3.0 LOCKS AND INTERLOCKS
WARNING
Ensure the circuit breaker has been tripped, indica ng OFF,
and the main springs are fully discharged before installing
locks and interlocks.
A variety of locks and interlock accessories are available.
CAUTION : Ensure circuit breker and its accessories are always
used within their designated ra ngs.
3.1 Breaker front Facia
Circuit Breaker Security padlocking
A standard feature allowing the user to place padlocks that will
lock the breaker with it's contacts open. Any a empt to close
the breaker, either electrically or manually, is prevented whilst
the padlocks are in place. The breaker padlocking device
accepts up to three padlocks with a hasp
dimension of 3 to 8 mm
To engage the device and place padlocks :
1. Push the breaker OFF bu on un l the padlocking lever moves
and slightly protrudes from the breaker front facia. (Fig 3.1).
2. Pull out and fully extend the lever.
3. Insert the padlock(s) into the lever holes.
To disengage the locking feature, simply remove the padlocks
and push the lever back into a posi on that is ush with the
breaker front facia.
Now the breaker can be operated normally.
3.1
Fig 3.1