  • Page 1 VB 40.5 Vacuum Circuit Breaker VB 40.5真空断路器 User Manual ⽤⼾⼿册...
  • Page 3 Caution! Please read this manual carefully before installing and using the circuit breaker: The installation and use of circuit breakers must comply with the requirements of this manual. Circuit breaker should be used in accordance with the normal indoor environmental conditions. Any operation and maintenance of the circuit breaker should be carried out by professional trained full- time electrical personnel.
  • Page 4: Table Of Contents

    Contents 1. Overview ..................................1 2. Structural principle ..............................1 3. Technical parameter ..............................5 4. Propulsion mechanism ............................... 7 5. Overall dimensions ..............................8 6. Electrical wiring diagram ............................12 7. Installation, commissioning and operation ......................... 14 8. Maintenance ................................15 9.
  • Page 5: Overview

    1. Overview 1-1 General: VB 40.5 vacuum circuit breaker (hereinafter referred to as circuit breaker) is applicable to AC 50Hz and 35kV Power Systems, and can be used as protection and control equipment for industrial and mining enterprises, power plants and substations, and is applicable to frequently operated occasions.
  • Page 6 phases, but also protects each phase circuit from the influence of the external bad environment, prevents dust and foreign matters from entering the conductive circuit, and reduces the overall size of the circuit breaker. 2-2 Operating mechanism The operating mechanism of the circuit breaker is a spring energy storage mechanism. There are closing unit, opening unit composed of one or several coils, auxiliary switch, indicating device and other components in the mechanism box;...
  • Page 7 energy storage keeping block 17 energy storage latch closing interlock block handcart interlock block Fig. 2 side view of operating mechanism upper terminal vacuum chamber 22 fixed pole lower terminal 24 insulating pull rod 25 threaded rod 26 connecting plate 27 crank arm 28 connecting plate Fig.
  • Page 8 2-2-1 Energy storage The energy required for closing the circuit breaker is provided by the closing spring. Energy storage can be done either by motor or by hand with energy storage handle. Energy storage operation: it is carried out by the energy storage motor 7 fixed on the frame or by inserting the energy storage handle into the manual energy storage shaft 8 and shaking it clockwise.
  • Page 9: Technical Parameter

    2. After closing the circuit breaker, if the closing electric signal is not removed in time, the internal anti tripping controller of the circuit breaker will cut off the closing circuit to prevent multiple reclosing. 3. When the handcart type circuit breaker fails to reach the test position or working position, the handcart interlocking board 19 shall buckle the closing board and cut off the closing circuit to prevent the circuit breaker from entering the load area in the closing state.
  • Page 10 3-2 Mechanical characteristic parameters Item Unit Value Rated voltage 630/1250/1600/2000/2500/3150 18±1.0(Fixed sealing pole) Contact distance 21±2.0(Insulating cylinder) 4±1.0 Contact travel ≤2 Three-phase closing ≤2 Three-phase opening ≤3 Closing bounce time Average opening speed 1.3~1.9 Average closing speed 0.5~1.0 Opening time (rated voltage) 20~50 Closing time (rated voltage) 30~70...
  • Page 11: Propulsion Mechanism

    4. Propulsion mechanism 4-1 Cabinet entry of handcart Close the valve of the interlocking piece 2 of the pushing mechanism, operate the left and right handles 1 to position B, and push the circuit breaker handcart into the switch cabinet along the guide rail until the pins 5 on both sides correspond to the positioning holes of the switch cabinet.
  • Page 12: Overall Dimensions

    5. Overall dimensions ● Floor type - 300mm apart...
  • Page 13 ● Floor type - 440mm apart...
  • Page 14 ● Withdrawable – 275mm apart ● Fixed connection – 300mm apart...
  • Page 15 ● Fixed connection – 300mm apart...
  • Page 16: Electrical Wiring Diagram

    6. Electrical wiring diagram ● Floor type (58 core, with auxiliary contact of propulsion mechanism)
  • Page 17 ● Withdrawable (58 cores)
  • Page 18: Installation, Commissioning And Operation

