First Startup With A New Program Module Or In Case Of Replacement Of Program Module - Siemens LME7 Series Manual

Burner
Hide thumbs Also See for LME7 Series:
Table of Contents
Alternately
nfo
>3 s
Alternately
Β
Alternately
Building Technologies
15.6
First startup with a new program module or
in case of replacement of program module
After 2 minutes, the unit changes to Loc 138
Basic Documentation LME7...
15 Operation via internal LED
Display shows alternately rSt and PrC.
Display shows the replacement of the program module.
Signal lamp blinks red once and yellow twice alternately.
nfo
Press
for >3 seconds to start data download from the
program module.
Signal lamp blinks yellow.
The process of 3 seconds is supported by a short flash of
the yellow signal lamp.
Note:
nfo
If you press
for <3 seconds, data download does not
start. To start the restore process again, the LME7 must be
reset by switching mains ON/OFF.
Display shows run during download (restore process) of the
program sequence.
Display shows alternately End and rSt.
Display shows the end of data exchange.
Signal lamp blinks red.
After the restore process, the unit is automatically in
the lockout position (LOC 138) and must be reset for
operation!
98/106
CC1P7105en
17.04.2018

Hide quick links:

Table of Contents
loading

This manual is also suitable for:

Lme71Lme73

Table of Contents