Section 1: Product Overview; Ul 864 Compliance; 1: Products Subject To Ahj Approval; 2: Programming Features Subject To Ahj Approval - Honeywell Notifier LCD2-80 Instruction Manual

Liquid crystal display
Hide thumbs Also See for Notifier LCD2-80:
Table of Contents

Section 1: Product Overview

The LCD2-80 alphanumeric display module is an ancillary device used by
Notifier fire alarm control panels including NCA-2, NFS-320, NFS2-640,
and NFS2-3030. The product operates in Terminal mode, where it acts as
a Display Interface.
NOTE:The LCD2-80 should not be used as a primary display in
Canada.
NOTE:The LCD2-80 should not be used as a primary display for
releasing service.

1.1 UL 864 Compliance

1.1.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL
864 9th Edition.
The following products have not received UL 864 9th Edition certification
and may only be used in retrofit applications. Operation of the LCD2-80
with products not tested for UL864 9th Edition has not been evaluated and
may not comply with NFPA 72 and/or the latest edition of UL 864. These
applications will require the approval of the local Authority Having
Jurisdiction (AHJ).
1.1.2 Programming Features Subject to AHJ Approval
This product incorporates field-programmable software. The features
and/or options listed below must be approved by the local AHJ.
This product incorporates field-programmable software. In order for the
product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Program feature
or option
6
• NCA
• NFS-640
• AFP-300/400
Piezo
Enable/Disable
LCD2-80 Instruction Manual — P/N 53242:A 08/18/2009
• AFP-200
• AFP-1010
• AM-2020
Permitted
Possible
in UL 864
settings
(Y/N)
N
SW3-2 ON =
Piezo Disabled
SW3-2 OFF =
Piezo Enabled
Settings
permitted
in UL 864
SW3-2 OFF =
Piezo Enabled