance of the temperature and humidity sensor depends on the actual delivery. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Smoke Detector

    Operating temperature –20°C to +80°C Operating voltage 9–16 V DC Storage temperature –40°C to +80°C Output Two RJ45 ports, bidirectional cascading 3.4.4.3 Smoke Detector A smoke detector detects smoke around cabinets. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 53: Cabinet Electronic Clasp Lock

    31 mm x 75 mm x 51 mm (with the base) Weight 50 g 3.4.5 Cabinet Electronic Clasp Lock The cabinet electronic clasp lock is used to manage access control. It can be automatically unlocked, or manually locked and unlocked. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 54 (2) DIP switch (3) RJ45 power ports Table 3-29 RJ45 port definitions Pin Description Description RS485+ RS485+ RS485- RS485- +12 V power supply +12 V DC RS485+ RS485+ RS485- RS485- Ground Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 55 (blinking at 10 Hz, on for 0.05s and then off for 0.05s). The cycle lasts for 5s. Alarm Steady on A system failure indicato alarm is generated. The system is normal. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Pad

    ● Material: Li-polymer ● Capacity: 4800 mAh ● WiFi connection/Web page browse time: about 6.5 hours ● Power adapter charge time: about 6 hours Operating system Android 4.4 (KitKat) + EMUI 3.0 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 57: Wifi Converter

    USB 2.0 Hi-Speed connector Voltage range 5.0 V DC ±5% Operating temperature –20°C to +70°C Storage temperature –40°C to +90°C Humidity 10%–90% RH (non-condensing) Storage humidity 5%–90% RH (non-condensing) Power < 0.8 W Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 58: Optional) Camera

    0 lux (infrared illuminator enabled) Wide dynamic range 120 dB Focal length 2.8–12 mm Video compression H.265/H.264/MJPEG standard Maximum resolution 1920x1080 Power supply 12 V DC, PoE IP rating IP67 Vandal resistant rating IK10 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 59: Optional) Ivs1800

    Platform 16 cameras to one 64 cameras to one IVS1800 performa cameras IVS1800 connect Table 3-35 Hardware specifications Category Item Specifications Storage Hard disk capacity quantity Hard disk SATA3.0 port Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 60: Optional) Neteco Intelligent Data Center Management System

    The management system provides a GUI to implement comprehensive management functions based on requirements. The system mainly monitors following devices: Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 61: Server

    2 x 1.2 TB + 8 x 1.8 TB SAS drives 2288X V5-H22X-basic 2 x 4208 [email protected] GHz CPU, 2 x 32 GB configuration memory, 2 x 1.2 TB SAS drives Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 62: Lan Switch

    6 mm ● A ground bar or general ground point is provided in the cabinet for equipment grounding. The ground bar does not need to be insulated. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 63: Cable Management

    Figure 3-22 Cable tray Table 3-38 Cable tray technical specifications Dimensions (H x W x Weight Space Occupied 43.6 mm x 482.6 mm x 1.89 kg 250 mm Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 64: Installation Guide

    Measuring tape (5 Level Step ladder (2 Phillips screwdriver Flat-head Torque wrench (M4, M6, and M8) screwdriver (2-5 Adjustable Socket wrench (M6, Hex key (5 mm) Laser locator wrench (6") M8, and M12) Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 65 Diagonal pliers RJ11 crimping tool Polyvinyl pliers chloride (PVC) insulation tape Wire stripper Hydraulic pliers Wire clippers Crimping tool Multimeter Electroprobe Heat shrink tubing Cable ties Hammer drill Electric screwdriver Rubber mallet Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 66 5% silver solder Oxygen Acetylene Hot melt device Clamp meter Pipe bender Insulation gloves Pressure gauge (1 Leather hose (3 PCS) PCS) Water pipe Nitrogen Reducing valve Vacuum pump thread sealant Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 67: Installation Environment Check

    Altitude 0–4000 m (The power is □ Passed □ Failed derated as described in IEC 62040-3 when the altitude exceeds 1000 m.) Levelness Allowed deviation: 3/2000 mm □ Passed □ Failed Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 68: Site Equipment Preparation

    □ Passed □ Failed condensate water from the smart cooling product. NO TE If any of the requirements is not met, contact Huawei technical support. 4.1.3 Site Equipment Preparation ● All cabinets and devices have been delivered to the site and checked against the delivery list.
  • Page 69: Installation Scenarios

    User Manual 4 Installation Guide 4.1.4 Installation Scenarios Cabinet Internal Layout Figure 4-1 Component layout in the cabinet scenario Table 4-4 Components in the cabinet scenario Component ECC800-Pro PDU5000 Electronic clasp lock Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 70: Personnel Requirements

    Only trained and qualified personnel who fully understand basic safety precautions are allowed to install and operate a modular data center. CA UTION Huawei will not be liable for any consequence caused by the violation of this document. The requirements are as follows: ●...
  • Page 71: Cabinet Transportation And Unpacking

