Error Code [6607] Error Source Address = Lossnay (Lc) - Mitsubishi Electric PUHY-M200YNW-A1 Service Handbook

Table of Contents
[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
7-8-11

Error Code [6607] Error Source Address = LOSSNAY (LC)

1. Error code definition
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. Cause, check method and remedy
Error display
ME remote controller (RC), MA remote controller (MA)
Types of refrigerant systems
Single refrigerant system
Troubleshooting problems for
LOSSNAY units
(1) Troubleshooting problems for LOSSNAY units
(1)
Incidental cause
(2)
The power source of LOSSNAY has been shut off.
(3)
When the address of LOSSNAY is changed in the middle
of the operation
(4)
Faulty or disconnected transmission wiring of LOSSNAY
(5)
Disconnected connector (CN1) on LOSSNAY
(6)
Controller failure of LOSSNAY
BS_07_E
Grouped operation of multiple
refrigerant systems
Troubleshooting problems for
LOSSNAY units
&
Troubleshooting problems for
all units (A)
Cause
Check method and remedy
1)
Turn off the power source of LOSSNAY and turn it
on again.
2)
If the error is accidental, it will run normally.
If not, check the causes (2) - (6).
69