    ● Fixed type (terminal) 7. Installation, commissioning and operation 7-1 When the circuit breaker is lifted from the packing box, the hook shall be hung on the lifting position with lifting mark on the circuit breaker. When moving, the upper and lower outlet arms shall not be stressed, and the circuit breaker shall not be subject to large impact and vibration.
  • Page 19: Maintenance

    Manual operation test. 8. Maintenance Maintenance must be carried out by AEG personnel or the user's personnel who are familiar with the equipment and have been trained and qualified. If the maintenance is carried out by the user's personnel, the user shall be responsible for the consequences of the repair.
  • Page 20 8-3 Disassembly and replacement of circuit breaker parts shall be carried out by AEG personnel or corresponding trained personnel, especially during reassembly, necessary adjustment shall be made. 8-4 Maintenance of circuit breaker a.
  • Page 21: Transportation And Storage

    9. Transportation and storage 9-1 When the product is transported, the circuit breaker shall be placed in a closed packing box without energy storage, and a proper amount of desiccant shall be built in. The circuit breaker shall be protected with plastic film to prevent water penetration during loading and unloading and dust intrusion during storage.
  • Page 22 Order number Product model (SAP) Over-current tripping coil (Y8) 26400056 36490042 Over-current control circuit board Closing locking electromagnet (S4) 26490381 Closing/opening control circuit board (please mention: operation voltage, whether there is anti- 26490463 tripping, whether there is locking) 26490093 Closing/opening auxiliary switch (QF) 26490090 Handcart position auxiliary switch (S8, S9) 26490580...
  • Page 23 注意安全! 在断路器安装使⽤前请仔细阅读本使⽤⼿册: 断路器的安装和使⽤必须遵守本⼿册的要求。 断路器的使⽤场合应符合⼾内正常的环境使⽤条件。 对断路器的任何操作和维护都应该由经过专业培训的专职电⽓⼈员进⾏。 禁⽌把断路器置于超出其额定参数的情况下运⾏。 必须注意断路器的任何标识。 必须保证断路器的联锁条件和⼯作规程的适⽤性和安全性。 不能在开关柜及⼆次控制回路带电的情况下从事检修⼯作。 必须确保断路器不受任何外力的冲击,否则将损坏设备。 对断路器的任何违规操作均可能损坏设备,甚⾄引起严重事故。 应把本⼿册放在可以⽅便拿到的地⽅。 应由专业⼈员负责断路器的安全管理。...
  • Page 24 目录 .概述 ..................................21 .结构原理 ................................21 .技术参数 ................................24 .推进机构 ................................26 .外形尺寸 ................................27 .电⽓接线图 ................................31 .安装、调试与操作 ..............................33 .维护与保养 ................................34 .运输与储存 ................................35 .随机文件 ................................36 .备品备件 ................................36...
  • Page 25: 结构原理