    Check against the packing list that the equipment and fittings are correct and complete. If some fittings are missing or do not comply with the packing list, record the information and contact your local Huawei office immediately. After checking that the cabinet is intact, remove the screw assemblies that...
  • Page 72: Optional) Removing The Aisle Containment

    If the site elevator is too small to transport a cabinet, remove the aisle containment from the cabinet. Reassemble them after transporting them to the installation position. Then perform subsequent operations. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 73 Record the PAD cable route because you need to bind the PAD cable along the original route in subsequent installation. Figure 4-3 Removing the PAD cable Step 3 Loosen the gas spring nuts using an adjustable wrench and remove the gas springs. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 74 Remove the gas springs only when the door is open. Step 4 Disconnect the cabinet ground cable. Step 5 Lift the cabinet doors off the hinges. Remove the front and rear doors. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 75 ● Before removing a cabinet door, disconnect the ground cable between the cabinet door and the cabinet. Figure 4-5 Removing the cabinet doors Step 6 Remove the top plate from the cabinet using a Phillips screwdriver. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 76 4 Installation Guide Figure 4-6 Removing the top plate Step 7 Remove the screws securing the aisle containment to the cabinet using a Phillips screwdriver, and remove the aisle containment from the cabinet. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 77: Installing A Cabinet

    The floor levelness meets engineering requirements. Context To position a cabinet, perform the following steps: Determine the position of the cabinet based on the engineering layout diagram. Place the cabinet at the correct installation position. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 78 Put a level at the bottom of the cabinet in width and depth directions and check that the air bubble is in the middle between the two lines marked on the glass tube. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 79: Installing A Drainage Pipe For The Smart Cooling Product

    The condensate drainpipe has been installed on the smart cooling product before delivery. You need to route the drainpipe from the bottom onsite. Procedure Step 1 Remove the baffle plate from the smart cooling product. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 80 Step 2 Use an electrician's knife to cut a cross in the middle of the rubber plug for the water pipe hole at the bottom of the cabinet. Figure 4-10 Cutting the rubber plug Step 3 Route the drainpipe. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 81: Installing Power Supply And Distribution Devices

    4.2.5.1 Installing Lithium Batteries Context Install lithium batteries in the 11th U and higher positions of the cabinet. Procedure Step 1 Push a lithium battery into the cabinet and secure it. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 82: Optional) Installing Busbars

    Step 3 Install other lithium batteries in the same way. ----End 4.2.5.2 (Optional) Installing Busbars Prerequisites If there is more than one lithium battery, install busbars. Procedure Step 1 Install busbars. Open the cabinet rear door. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 83: Installing Rpdus

    U positions at the rear door of the cabinet. Procedure Step 1 Open the rear door of the cabinet, and install floating nuts in the rPDU installation position. Step 2 Secure the horizontal rPDUs using screws. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 84: Installing Monitoring Devices

    Step 2 Remove the ECC800-Pro main control module, and then insert the SIM card into the left slot of the ECC800-Pro main control module. NO TE The SIM card needs to support LTE, WCDMA, or GSM. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 85 Route the antenna cable into the cabinet through the signal cable hole at the top of the cabinet and then to the appropriate port on the ECC800-Pro. Connect the antenna cable to the antenna port on the ECC800-Pro. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 86: Installing A Pad

    FusionModule500 Smart Mini Data Center User Manual 4 Installation Guide Figure 4-17 Installing an antenna cable ----End 4.2.6.2 Installing a PAD Context The PAD is to be installed on the front door of the cabinet. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 87 Figure 4-18 PAD installation position (1) PAD installation position Procedure Step 1 Adjust the width and height of the PAD support to match the dimensions of the PAD to be installed. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 88 Step 3 Route the PAD power cable to the cable hole in the PAD support and connect the cable to the PAD. Step 4 Adjust the feet above the PAD support and clamp the PAD to the PAD support. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 89: Installing Remote T/H Sensors For Smart Cooling Products

    The installation positions of the T/H sensors can be adjusted as required. Step 2 Set the DIP switch address of the T/H sensor on the front door to 2 and that of the T/H sensor on the rear door to 1. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 90: Installing T/H Sensors

    Table 4-5 DIP switch setting on a T/H sensor Address DIP Switch Sequence No. NO TICE The default address of T/H sensors purchased from Huawei is 1. Step 3 Insert the pre-routed cable into the port on the T/H sensor on the front and rear doors. ----End 4.2.6.4 Installing T/H Sensors...
  • Page 91: Installing An Electrode Water Sensor

    Step 4 Install the water detector. ----End 4.2.6.6 (Optional) Installing a Server Procedure Step 1 Determine the installation position of the server and check whether floating nuts are installed. If not, install them first. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 92 Step 4 When the two mounting ears on the server contact the mounting bars on the rack, tighten the captive screws on the mounting ears to secure the server. Figure 4-25 Installing a server Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 93: Optional) Installing A Camera

