Coil Removal Instructions - Mitsubishi Electric PUHY-M200YNW-A1 Service Handbook

Table of Contents
[8-8 Troubleshooting LEV, FCV Problems ]
8-8-5

Coil Removal Instructions

(1) Outdoor unit LEV (LEV1, LEV4, and LEV9)
1) LEV component
As shown in the figure, the outdoor LEV is made in such a way that the coils and the body can be separated.
2) Removing the coils
Fasten the body tightly at the bottom (Part A in the figure) so that the body will not move, then pull out the coils toward the
top.If the coils are pulled out without the body gripped, undue force will be applied and the pipe will be bent.
3) Installing the coils
Fix the body tightly at the bottom (Part A in the figure) so that the body will not move, then insert the coils from the top, and
insert the coil stopper securely in the pipe on the body.
If the coils are pushed without the body gripped, undue force will be applied and the pipe will be bent. Hold the body when
pulling out the coils to prevent so that the pipe will not be bent.
32
- chapter 8
Coils
Stopper
Lead wire
Part A
Part A
Body
BS_08_E