Led Diagnostics - Emerson SolaHD SDU AC B-Series User Manual

Uninterruptible power supply
Table of Contents
6
GREEN MODE
The Green mode is only for 230V models only. By default, Green Mode Enabled. If the load level is less than
approximately 8% ~ 12%, the UPS will shut down to save battery in 3 minutes. If power is restored within 3
minutes the UPS will return to AC mode. Green Mode can be ENABLED or DISABLED by pressing the POWER
ON/OFF at start-up shown on below table.
Green Mode
Enabled
Disabled
7
REMOTE ON/OFF
Allows the user to perform remote power ON/OFF functions using a switch on terminals (non-polarized) to
toggle ON/OFF state.
To Enable the UPS, close the switch that is connected to the terminals.
To Disable the UPS, open the switch that is connected to the terminals.

7.0 LED Diagnostics

Condition
Description
BACK-UP MODE UPS is in back-up mode due
to AC Loss
Normal condition source
AC MODE
supplied by AC Mains
Load around 105% of rated
capacity
AC MODE
Load > 120% of rated c apacity
OVERLOAD
Load > 130% of rated
c apacity
Load around 105% of rated
capacity
Load > 120% of rated
BACK-UP MODE
OVERLOAD
capacity
Load > 130% of rated
capacity
LOW BATTERY
Low Battery Charge
Alarm Signal
Press Power ON/OFF button and release until "3 beeps"
Press Power ON/OFF button and release until "2 beeps"
Remote Enable/Disable of UPS
SDU-B Remote
ON/OFF Switch Wired
UPS-B
UPS-B
Remote ON/OFF Terminals: Shorted (closed) for ON, Open for OFF Non-Polarized terminals.
No external voltage is required. We recommend using stranded UTP (Unshielded Twisted Pair)
wire for connections.
LED
YELLOW
GREEN
GREEN/RED
GREEN/RED
GREEN/RED
YELLOW/RED
YELLOW/RED
YELLOW/RED
YELLOW
Table 1 Diagnostics LED/Alarms
UPS Condition/State
Switch or Terminal Condition
ON
OFF
Alarm
Slow beeping. UPS sounds until
AC utility power recovers.
No Alarm
Alarm is ON during overload (if
overload exceeds 105% of nominal
at 5mins, 120% at 10s, and 130% at
3s) and enters retry mode every
10mins, until load is removed. UPS
will not shut down.
Alarm is ON during overload (if
overload exceeds 105% of nominal
at 20s, 120% at 10s, and 130% at 3s)
and enters retry mode every
10mins, until load is removed. UPS
will not shut down.
During back-up mode when the
battery charge runs low, the UPS
beeps rapidly (ON 0.5 seconds, OFF
0.5 seconds) until the UPS shuts
down or returns to AC Mode.
SDU AC B-Series
A272-353 Rev. 1 2/2021
11 |
P a g e