FA Global Site http://www.mitsubishielectric.com/fa/products/lvd/lvcb/index.html Eco Changes is the Mitsubishi Electric Group’s environmental statement, and expresses the Group's stance on environmental management. Through a wide range of businesses, we are helping contribute to the realization of a sustainable society.
Page 2
Medium voltage: VCB, VCC Closing method Appearance and Product structure Power monitoring, energy management Connections Mitsubishi Electric offers a wide range of automation equipment from PLCs and HMIs to CNC and EDM machines. Accessories Compact and Modular Controllers Electronic trip relay...
• Do not use the product under the conditions with over-rated current. Otherwise, ground-fault or short circuit [7] Any other failure found not to be the responsibility of Mitsubishi Electric or that admitted not to be so by the user.
50 kA or less. The C-class has the solenoid mechanism inside its body. Specifications of AE V Series C-class compared to AE-SW Series (Existing model) Developed to meet customers’ expectation and needs.
Page 5
New Features Built-in drawout handle Without DP With DP AE V Series C-class is equipped with a built-in drawout handle as standard. Just insert a built-in drawout handle into the body after using it. Built-in drawout handle The shape of...
Product Specification Closing method Solenoid mechanism Type AED630-CV AED1000-CV AED1250-CV AED1600-CV Number of poles 3, 4 The breaker closes electrically. Rated insulation voltage (V) 1000 The following describes the closing methods. Impulse withstand voltage (kV) Uimp Rated operational voltage (V AC 50/60 Hz) 1.
Page 7
Control circuit terminal block Electronic trip relay Manual reset button OFF button ON button Padlock hook ON/OFF indicator World Super AE V Series AED1600-CV For the fixed type, lifting hooks (HP) are attached. Air circuit breaker UVT delay unit Cradle Counter (CNT)
Page 8
Connections Accessories Overview (AED630-CV to AED1600-CV) For breaker unit Connections Horizontal (HT) Vertical (VT) Front (FT) Type Auxiliary switch Standard/Low capacity type Shunt trip device Under voltage trip device Fixed type (FIX) OCR alarm FIX-HT FIX-VT FIX-FT Drawout type (DR) DR-HT DR-VT DR-FT...
Page 9
Under voltage trip device (UVT) Auxiliary switch Option Standard (LAX) / Low capacity type (LVAX) This is the device that automatically trips the breaker when the circuit voltage Option drops below the nominal voltage. This is the contact that remotely indicates the ON or OFF status of the breaker. There are 4 kinds of tripping time, INST, 0.5 s, 1.5 s, and 3 s.
Page 10
Interphase barrier (BA) For drawout type Option This device enhances the interphase insulation between the terminals of the breaker, and prevents short-circuit due to conductive objects or dust. Shorting b contact (Rear side) Cell switch It can be attached and detached easily. The interphase insulation is available for all connection methods.
Page 11
Safety shutter (SST) Operating position of drawout type Option The safety shutters cover the conductors (cradle side) and prevent contact CONNECTED position TEST position DISCONNECTED position DRAWOUT position with them when the breaker is drawn out. Safety shutter lock (SST-Lock) Both the main and control circuits The main circuit is disconnected, Both the main and control circuits...
Page 12
Electronic trip relay Power supply module Criterion for Type Rated voltage (V) Applicable voltage range (V) Alarm output power requirement (VA) 100-240 AC (50/60 Hz)/ 85-264 AC 5 output contacts 100-125 DC 85-138 DC 24-60 DC 18-72 DC 5 output contacts Feature Contact capacity (Type P3 and P4) Current (A)
Page 13
For general purpose: Type S1 Operating characteristic curve (for general purpose: Type S1) 5000 4000 3000 2000 Pre-alarm current: Ip 1000 Iu × 0.68-1.0 (step 0.04) - OVER ±10% (min) Uninterrupted current: Iu Ir × 0.8-1.0 (step 0.02) LTD pick-up 1.05 × Iu … Non pick-up 1.25 ×...
Page 14
Maximum current (A) Bar graph display Harmonics (HI) Trip cause Neutral CT (NCT) *Only use for AE V Series current (A) Option Time after tripping “HH:MM” The Neutral CT is used for ground fault protection when the 3-pole breaker is Specifications of display indication used on a 3-phase 4-wire system and for the overcurrent protection on N phase.
Page 15
Electronic trip relay circuit diagram for general use Setting procedure Push the screwdriver into the direction Prepare a small flat tipped screwdriver. Upper terminal of the arrow to open the ETR cover Electronic trip relay Trip coil Characteristic setting Side view of the flat tip ETR cover Micro controller Setting input...
Wiring diagram The following diagram shows the case that accessories are fully equipped. For the N pole, the following diagram shows the (Standard) case that the accessories are equipped on the right side. Close to reset alarm Close to ON (less than 2 m) (less than 10 m) L2 L3 N...
Outline dimensions Drawout type AED630-CV, AED1000-CV, AED1250-CV, AED1600-CV Fixed type AED630-CV, AED1000-CV, AED1250-CV, AED1600-CV (mm) (mm) Front view Side view Front view Side view Vertical terminal Front terminal Vertical terminal Front terminal Operating panel center Control circut Front face of control terminal Disconnected terminal block (M3.5 screw)
Technical information Panel cut-out, Front terminal adapter, Drawout handle, Lifting hook (HP) (mm) Panel cut-out dimensions Door frame panel cut-out dimensions Precautions for connecting Outline Panel cut-out dimensions Operating panel center Use M12 bolts, plain washers, and spring washers to connect the conductor. Clean the surface of conductor to be 8 ×...
Page 19
Deratings of Max. rated current by ambient temperature (Horizontal connection) Table 2 4. Installation conditions current capacity, and breaking capacity are derated. When installing the AE V Series air circuit breaker, refer to the Moreover, the insulation durability is also decreased owing Standard Ambient temperature...
Page 20
Discrimination table AE V Series air circuit breakers provide easy selective coordination with branch circuit breakers. For the selective coordinations, refer to the following table. 230 V AC sym kA 440 V AC sym kA AED-CV AED-CV Main circuit breaker...
Ordering information World Super AE V series (C-class) World Super AE V series (C-class) Air Circuit Breaker and Switch Disconnector Air Circuit Breaker and Switch Disconnector Customer name: Order ref no: Quantity: Customer name: Order ref no: Quantity: To indicate customer’s choices, please check the applicable square boxes To indicate customer’s choices, please check the applicable square boxes...
Page 22
+86-755-2399-8272 China Mitsubishi Electric Automation (China) Ltd. GuangZhou Branch Rm.1006, A1 Times E-Park, No.276-282, Hanxi Road East, Zhongcun Street, Panyu Distric, Guangzhou, China 510030 +86-20-8923-6730 Mitsubishi Electric Automation (China) Ltd. ChengDu Branch 1501-1503, 15F, Guang-hua Centre Building-C, No.98 North Guang Hua 3th Rd Chengdu, China 610000 +86-28-8446-8030 Mitsubishi Electric Automation (Hong Kong) Ltd.