    ----End 4.2.6.7 (Optional) Installing a Camera Prerequisites ● A camera and tools for installing it have been prepared. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 94 Step 1 (Optional) Install an SD card. Remove the transparent cover using a Phillips screwdriver. Figure 4-28 Removing the transparent cover Gently insert the SD card into the SD card slot. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 95 Figure 4-30 Installing a camera base (1) Cable outlet Step 4 Install the mounting plate with the camera at the top of the front door of the end cabinet, as shown in Figure 4-31. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 96 During the installation, adjust the surveillance angle to avoid video image rotation after the installation. ● When adjusting the surveillance angle, pay attention to the position of the illuminator to prevent the illuminator from being blocked. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 97: Optional) Installing A Lan Switch

    Step 2 Install the mounting ears delivered with the LAN switch, and secure the LAN switch to the rack rails in the front of the cabinet. NO TE This section describes only the installation method. The actual product appearance prevails. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 98: Installing An Ivs1800

    4.2.6.9 Installing an IVS1800 Context By default, the IVS1800 is delivered without disks. After the IVS1800 is delivered to the site, install hard disks as required and then install the IVS1800 in the cabinet. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 99 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 100 Figure 4-40 Connecting data and power cables to hard disks Close the chassis cover, and use a PH2 screwdriver to fasten the rear screws. Figure 4-41 Closing the chassis cover Step 2 Install the device. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 101 If the vents are blocked, change the guide rails. ● Huawei provides guide rails that can be adjusted from 500 mm to 800 mm for additional purchase if required for IVS1800 installation.
  • Page 102 Figure 4-44 Installing a filler panel for guide rails Install the cage nuts that secure the IVS1800. The cage nut installation locations are the first and sixth holes along the guide rails, as shown in the following figure. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 103 Thread M6 screws (prepared by the customer) through two slotted holes on each mounting ear. Fasten the M6 screws using a Phillips screwdriver to fix Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 104: Cable Routing

    Attach labels to both ends of a cable. Requirements for Neatly Routing and Binding Cables To route and bind cables in an appealing way, follow these rules: Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 105 Also comply with these rules when cables of different thickness are bound together. Arrange cables by thickness when arrangement by thickness conflicts with arrangement by color. Figure 4-50 Binding cables in different colors Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 106 Figure 4-52. Figure 4-52 Cable connections Protect cable holes in a metal kit with grommet strips. Alternatively, ensure that the holes are rounded, free from burrs or sharp edges. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 107 Figure 4-53 Cutting off the excess part of a cable tie Do not use cable ties at a place where the cables are bent. Otherwise, the cable cores may break due to strong stress, as shown in Figure 4-54. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 108: Cable Connections To The Power Supply And Distribution System

    4.3.2.1 Grounding the Smart Module Connect the ground point in the cabinet to the general ground bar. Connect the general ground bar in the cabinet to the floor ground bar or collective ground bar. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 109: Connecting Cabinet Input Power Cables

    The actual position prevails. Procedure Step 1 (Optional) Connect input power cables to the PDU. (Optional) Remove the transparent protective panel at the rear of the PDU. Connect input power cables to the PDU. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 110: Connecting Rpdu Power Cables

    Step 1 Connect cabinet rPDU power cables. Remove the front panel from the rPDU. Connect one end of the reserved rPDU power cable to the rPDU terminal block and the other end to the power distribution subrack. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 111: Connecting Cables Between The Lithium Battery And The Ups

    The busbars, batteries, power distribution unit (PDU), and UPS have been installed. ● If only one battery is configured onsite, battery cables have been preinstalled in the battery position. If more than one battery is configured onsite, connect battery cables. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 112 –48 V port on the busbar. Figure 4-59 Connecting cables between lithium batteries and busbars Connect cables between the busbars and the PDU. Connect cables between the PDU and the UPS. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 113 After lithium batteries are connected in parallel, connect a signal cable to the BMS port of the UPS. A build-out resistor needs to be installed at the COM-OUT port of the lithium battery at the end. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 114: Management System Cable Connection

    A Phillips screwdriver and M4 screws are required. NO TE The customer needs to prepare the ground cable. Step 2 Connect one end of the network cable to any GE network port on the IVS. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 115: Verifying The Installation

    □ Passed □ Failed All labels are correct, clear, and complete. □ Passed □ Failed The cabinet has no waste tape, cable ties, paper, □ Passed □ Failed or packing materials around it. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 116 The ground cable, AC power cables, and internal □ Passed □ Failed cables are correctly connected and screws are secured. No short circuit occurs during power input or output. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 117 Lithium battery cables are connected correctly. □ Passed □ Failed DIP switches on devices are correctly set. □ Passed □ Failed Customer Sign: Check Data: Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 118: Power-On Commissioning

    Step 4 After the UPS starts, set parameters such as the battery capacity based on the site requirements, start the inverter, and switch on the UPS output circuit breaker. Step 5 Switch on the rPDU circuit breakers. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 119: Ups Power-On Commissioning