    1.概述 - 总则: . 真空断路器(以下简称断路器)适⽤于交流 Hz、 kV电力系统中,可供⼯矿企业、发电厂及 变电站等作为保护和控制设备之⽤,并适⽤于频繁操作的场合。 1-2 引⽤总则: 断路器符合以下标准: GB/T 《⾼压交流断路器》 IEC 62271-100 《⾼压交流断路器》 《⾼压开关设备和控制设备标准的共⽤技术要求》 DL/T 《 . kV⾼压真空断路器订货技术条件》 1-3 正常使⽤条件: 环境温度 最⾼温度: +40℃ 最低温度: -25℃ 最⾼日平均温度: +35℃ 环境湿度 日平均相对湿度: ≤95% 月平均相对湿度: ≤90% 日平均饱和蒸汽压: ≤2.2X10 月平均饱和蒸汽压: ≤1.8X10 地震强度: ≤8度...
  • Page 26 1 合闸弹簧 2 合分闸指示 3 分闸半轴 4 储能指示 5 计数器 6 微动开关 7 储能电机 8 ⼿动储能轴 9 电机输出轴 10 ⼩齿轮 11 ⼤齿轮 12 合闸线圈 13 合闸板 14 分闸线圈 15 过流线圈或第⼆分闸线圈 图 1 断路器操动机构正视 储能保持挚子 17 储能保持块 18 合闸联锁板 19 ⼿车联锁板 图2 断路器操动机构侧视...
  • Page 27 20 上出线座 21 真空灭弧室 22 固封极柱 23 下出线座 24 绝缘拉杆 25 螺杆 26 连板 27 拐臂 28 连板 图 3 断路器内部结构图(落地式) - - 储能 断路器合闸所需要的能量由合闸弹簧提供,储能即可以由电机电动完成,也可以使⽤储能⼿柄⼿动完 成。 储能操作:由固定在框架上的储能电机 进⾏,或者将储能⼿柄插⼊⼿动储能轴 中顺时针摇动进⾏。 电动储能时由电机输出轴 带动齿轮系统进⾏,⼿动储能时通过⼿动储能轴 带动齿轮系统进⾏。⼩齿轮转 动时,带动⼤齿轮⼀起运动,从而拉动储能弹簧进⾏储能。到达储能位置时,储能保持挚子顶住储能保持 块,使离合器分离,保持储能状态,储能指示牌显示拉簧拉伸状态,储能完成。微动开关切断储能电机供 电电源,此时断路器处于合闸准备状态。 - - 合闸 在合闸过程中,不论⽤⼿动按下“合闸”按钮或远⽅操作使合闸线圈 动作,均可使储能保持挚子转 离储能保持块,在合闸弹簧力的作⽤下,带动凸轮转动,凸轮又驱动连杆机构带动绝缘拉杆...
  • Page 28: 技术参数

    注:当断路器已处于合闸状态或选⽤合闸闭锁装置而未接通外接电源、断路器在推进过程中,或推进 机构的操作⼿柄未拔下时,均不能进⾏合闸操作。 - - 分闸 既可按"分闸"按钮, 也可接通外部电源使分闸脱扣电磁铁或过流脱扣电磁铁动作, 使分闸保持挚子与分 闸半轴解锁而实现分闸操作。 由触头弹簧和分闸弹簧储存的能量使灭弧室动静触头分离。 在分闸过程后段, 由液压缓冲器吸收分闸过程剩余能量并限定分闸位置。 连杆拉动合分指示牌显示出“O”的位置,由传动连杆拉动辅助开关切换。 - 防误联锁 断路器能提供完善的防误联锁操作功能 .断路器合闸操作完成后,合闸联锁板 转动顶住合闸板 ,在断路器未分闸时将不能再次合闸。 .断路器在合闸结束后,如合闸电信号未及时去除,断路器内部防跳控制器将切断合闸回路防⽌多次 重合闸。 .断路器在没有到达试验位置或⼯作位置时,由⼿车联锁板 扣住合闸板,同时切断合闸回路,防⽌ 断路器处于合闸状态进⼊负荷区。 .断路器在⼯作位置或试验位置合闸后,由滚轮压住推进机构,⼿车将⽆法移动,防⽌在合闸状态拉 出或推进负荷区。 .如果选⽤电⽓合闸闭锁,在⼆次控制电源未接通情况下阻⽌⼿动进⾏合闸操作。 3.技术参数 - 主要技术参数 序号 名 称 单 位 数 值 额定电压 min ⼯频耐受电压(有效值) 相间、相对地/断口:...
  • Page 29 主要技术参数(续) 序号 名 称 单 位 数 值 额定操作顺序 O- . s-CO- s-CO 分合闸电磁铁额定电压 AC: ;DC: 储能电机额定电压 AC: ;DC: 分级 级 E -M -C - 机械特性参数 参数名称 单位 参数值 序号 额定电流 ± . (固封) 触头开距 ± . (筒式) 接触⾏程(超⾏程) ± . 三相合闸不同期...
  • Page 30: 推进机构

