Correcting Circuit Diagrams - Siemens 8DJH Installation And Operating Instructions Manual

Medium-voltage switchgear
Table of Contents
500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05
Availability of lateral wiring ducts in the cable compartment
Panel type
R, K
Lateral wiring
left
duct
Panel without
on request
current
transformers
Panel with current
on request
transformers
The terminal strips of the secondary equipment supplied are assigned to the associated
operating mechanisms or feeders. For information about the external connection, see the
supplied circuit diagrams.
➭ Switch off auxiliary voltage.
➭ Remove the front plate.
➭ Connect the customer wiring ⑦ to the terminal strip ⑥ or directly to the equipment
terminals (e.g. CAPDIS S2+, short-circuit indicators) according to the circuit diagrams, and
lay it cleanly.
➭ If available, use the wiring duct ① on the operating mechanism box and the lateral wiring
ducts ② .
- Lead the secondary wires of the current transformers and voltage transformers through
steel mesh tubes or steel tubes in a shielded way into a lateral wiring duct.
- Earth the steel mesh tubes or steel tubes with metal cable straps.
➭ Avoid extra-long secondary wires or lay them in the wiring ducts ① and ② or the fixing
duct ⑤ in a meandering pattern.
Fig. 52:
Secondary wires laid in a meandering pattern
➭ Wire routing to the side is possible through the cut out cap ③ .
➭ For wire routing from below, use screened cable plugs.
➭ Do not switch on auxiliary voltage yet.
13.7

Correcting circuit diagrams

➭ Document any modification due to installation.
➭ Document the modifications in the circuit diagram.
➭ Send documented modifications to the regional Siemens representative.
T
right
left
on request
partially
occupied
partially
occupied
L
right
left
yes
yes
partially
occupied
Installation
right
yes
partially
occupied
75/121