    220 V AC. 230: indicates that the output voltage is 230 V AC (default value). 240: indicates that the output voltage is 240 V AC. Step 4 Set the battery capacity. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 120: Connecting The Lithium Battery Supply

    Step 4 Hold down the MANUAL ON/OFF button on the ESM panel for at least 5s and less than 15s to activate the ESM. ----End 5.2 Power-On Commissioning for the Cooling System Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 121: Powering On Devices

    Log in to the ECC800 WebUI as an administrator. Add the NetCol8000-A0131. Table 5-1 Adding a smart cooling product Path Parameter Setting Choose Device Select Air Conditioner from the drop- System Attribute down list box. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 122 (such as on/off control parameters). CA UTION After the smart cooling product is shut down, the temperature of the smart module increases and data running is affected. Exercise caution when performing this operation. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 123: Commissioning The Cooling System

    Pressure Temperatu Pressure re (°C) (MPa) re (°C) (MPa) re (°C) (MPa) 1.31 2.21 0.73 1.35 2.27 0.75 1.39 2.33 0.78 2.39 0.81 1.47 2.45 0.84 1.51 2.51 0.87 1.56 2.57 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 124 Step 2 Choose Controls > Control Information, set Power on/off to ON, and click Submit. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 125 Tighten the needle valve nut when the charge is complete. Check whether a needle valve leaks by applying soapy water to the valve vent or using a halogen leak detector. If it leaks, contact Huawei technical support. Figure 5-3 Charging refrigerant...
  • Page 126: Management System Power-On Commissioning

    (protected by a security mechanism) on the ECC800-Pro. Table 5-3 Default IP addresses for the WAN and LAN ports on the ECC800-Pro Port Default IP Address WAN_1 192.168.8.10 WAN_2 192.168.0.10 192.168.248.10 LAN_1 and LAN_2 192.168.248.10 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 127 Click the Advanced tab and select Use TLS1.1 and Use TLS1.2. (Optional) Click the Connections tab and select LAN settings. (Optional) On Proxy server, clear Use a proxy server for your LAN. Click OK. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 128 Compatibility View, and add the web access address to the compatibility view. Choose Tools > Internet Options > Security, and add the ECC800-Pro access address to the list of trusted sites. Figure 5-5 Adding an address Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 129 Step 5 Log in to the ECC800-Pro WebUI. Enter https://monitoring IP address (such as monitoring IP address https:// 192.168.8.10) in the address box of the browser, and then press Enter to enter the WebUI login page. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 130: Preparations And App Login

    – After the first login, change the password in time to ensure account security and prevent unauthorized network attacks, such as data tampering. Huawei will not be liable for any security issues caused by your failure to change the preset password in time or password loss after changing.
  • Page 131 NO TICE Do not use the Google Play to download the Huawei AppGallery. iii. Install the Huawei AppGallery. If the downloaded file exists in the drop-down list box, tap the file to install the Huawei AppGallery. If the downloaded file does not exist in the drop-down list box, choose File >...
  • Page 132 – If an exception in network or an unexpected exit from the app occurs, the original user can log in immediately and the newly-added user need to wait 5 more minutes to log ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 133: Date And Time

    Add Device. Device Type Select UPS2000G-L from The parameters for the drop-down list box. adding devices are displayed. Connect To Select ECC800 from the drop-down list box. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 134: Commissioning Sensors

    If a smoke detector is installed, perform the following steps to configure it. Context If the detector is prefabricated, only check its settings. Procedure Step 1 Set smoke detector parameters. Log in to the ECC800-Pro WebUI as an administrator. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 135: Commissioning A T/H Sensor

    Operate the DIP switch on the T/H sensor to set the device address for the sensor. Toggle switches 1 to 6 specify the device address in binary mode. ON indicates 1, and OFF indicates 0. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 136 Select T/H sensor from the drop-down list Device box. Management and click Add Connect To Select ECC800 from the drop-down list box. Device. Communica Select COM1 from the drop-down list box. tions Port Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 137: Commissioning The Electrode Water Sensor

    5.3.6.3 Commissioning the Electrode Water Sensor Prerequisites One end of the network cable has been stripped, core wires 7 and 8 have been connected to the cable delivered with the electrode water sensor, and the other Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 138 Wipe dry the two contacts of contacts of the on the active alarm screen of the water sensor. The alarm electrode water the app or on the WebUI. disappears automatically. sensor in water. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 139: Commissioning Cabinet Electronic Clasp Locks

    ON indicates 1, and OFF indicates 0. Figure 5-9 Toggle switch addresses of the cabinet electronic locks NO TICE The number indicates the DIP switch setting of the electronic clasp lock. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 140 ECC800-Pro, whether both are running properly, and whether the parameter settings are consistent with the device parameters. Repeat Step 4.3 Step 4.4 to connect other cabinet electronic clasp locks. Step 5 Commission the cabinet electronic clasp locks. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 141 Check whether there is friction between the lock tongue and the electronic clasp lock. If there is friction, adjust the installation position of the electronic clasp lock. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 142 Check whether there is interference between the castors and the door sill at the bottom of the cabinet. If they interfere with each other, remove the fastener that secures the castors. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 143: Commissioning Event Notification