    - 操作机构与闭锁电磁铁的技术参数 额定电压(V) 储能电机(A) 合闸线圈(A) 分闸线圈(A) 闭锁电磁铁(mA) 4.推进机构 - ⼿车的进柜 把推进机构的联锁片 的活门关好, 操作左右把⼿ ⾄位置 B, 并推进断路器⼿车沿着导轨进⼊柜体, 直到其两侧的插销 和柜体的定位孔相对应时,放开左右把⼿,使断路器⼿车固定在柜体内。操作接地联 锁⼿把 ⾄位置 A,使其处于插⼊位置。(如推进机构不带接地联锁,此步骤可以跳过) - ⼿车的推进和退出 使断路器处于分闸状态(⼿动或电动) ,把联锁片 的活门打开,插⼊操作⼿柄,可使断路器⼿车在柜 体内推进和退出。当⼿车进到⼯作位置或退到试验位置时,可听到离合器打滑的“咔嚓”声,⼿车不再移 动,此时应停⽌摇动操作⼿柄。断路器⼿车在柜体内的推进和退出应灵活并⽆明显的卡滞现象。(注意:在 断路器碰上柜体的活门机构和快到位时,推进力要明显加⼤,这属正常现象) - 合闸操作 .将⼿车推进柜内,操作左右把⼿⾄位置 A。 .分接地开关,操作接地联锁⼿把⾄位置 A。 .按下联锁片,⽤摇把顺时针转动主操作轴,使断路器推进⾄柜内⼯作位置。 .合上联锁片,合断路器,运⾏。 - 紧急分闸 开关柜在紧急情况时,紧急分闸⼿把 逆时针旋转,可使断路器分闸。 - 图示说明(⼯作位置)...
  • Page 31: 外形尺寸

    5.外形尺寸 落地式-相距300mm ●...
  • Page 32 落地式-相距 440m ●...
  • Page 33 ⼿车式-相距275mm ● 固定式-相距 300mm ●...
  • Page 34 固定式-相距 300mm ●...
  • Page 35: 电⽓接线图

    6.电气接线图 落地式(58芯,带推进机构辅助接点) ●...
  • Page 36 ⼿车式 (58芯) ●...
  • Page 37: 安装、调试与操作

    固定式 ● 7.安装、调试与操作 7-1 断路器从包装箱中起吊时,挂钩应挂在断路器上有起吊标志的起吊位置处。移动时不得使上、下 出线臂受力,同时不应让断路器受到较⼤的冲击震动。 7-2 在操作中遇到问题,先按照下表确定原因。如不能解决,请与制造厂联系,切勿⾃⾏对断路器拆 装。...
  • Page 38: 维护与保养

    3.选⽤了合闸闭锁电磁铁,而辅助电源未接通或低于技术要求 4.⼆次线路不正确 1.断路器处于合闸状态 2.推进⼿柄未完全插⼊推进孔 不能摇进摇出 3.推进机构未完全到达试验位置,致使⾆板不能与柜体解锁 4.与柜体接地联锁未解除 7-3 调试与操作中的各项⼯作应由受过专门培训、详细了解本断路器性能的⼈员进⾏。⼯作中必须考 虑相应的保护和预防措施。 ⽆故障操作前提之⼀是按GB/T 1984和IEC 60694标准相应的规定,在正常⼯作条件下使⽤断路器。 检查断路器有⽆损坏或任何其它有危害性的环境影响。若有此现象,通电前应先排除以恢复到正常 ● 的⼯作条件。 清除污垢,尤其是绝缘件表面的脏污。这些可能是由于在运输或储存过程造成的脏污会影响产品绝 ● 缘性能。 检查⼀次回路接触、⼆次回路连接和接地体的连接状态。 ● ⼿动操作试验。 ● 8.维护与保养 必须由AEG公司⼈员或对本设备熟悉并经培训合格的⽤⼾⽅⼈员进⾏维修。如由⽤⼾⽅⼈员进⾏维 修,则由⽤⼾⽅承担相应维修后果责任。 8-1 在正常使⽤期间,断路器免维护。由于断路器具有结构简单和耐⽤的特点,因此有很⻓的使⽤寿 命。维护⼯作与零部件受磨损和⽼化情况有关。为使断路器可靠地⼯作,所需进⾏地维护⼯作的间隔时间 和检修范围将取决于⼯作环境的影响、操作次数、运⾏时间以及短路电流开断的次数等诸因数。 8-2 在进⾏维护⼯作前,所有的辅助电源均必须断开且没有再送电的危险。断路器本⾝处于分闸且弹 簧未储能状态。为防⽌意外事故,在对操作机构上进⾏的各项⼯作应格外⼩心。 8-3 拆卸和更换断路器零部件,应由本公司⼈员或相应的受过培训的⼈员来实施,特别是在重新装配 期间,需做必要的调整。 8-4 断路器维护保养 a.在运⾏满2年时(从新设备投⼊运⾏开始日计)或断路器操作规定次数(25kA及以下的断路器在操作满 2000次、31.5kA断路器在操作满1500次)时需对操作结构进⾏检查:...
  • Page 39: 运输与储存

