Honeywell Notifier ACPS-610/E Manual page 31

Addressable charger/power supply
Table of Contents
Programming the ACPS-610
Label
For greater ease of identification, you may create a label for each power supply. Labels may
have a maximum of 40 characters.
Battery Charger
Choose the appropriate battery charger current for the system's battery capacity. Refer to
Section 5.2, "Calculating the Battery Requirements", on page 49 for more information on
determining your system's battery capacity.
There are three charger current options. Select
Select
supply will not be connected to any batteries or when the batteries will be powered by an
external charger (See page 23).
NOTE: When the battery charger is disabled, the power output continuous current is 2.5 Amps.
ACPS-610/E Manual — P/N 53018:A1 07/31/2007
Figure 3.4 PK-PPS: Label
Figure 3.5 PK-PPS: Battery Charger
to charge 56 to 200 AH batteries. Select
5A C
HARGE
Configuration and Programming
2A C
to charge 12 to 55 AH batteries.
HARGE
D
C
ISABLE
HARGER
when the power
31