    WAN port. Both the Internet and local area network (LAN) are supported. NO TE The ECC800-Pro supports only SMS notification service but not data service by using the 4G module. Procedure Step 1 Choose System Settings > Event Notification. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 144 Table 5-13 Main parameters on the sender's email configuration page Email Email Mailbox Server Encryption Remarks Type Server IP Address Mode and Domain SMTP port Name Sina Mail smtp.sina.co How to obtain: Non- ● The email encryption: 25 server must Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 145 The email address is used only for configuring the email function and is not used for other purposes. The address is encrypted during transmission in the ECC800-Pro to ensure that the personal data of users is fully protected. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 146 The mobile number is used only for configuring the SMS function and is not used for other purposes. The mobile number is encrypted during transmission in the ECC800-Pro to ensure that the personal data of users is fully protected. Figure 5-15 Adding a mobile number Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 147 Mailbox Settings. Mobile Phone Number can be selected after it is added in SMS Settings. Step 6 Click Confirm to access the re-authentication page. Enter Login password and click Submit. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 148: Linkage Control

    ● If the rear door of the cabinet is open and the temperature in the cold aisle is higher than the preset value (35°C by default), the front door of the cabinet automatically opens. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 149: Unlocking The Cabinet Electronic Clasp Lock When A Smoke Alarm Is Generated

    Step 2 Choose System Settings > Linkage Control. Step 3 Ensure that Enable linkage control function is Yes. Step 4 On the Linkage Group tab page, set Link smoke alarm with clasp lock open to Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 150: Unlocking The Cabinet Electronic Clasp Lock When A Fire Alarm Is Generated

    Select Link fire control with clasp lock open under Linkage Group. If its value is on, the corresponding logic configurations under Linkage Logic List are available. If its value is off, the corresponding logic configurations under Linkage Logic List are unavailable. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 151: Link Emergency Ventilation With Clasp Lock Open

    Select Link emergency ventilation with clasp lock open under Linkage Group. If its value is on, the corresponding logic configurations under Linkage Logic List are available. If its value is off, the corresponding logic configurations under Linkage Logic List are unavailable. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 152: Commissioning A C3220 Camera (Sd Card Configured)

    Set IPv4 address, IPv4 subnet mask, and IPv4 gateway address to the planned values. Figure 5-18 Setting the IP address of the camera Format the SD card. Choose Settings > System Configuration > Storage Management. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 153 Supporte Protocol Rate Interval Bit Rate d Video Required Storage Duration H.265 1080P 1 Mbit/s H.264 1080P 1 Mbit/s H.265 720P 0.8 Mbit/s H.264 720P 1 Mbit/s H.265 720P 0.6 Mbit/s Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 154: Optional) Commissioning The Ivs1800

    Save. Set the deployment policy. Figure 5-20 Setting the deployment policy Set the alarm linkage policy. Figure 5-21 Setting the alarm linkage policy ----End 5.3.11 (Optional) Commissioning the IVS1800 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 155: Commissioning A C3220 Camera (No Sd Card Is Configured)

    1. Choose Tools > Internet Options. The Internet Options dialog box is displayed. 2. Click the Connections tab. 3. Click LAN Settings. 4. Deselect Use a proxy for your LAN. 5. Click OK. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 156 2. Click the Security tab. 3. Select Internet. 4. Click Custom level. The Security Settings-Internet Zone dialog box is displayed. 5. Set Use Pop-up Blocker to Disable. 6. Click OK. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 157 Subnet mask of the network where the camera is mask located. The default value is 255.255.255.0. Primary DNS Primary DNS IP address. The default value is 0.0.0.0. Secondary DNS Secondary DNS IP address. The default value is 0.0.0.0. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 158 Select Video and set the parameters, as shown in the following figures. NO TICE Set the encoding protocol to H.265. Figure 5-23 Setting primary stream parameters Figure 5-24 Setting secondary stream 1 parameters Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 159 High profile. Among these profiles, the baseline profile has the lowest encoding compression performance and lowest requirements on hardware decoding performance, while the high profile has the highest. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 160 This parameter is available only when you set Encoding protocol to H.264 or H.265 and Bit rate type to Variable bit rate. Better image quality requires higher bandwidth. Therefore, select proper image quality based on the site requirements. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 161: Setting Parameters On The Ivs1800 Webui

    NO TE The OMU portal supports Internet Explorer 10.0 and later versions. Step 2 Log in to the OMU portal. Set the service system and operating system passwords at the first login. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 162 Step 4 Modify the IP address for the IVS1800. Choose Local Configuration > Server configuration. Set the service IP address (internal IP address of the IVS1800), time zone, and time according to the site requirements. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 163 Search. In the search result, click Edit in the row where the value of Parameter Name is MUNNatIP and set Value to the external IP address of the IVS1800. Click Save. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 164 Set Module Name to SCU and Parameter type to System property, and click Search. In the search results, click Edit in the row where Parameter Name is NTPIPC and set Value to 1. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 165: Setting Parameters On The Iclient

