ATTENTION: Only qualified personnel, which are trained and approved to install PowerFlex® 755T products and familiar with associated machinery, should plan
or implement the installation, start-up, and subsequent maintenance of the system. Failure to comply can result in personal injury and/or equipment damage.
ATTENTION: The information that is contained in this publication is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume
responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment.
A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
ATTENTION: This product contains Electrostatic Discharge (ESD) sensitive parts and assemblies. Static control precautions are required when you install these
assemblies. Component damage can result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference any
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits Required Tools Tool Description Details Allen (hex) socket wrench 4 mm Electric drill and bits (Bit sizes to meet conduit size requirements) Flat-nose screwdriver 6.4 mm (0.25 in.)
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits Frame 5 Conduit Box Installation Follow these steps to install the frame 5 conduit box and debris hood. 1. Use the pilot holes in the conduit box bottom plate to drill the required holes for control and input/output power wire conduit fittings.
Page 4
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 2. Loosen the four M4 captive screws that secure the cover to the assembly, and remove the cover. M4 (Captive) F - 6.4 mm (0.25 in.) or 4 mm hex 2.6 N...
Page 5
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 3. Place the conduit box onto the chassis of the drive, so that the conduit box flanges are located on the inside of the drive chassis.
Page 6
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 6. Insert and tighten the five M5 x 10 mm slotted-torx screws in the bottom of the conduit box to secure the bottom plate to the conduit box.
Page 7
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 8. Insert and tighten the M6 x 12 mm torx screw in the hole on the front of the conduit box to secure the front plate to the conduit box.
Page 8
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 10. Place the debris hood on the top of the chassis and tighten the four M5 captive Phillips-head screws. M5 (Captive) 3.6 N•m (32 lb•in)
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits Frame 6 Conduit Box with Debris Hood Kit (Cat. No. 20-750-CBOX1-F6) The frame 6 conduit box with debris hood kit contains the following components. Frame 6 with Conduit Box and Debris Hood Kit Installed...
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits Frame 6 Conduit Box and Debris Hood Installation Follow these steps to install the frame 6 conduit box and debris hood. 1. Use the pilot holes in the conduit box bottom plate to drill the required holes for control and input/output power wire conduit fittings.
Page 11
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 2. Loosen the eight M4 captive screws that secure the cover to the assembly, and remove the cover. M4 (Captive) F - 6.4 mm (0.25 in.) or 4 mm hex 2.6 N...
Page 12
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 3. Remove the two M8 nuts and washers from the PE ground studs on the chassis. 4. Place the two slots in the tab at the top of the conduit box onto the ground studs.
Page 13
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 7. Align the screws on the bottom plate with the holes on the conduit box and tighten the six M4 captive slotted-torx screws to secure the plate to the box.
Page 14
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 9. Align the two slots at the top of the front cover with the two tabs on the conduit box and place the cover on the box.
Page 15
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 12. Place the debris hood on the top of the chassis and tighten the four M4 captive slotted-torx screws. M4 (Captive) 3.6 N m (32 lb •...
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits Frame 5 Ground Plate Installation Follow these steps to install the frame 5 ground plate. 1. Loosen the four M4 captive screws that secure the cover to the assembly, and remove the cover.
Page 18
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 2. Insert and tighten the four M5 x 10 mm torx screws in the holes on the side panels of the chassis to secure the ground plate to the chassis.
Page 19
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 4. As required, insert the M4 slotted torx screws to secure ground wires to the ground plate. 5. As required, insert the appropriate sized cable clamps into the ground plate receptacles and secure the power wires.
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits Frame 6 Ground Plate Installation Follow these steps to install the frame 6 ground plate. 1. Loosen the eight M4 captive screws that secure the cover to the assembly, and remove the cover.
Page 22
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 2. Remove the two M8 nuts and washers from the PE ground studs on the chassis. 3. Place the two slots in the tab at the top of the ground plate onto the PE ground studs.
PowerFlex 755T Frames 5 and 6 Conduit Box with Debris Hood and Ground Plate Kits 6. As required, insert the appropriate sized clamps into the ground plate receptacles and secure the power wires. 7. Secure the cover to the chassis as shown in step 1 page 21.
Page 24
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf. Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, PowerFlex, Rockwell Automation, Rockwell Software, and TotalFORCE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.