    切断储能电源,操作断路器合、分闸各⼀次以使机构释能。 ● 检查滚动或滑动轴承表面的润滑脂情况 ● 在电⽓和机械动作时检查各个元件功能的正确性。 ● 做全面外观检查。 ● b.在运⾏满5年时(从新设备投⼊运⾏开始日计)或断路器操作规定次数(25kA及以下的断路器在操作满 4000次、31.5kA断路器在操作满3000次)时需对操作结构进⾏维护: 切断储能电源,操作断路器合、分闸各⼀次以使机构释能。 ● 对支撑轴、滚动和滑动轴承等需要润滑部位重新涂抹润滑脂。 ● 在电⽓和机械动作时检查各个元件功能的正确性。 ● 检查连杆、拐臂、支杆等处安装的紧固件状况或有⽆松动现象。 ● 维护时应重点检查在运⾏中受到⼤应力作⽤的部件。 ● 如有更换零部件重新装配设备时,应更换所有的紧固件。 全面复查操作机构。 8-5 在断路器运⾏了约5年之后或当操作机构进⾏维护时,也应对断路器本体进⾏检查。尤其是检查 外观情况的同时,也需检查设备表面的污秽、受潮及腐蚀情况。⽤干布清洁绝缘件表面的灰尘,然后⽤粘 有家⽤碱性清洗剂或安全清洗剂的绸布揩去各种污秽物(应注意所使⽤的清洁剂是否适⽤于塑料和合成橡㬵 材),不得使⽤四氯化碳或三氯⼄烯去清揩。 在⼀些特殊使⽤场合或有损害的环境条件下运⾏的开关设备(如在⾼污秽和重腐蚀性⽓体的环境条件 中),上述检查⼯作的最短间隔时间应⼩于5年。 9.运输与储存 9-1 产品运输时,断路器应处于分闸且弹簧未储能的状态下装⼊封闭的包装箱内加以固定,内置适量 干燥剂。断路器应⽤塑料薄膜加以保护,以防在装卸时渗⼊⽔和在存储时侵⼊灰尘。 9-2 装卸包装箱应采⽤以下⼯具 起重机 ● 叉车 ● ⾏车 ●...
  • Page 40: 随机文件

    定期检查是否有凝露现象等不适宜储存要求的状况。 ● 10.随机文件 a. 产品合格证 b. 出厂检验报告 c. 装箱单 11.备品备件 当⽤⼾需要时,可按照下述确定所需备件,并在订货时提出,以备不时之需。 订货号(SAP) 产品型号 过流脱扣线圈(Y ) 过流线路板 合闸闭锁电磁铁(S ) 合分闸控制线路板(需注明:操作电压、有⽆防跳、有⽆闭锁) 合分闸辅助开关(QF) ⼿车位置辅助开关(S 、S ) 储能微动开关(S 、S 、S ) 位置闭锁开关( V) 位置闭锁开关( V) 合分闸线圈( V) 合分闸线圈( V) 断路器储能电机( V) 断路器储能电机( V) 断路器摇进⼿柄 机构储能⼿柄头...