    The network communication between the IVS1800 and the camera is normal. Procedure Step 1 Install the iClient. Download the iClient. You can obtain the iClient in either of the following ways: Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 166 Method 2 1. Log in to the OMU portal, choose Local Configuration > Basic Configuration, and view Current version. 2. Log in to https://support.huawei.com/enterprise/, and search for and choose iClient. In the search result, click the Software Download tab, click the version and patch number corresponding to the current version, and download the software package.
  • Page 167 On the home page of the iClient, choose System Management > Device Management > Device Management > Micro Edge. Right-click an IVS1800 and choose Camera Access. Select Auto Batch Access and click Start. Set the IP address segment. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 168 NO TE If there are multiple IVS1800s for multiple smart modules, you are advised to evenly distribute the cameras to each IVS1800. Select the cameras to be added and click Next. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 169: Optional) Neteco Management

    When the smart module can be connected to the NetEco, perform the following steps to configure parameters. Procedure Step 1 Apply for a fixed IP address to the equipment room network administrator. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 170 The NetEco IP address and the ECC800- Pro IP address must be configured in the same network to ensure normal connection between the NetEco and the ECC800-Pro. Port number 31220 31220 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 171: Obtaining The Neteco Software License

    5.3.12.1.3 Obtaining the NetEco Software License The NetEco software license is not provided together with software to the customer. Therefore, obtain the NetEco software license in advance. Obtain the license from the Huawei's enterprise support website. ● For enterprise users:...
  • Page 172: Logging In To The Neteco Client

    ● You are advised to set the display resolution as 1920*1080 or higher. ● Make sure that the IP address of the NetEco server is not contained in the compatibility view website. Step 2 Enter the User Name, Password, and click Login. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 173: Loading A Neteco License

    Huawei will not be liable for any security issues caused by your failure to change the preset password in time or password loss after changing.
  • Page 174: Adding A Management Domain

    NetEco 6000. Based on the actual NE types and versions to download the mediation software installation package. ● For carriers: Log into Huawei's carrier support website https://support.huawei.com. Browse or search iManager NetEco 6000 V600R009 Version Mapping, iManager NetEco 6000 V600R009 Version Mapping from Support obtain >...
  • Page 175 You can configure Management Info, Electricity Info, and Refrigeration Info for the equipment room management domain. Click on the toolbar. Repeat steps Step 2.1 Step 2.4 until the configuration is complete. Step 3 Click on the toolbar. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 176: Adding A Module

    Step 5 Select the Modular to be added and drag the modular icon to the Room area. Figure 5-39 Adding the modular in the room area Step 6 Modify Management Info of the module or retain the default values, and then click Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 177 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning NO TICE The parameters with * are mandatory. ----End Follow-up Procedure Perform the following operations in the Data Center Planning page as required. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 178 Figure 5-40 Delete one module page 2. In the displayed Confirm dialog box, click Yes. ● Delete multiple modules in batches. 1. Click on the toolbar to display the Figure 5-41 page. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 179 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning If You Then... Need To... Figure 5-41 Delete multiple modules in batches page Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 180: Creating An Ecc800-Pro On The Neteco

    Name. 4. In the upper area of the current page, click 5.3.12.1.10 Creating an ECC800-Pro on the NetEco Prerequisites ● You have logged in to the NetEco client by web browser. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 181: Cloudopera Neteco Management

    You have created a free trial order or purchased an official business package. Procedure IP address of the NetEco server :31943, Step 1 In the browser address box, enter https:// and then press Enter. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 182: Installing The Edcm App

    Huawei will not be liable for any security issues caused by your failure to change the preset password in time or password loss after changing.
  • Page 183: Allowing A User To Log In To The Edcm On A Mobile Device

    You have obtained the IP address of the EDCM server. ● The Allow login on mobile terminals function is enabled for the user who needs to log in to the EDCM app. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 184: Setting Edcm Communication Parameters On The Ecc800-Pro

    Step 2 Open the EDCM app, and enter the Organization, Username, and Password. NO TE ● Organization and Username are the tenant name registered on HUAWEI CLOUD. ● If you fail to log in for three consecutive times, the system automatically displays Verification code.
  • Page 185: Connecting To The Network

    Connect the network to the CloudOpera NetEco through the CloudOpera NetEco app. Prerequisites ● You have logged in to the EDCM app. ● You have set EDCM communication parameters on the ECC800-Pro. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 186 Longitude of the network. You can manually enter the value or use GPS to locate. Latitude Latitude of the network. You can manually enter the value or use GPS to locate. Customer Information Customer information. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 187 FusionModule500 Smart Mini Data Center User Manual 5 Power-On Commissioning Parameter Description Address Address of the network. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 188: Routine Maintenance

