Fujitsu Super High Power Series Design & Technical Manual page 70

Split type
Table of Contents
• Flow setpoint limitation
It is possible to assign a lower limitation to the cooling flow temperature.
The limitation line will be defined by two reference points. In addition, the resulting flow setpoint
will have a lower limitation and may not be less than 5°C.
– Flow temperature setpoint minimum at OT 25°C: Determines the lowest flow temperature for
a composite outdoor temperature of 25°C.
– Flow temperature setpoint minimum at OT 35°C: Determines the lowest flow temperature for
a composite outdoor temperature of 35°C.
WARNING
If no outdoor temperature is available, the controller will use the "Minimum flow setpoint at OT
= 35°C" parameter.
3-5. Cooling circuit 1 functions
Line
923
Flow temperature setpoint minimum at OT 25°C
924
Flow temperature setpoint minimum at OT 35°C
Flow temperature
setpoint
923
924
25
°C
Function
Flow temperature
setpoint
35
°C
- (03-26) -
Composite
OT
3. Function table