    (MCB) status. the surge ● The MCB is protection switched on. module. ● If the MCB is off, switch it Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 189 Lithium battery Battery No battery Identify the management management cause of an alarm alarm is alarm based on generated. the alarm information. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 190 Frequency: 45– the power grid 55 Hz status and input cable connection. Output voltage Output voltage: If the output 53.5 V DC±5% voltage is abnormal, check the load power and cable connection. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 191 Troubleshootin to rectify the fault. Network interface The green If the indicator indicator indicator is status is steady on, and abnormal, check the yellow the network indicator is cable blinking. connection. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 192 IP address to connections or find the camera, replace the and click View to camera. For view the real- details, see time monitoring 6.4.3.5 page. Replacing a Camera. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 193 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 194: Quarterly Maintenance

    LCD, all units the fault by are operating checking the properly. No device status fault or alarm and parameters. information is found in the active and historical alarm records. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 195 ● Secure distribution free from output subrack) noticeable terminals. sparks. Lithium battery Battery No battery Identify the management management cause of an alarm alarm is alarm based on generated. the alarm information. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 196 Battery Check that the Set parameters management settings of correctly. parameter settings battery management parameters meet the requirements in the user manual. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 197 3. If the fault persists, contact Huawei technical support. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 198 Operating ● Ambient If the environment temperature: temperature or –20°C to humidity is +65°C abnormal, check the smart ● Humidity: cooling product 0%–95% RH status. (non- condensing) Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 199 Cable connection The cable Secure loose connection is cables. secure. Cables are not Replace damaged. damaged cables. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 200 Measurement of The ambient Locate the the ambient temperature of cause of an temperature of the intelligent abnormal the intelligent battery temperature. battery monitoring monitoring system system is lower than 45°C. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 201: Yearly Maintenance

    Bolts between Tighten all bolts The bolts are Tighten a bolt if power cables and regularly using an secured. it is loose. the busbar adjustable wrench after powering off the device. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 202 2 maintain the tester after megohms. signal cable and power-off. smart ETH gateway. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 203 Parameter Reset the configuration configuration of parameters. the output voltage grade, frequency, number of batteries, and battery capacity meets requirements. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 204 (charging); – operating 20°C to +45°C temperature. (discharging) 2. If the fault 2. Battery persists, charge and contact discharge Huawei conditions technical meet the support. requirements specified in the battery specifications. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 205 Huawei indicating tight technical connections does support. not change. Cables between No cable Replace the batteries deteriorates and faulty cable. the insulation layer does not crack. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 206 (recommended) discharge test an exception when the UPS is is identified. backed up to 2. If the fault verify that the persists, batteries can contact discharge Huawei properly. technical support. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 207 The torque meets requirements of the battery manufacturer. After checking that the battery screws meet requirements, mark the screws for later check. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 208 The monitoring If the indicator module indicator module indicator is off or any is steady green abnormal or blinking condition green. occurs, see 6.2.2 Management System Troubleshootin to rectify the fault. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 209 Cable connection The cable Secure loose connection is cables. secure. Cables are not Replace damaged. damaged cables. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 210 Measurement of The ambient Locate the the ambient temperature of cause of an temperature of the intelligent abnormal the intelligent battery temperature. battery monitoring monitoring system system is lower than 45°C. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 211: Troubleshooting

    UPS again. Otherwise, the fault may be extended, or the UPS may be damaged. ● If the fault is not rectified, contact Huawei technical support. Table 6-4 Power supply and distribution system troubleshooting...
  • Page 212 UPS on the ECC800-Pro WebUI. The UPS does not report The output cable is not Check the output power a fault but has no output properly connected. cable connection. voltage. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 213 AC power supply incorrectly set. immediately. ● Verify that the number of batteries and battery capacity are correctly set based on the actual configuration. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 214: Management System Troubleshooting

    PSU communication 1. Clean the connector (yellow) is blinking. failure in the rear of the faulty PSU. Monitoring module 2. If the fault persists, communication failure replace the ECC800- Pro subrack. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 215 WebUI or network - AIDI_5, COM1- management system. COM4, and DO). The corresponding Check whether the power ports are short- connected load is circuited. short-circuited. If yes, eliminate the short circuit. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 216: Alarm References

    Fan fault Critical The fan is abnormal. Clean up foreign matter around the fan. If the fault persists, contact Huawei technical support. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 217 ● The battery terminal ● Check that battery is not properly terminals are connected to the properly connected connector. to connectors. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 218: Parts Replacement

    Step 1 Open the front or rear door of the cabinet. Step 2 Remove the signal cables from the cabinet electronic clasp lock. Step 3 Remove the cabinet electronic clasp lock bolts using a Phillips screwdriver. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 219: Replacing A Gas Spring

    6.4.1.2 Replacing a Gas Spring Prerequisites ● Tools: Phillips screwdriver, step ladder ● Material: A spare gas spring is available and functional. Context Gas springs are installed on the top of a cabinet. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 220: Replacing A Pdu2000

    Material: A spare PDU2000 of the same model is available and functional. Context A PDU2000 is installed at the rear door of a cabinet. Procedure Step 1 Open the rear door of the cabinet. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 221: Replacing Power Supply And Distribution System Components

    Material: A new surge protection module of the same model is available and functional. Procedure Step 1 Switch the SPD circuit breaker to OFF. Step 2 Remove the protective panel from the SPD. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 222 Step 4 Hold the faulty surge protection module and pull it out, as shown in Figure 6-5. D ANGER During replacement, do not touch the energized components in the power distribution subrack. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 223: Replacing A Ups2000-G

    Step 3 Remove the rear cover from the UPS, and remove the input and output power cables, battery cable, and signal cable. NO TICE Wrap the exposed cable with insulation tape. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 224: Replacing A Lithium Battery

    Step 7 Connect the cables to the new battery based on the cable labels. Step 8 Switch the BAT– battery circuit breaker in the power system to ON or reinstall the battery fuse using a fuse extracting unit. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 225: Replacing Management System Components

    Step 3 Remove the cables and antenna from the ECC800-Pro main control module. Step 4 Loosen the captive screws on both sides of the ECC800-Pro main control module and pull the handles on both sides of the module to remove the module. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 226: Replacing An Ecc800-Pro Psu

    ----End 6.4.3.2 Replacing an ECC800-Pro PSU Prerequisites D ANGER Do not touch the terminals in the rear of a removed PSU to avoid electric shocks. ● Tool: insulation gloves Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 227: Replacing An Ecc800-Pro Antenna

    Materials: A spare ECC800-Pro antenna of the same model is available and functional. Procedure Step 1 Remove the 4G antenna. Step 2 Install the spare 4G antenna in the original position and connect it to the ECC800- Pro. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 228: Replacing A Sim Card

    Step 3 Pull the handles on both sides of the panel of the ECC800-Pro main control module, and remove the main control module. Figure 6-10 Removing the ECC800-Pro main control module Step 4 Remove the SIM card from the card slot. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 229: Replacing A Camera

    The operation of the video surveillance system will be interrupted. Preparations ● Tools: ESD wrist strap, ESD gloves, step ladder, label, marker, Phillips screwdriver ● Material: camera Procedure Step 1 Remove the transparent cover using a Phillips screwdriver. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 230 Figure 6-13 Removing the transparent cover Step 2 Remove the SD card. Figure 6-14 Removing an SD card Step 3 Remove the monitoring network cable from the camera and remove the camera. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 231: Replacing An Ivs1800

    A spare IVS1800 of the same model is available and functional. Context NO TICE Videos cannot be recorded during the replacement of the IVS1800. D ANGER Do not operate with power on. Take appropriate insulation measures. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 232: Replacing A Hard Disk For The Ivs1800

    A spare hard disk of the same model is available and functional. ● Before replacing a faulty disk, ensure that the power switch on the rear panel is off and disconnect the power cable to power off the device. Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 233 Figure 6-19 Installing hard disks Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 234 Close the chassis cover, and use a PH2 screwdriver to fasten the rear screws. Figure 6-22 Closing the chassis cover Step 4 Observe the hard disk indicator to check whether the hard disk works properly. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 235: Replacing A T/H Sensor (33010516)

    FusionModule500 Smart Mini Data Center User Manual 6 O&M Follow-up Procedure If the hard disk works abnormally, contact Huawei technical support. 6.4.3.8 Replacing a T/H Sensor (33010516) Prerequisites ● A T/H sensor needs to be replaced. ● A spare T/H sensor of the same model is available and functional.
  • Page 236 Step 5 Blow smoke toward the smoke detector using a smoke pistol until the smoke detector indicator changes from blinking once every 6s to steady on. If a smoke detector fire alarm is triggered, the smoke detector is functional. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 237: Replacing An Electrode Water Sensor

    Step 2 Remove the faulty water sensor. Step 3 Place the new water sensor in the correct position. Step 4 Connect the water sensor cable connected to the ECC800-Pro to the new water sensor. ----End Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 238: Technical Specifications

    1000 m) Installation mode Installed on a concrete floor or an ESD floor Operating temperature Indoor: 0–40°C Outdoor: –20°C to +45°C Storage temperature –40°C to +70°C Storage humidity ≤ 95% RH (non-condensing) Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 239: A Equipment Derating Coefficients

    (sea level +15ºC). Table A-1 Derating coefficients of the UPS2000-G Altitude (Unit: m) Derating Coefficients 1000 1500 0.95 2000 0.91 2500 0.86 3000 0.82 3500 0.78 4000 0.74 4500 5000 0.67 Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 240: B Acronyms And Abbreviations

    Auto Transformer Switch Equipment Battery Interface Module Communication Interface Module direct current International Electrotechnical Commission miniature circuit breaker SNMP Simple Network Management Protocol surge protective device State Of Charge State Of Health Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.
  • Page 241 FusionModule500 Smart Mini Data Center User Manual B Acronyms and Abbreviations uninterruptible power system Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd.